Contattore CA ABB A185-30-11-80

Ordine n.: 1SFL491001R8011,Codice SA: 85364900 ✅ Model Code Explanation A185: Dimensioni del telaio, AC-3 rated current 185A @400V 30: 3 normally open main poles, 0 normally closed main poles (3-palo) 11: Auxiliary contacts 1NO + 1NC 80: Coil code → AC220~230V 50Hz / AC230~240V 60Hz ✅ Key Electrical Parameters Main circuit rated voltage: 690V (CEI), UL ...

  • Dettagli del prodotto

Ordine n.: 1SFL491001R8011,Codice SA: 85364900

✅ Model Code Explanation

A185: Dimensioni del telaio, AC-3 rated current 185A @400V

30: 3 normally open main poles, 0 normally closed main poles (3-palo)

11: Ausiliario contacts 1NO + 1NC

80: Coil code → AC220~230V 50Hz / AC230~240V 60Hz

✅ Key Electrical Parameters

Main circuit rated voltage: 690V (CEI), UL 600V

AC-3 (Carico del motore):

380/400V: 185UN, for 90kW motor

690V: 170UN, for 132kW motor

AC-1 (Carico resistivo): 275A @690V (40℃)

Corrente termica convenzionale Ith: 275UN

Tensione di isolamento Ui: 1000V; Tensione di tenuta ad impulso Uimp: 8kV

Vita meccanica: 5 milioni di operazioni; Vita elettrica AC-3: massimo 300 operazioni/ora

Corrente di breve durata: 2000A for 1s; 1500A for 10s

✅ Coil Parameters (220VCA)

Potenza di spunto: 550VA (50Hz) / 600VA (60Hz)

Sealed holding power: 35VA (50Hz) / 40VA (60Hz), holding power consumption 12.5W

Coil operating range: 0.85~1.1×Uc, max ambient temperature 70℃

✅ Wiring & Dimensioni

Main circuit copper cable: 6~185mm²; Aluminium cable 25~150mm²; Wiring torque 18N·m

Dimensione complessiva: W111.5 × D160 × H196 mm, Net weight 2.9kg

Protezione: Coil terminals IP20, main terminals IP00

✅ Replacement Information (Importante)

A185 belongs to the old A series, interrotto; Direct upgrade replacement model: AX185-30-11-80 (Serie AX, same rating, same coil, drop-in replacement)

✅ Optional Accessories

Relè termico: TA200DU (per la gamma 185A)

Blocchi di contatti ausiliari: CA5, CAL5 series

Soppressore di sovratensioni, interblocco meccanico, barriera di fase, terminal protective cover

Confronto: ABB A185-30-11-80 VS AX185-30-11-80

Suffisso -80 same definition: AC220~230V 50Hz / AC230~240V 60Hz; Mounting hole position, main terminal layout and auxiliary contact definition are fully compatible, direct on-site replacement

ArticoloA185-30-11-80 (Old A series, Interrotto)AX185-30-11-80 (New AX series, Attivo)Osservazioni
Ordine n.1SFL491001R80111SFL491074R8011Different part numbers, do not mix for ordering
Stato del prodottoInterrotto, stock consumption onlyProduzione di massa, available from stockOfficial recommended upgrade replacement
Configurazione del contatto principale3 NESSUN polo principale3 NESSUN polo principaleIdentico
Contatti ausiliari incorporati1NA+1NC1NA+1NCIdentico
AC-3@400V185UN / 90kW185UN / 90kWSame motor capacity
Conventional thermal current Ith @40℃275UN250UNA185 has larger margin for AC-1 resistive loads
Tensione di isolamento Ui1000V (CEI)690V (CEI)A185 supports up to 1000V applications; AX rated max 690V
Impulse withstand Uimp8kV8kVIdentico
Short-time withstand Icw (1S)2000UN1800UNA185 has slightly higher short-circuit withstand capability
Dimension W×H×D111.5 × 196 × 160 mm111.5 × 196 × 162.3 mmStessa larghezza & altezza, only 2.3mm deeper, no impact on mounting
Peso netto2.9 kg3.2 kgAX with optimized housing & magnetic circuit, slightly heavier
Vita meccanica5 milioni di operazioni5 milioni di operazioniIdentico
Max AC-3 operation frequency300 ops/hour300 ops/hourIdentico
Specifica della bobinaAC coil 220~230V 50HzAC coil 220~230V 50HzSame code -80; spunto & holding power close
MontaggioGuida DIN + fissaggio a viteSame mounting layoutDirect swap, no cabinet drilling or busbar modification
Compatible thermal relayTA200DUTA200DUThermal relay interchangeable
AccessoriCA5, CAL5 aux blocks, VM interlock, barriera di faseCompatible with VM, CA5, CAL5Most accessories compatible; few new accessories only for AX
OrigineEarly Sweden, later domestic madeMainly domestic madeAX is optimized domestic version
CertificazioneCCC, ULCCC, ULShared UL file, mutually recognized
Design featureClassic A-series magnetic system, thicker silver contactOptimized arc chamber, basso rumore, anti-chatter, conservative temperature rise controlAX preferred for continuous long-run & low-noise cabinet requirements

⚠️ Critical Replacement Notes

  1. Motor load AC-3 (90kW): No impact, sostituzione diretta
  2. Long-term AC-1 resistive load near 250A: Evaluate carefully; A185 Ith=275A provides larger margin
  3. Circuit voltage >690V: AX is not suitable, non può sostituire
  4. Extra 2.3mm depth: Check clearance if contactor is fitted tight against cable trunking or door plate
  5. Strategia dei pezzi di ricambio: New projects specify AX185 only; A185 only for emergency maintenance with existing stock
  6. This list applies to Axxx-30-11-80 (3-palo, built-in 1NO+1NC auxiliary, Bobina AC220V, discontinued old A series); suffisso -80 = 220VAC coil
  7. AX replacement: AXxxx-30-11-80, official direct upgrade for A series
  8. Comparison basis: AC-3 @400V motor duty; 220Bobina V, built-in 1NO+1NC for Schneider LC1D and Siemens 3RT5/3RT6
  9. Nota: Only electrical equivalent rating, not mechanically interchangeable; fori di montaggio, busbar and accessories are not compatible; HS code unified 85364900
  10. ABB Old A Series Contactor List (Interrotto, 30-11-80, 220VCA)
ModelloAC-3@400VMotor kWOrdine n.AX Replacement ModelAX Order No.Compatible Thermal Relay
A9-30-11-809UN41SBL141001R8011AX09-30-11-801SBL141074R8011TA25DU
A12-30-11-8012UN5.51SBL151001R8011AX12-30-11-801SBL151074R8011TA25DU
A16-30-11-8016UN7.51SBL161001R8011AX18-30-11-801SBL161074R8011TA25DU
A26-30-11-8026UN111SBL241001R8011AX25-30-11-801SBL241074R8011TA25DU
A32-30-11-8032UN151SBL291001R8011AX32-30-11-801SBL291074R8011TA42DU
A40-30-11-8040UN18.51SBL321001R8011AX40-30-11-801SBL321074R8011TA42DU
A50-30-11-8050UN221SBL351001R8011AX50-30-11-801SBL351074R8011TA75DU
A63-30-11-8063UN301SBL361001R8011AX65-30-11-801SBL361074R8011TA75DU
A75-30-11-8075UN371SBL371001R8011AX80-30-11-801SBL371074R8011TA75DU
A95-30-11-8095UN451SBL391001R8011AX95-30-11-801SBL391074R8011TA110DU
A110-30-11-80110UN551SBL401001R8011AX115-30-11-801SBL401074R8011TA110DU
A145-30-11-80145UN751SFL461001R8011AX150-30-11-801SFL461074R8011TA200DU
A185-30-11-80185UN901SFL491001R8011AX185-30-11-801SFL491074R8011TA200DU
A210-30-11-80210UN1101SFL501001R8011AX205-30-11-801SFL501074R8011TA200DU
A260-30-11-80260UN1321SFL521001R8011AX260-30-11-801SFL521074R8011TA450DU
A300-30-11-80300UN1601SFL541001R8011AX300-30-11-801SFL541074R8011TA450DU

Osservazione: A series also includes A370, A400, A500 larger frames, rarely used for general projects. A series is different from AF series (AF = wide-voltage coil type, not included here)

  1. Cross-Brand Equivalent Rating Table (AC-3 400 V, 220Bobina V, 1NO+1NC incorporato)
ABB Old AABB New AXSchneider TeSys D LC1DSiemens SIRIUS 3RT5Motor kW @400V
A9-30-11-80AX09-30-11-80LC1D09M7C3RT6023-1AN204
A12-30-11-80AX12-30-11-80LC1D12M7C3RT6024-1AN205.5
A16-30-11-80AX18-30-11-80LC1D18M7C3RT6025-1AN207.5
A26-30-11-80AX25-30-11-80LC1D25M7C3RT6026-1AN2011
A32-30-11-80AX32-30-11-80LC1D32M7C3RT6027-1AN2015
A40-30-11-80AX40-30-11-80LC1D40M7C3RT5034-1AN2018.5
A50-30-11-80AX50-30-11-80LC1D50M7C3RT5035-1AN2022
A63-30-11-80AX65-30-11-80LC1D65M7C3RT5036-1AN2030
A75-30-11-80AX80-30-11-80LC1D80M7C3RT5044-1AN2037
A95-30-11-80AX95-30-11-80LC1D95M7C3RT5045-1AN2045
A110-30-11-80AX115-30-11-80LC1D115M7C3RT5046-1AN2055
A145-30-11-80AX150-30-11-80LC1D150M7C3RT5054-1AN2075
A185-30-11-80AX185-30-11-80LC1D170M7C3RT5056-1AN2090
A210-30-11-80AX205-30-11-80LC1D205M7C3RT5064-1AN20110
A260-30-11-80AX260-30-11-80LC1D245M7C3RT5065-1AN20132
A300-30-11-80AX300-30-11-80LC1D300M7C3RT5066-1AN20160
  1. Promemoria importanti per la sostituzione
  2. A → AX is the only drop-in compatible upgrade: Same mounting pitch, terminal layout and auxiliary contact logic; no busbar modification required
  3. Schneider LC1D and Siemens 3RT5: Only electrical equivalent, not mechanically interchangeable. Guida DIN, fori di montaggio, terminal spacing and thermal relay interfaces are incompatible
  4. Coil code rules (common for A & ASCIA):

80: AC220~230V 50Hz / 230~240V 60Hz

84: AC110~120V

83: AC48V

85: AC380~400V

  1. If you need other coil voltages (per esempio. -84 for 110V), I can export a full list with -84 part numbers
  2. Thermal relays: TA series is ABB dedicated. Schneider LRD and Siemens 3RU cannot clip directly onto A / AX contactors

Old ABB A series: Larger contact margin, higher short-circuit withstand, rated up to 1000V insulation; suitable for heavy duty, AC-4 frequent reversing, high voltage and high-reliability legacy equipment. Drawbacks: interrotto, scarce stock, higher coil noise, shrinking accessory ecosystem.

SchneiderLC1D (TeSys D): Rich accessory portfolio, wide coil options, stable stock, costo competitivo. Optimized for standard AC-3 motor duty, OEM mass production, HVAC, elevators and standardized automation projects. Lower overload margin for extreme heavy shock loads.

Application Scenario Difference between Old ABB A series and Schneider LC1D

✅ Preferred applications for Old ABB A series

  1. Riparazione & overhaul of legacy original panels (old ABB packaged cabinets, compressori d'aria di grandi dimensioni, estrusori, carta & metallurgy lines; drawing specification locked to A series, no busbar / cabinet modification allowed)
  2. AC-4 frequent reversing, jogging, heavy shock loads: montacarichi, gru, frantoi, roller tables, extruder main motors. Thicker silver contacts, higher thermal margin and superior 1s short-time withstand against current surges.
  3. 690V motor circuits, high-power fans/pumps, high AC-1 resistive loads: Ui=1000 V, higher Ith rating, suitable for continuous full resistive loading such as heating elements, furnace banks and bus transfer.
  4. Process-critical equipment requiring high short-circuit withstand and Type 2 coordination: Production lines where contact welding is unacceptable.
  5. Integrated ABB motor control packages: Matched with ABB MCB, Tmax MCCB and TA thermal relays for factory-tested protection coordination.

❌ Not recommended for A series

Nuovi progetti, mass OEM, budget ristretto, heavy custom accessory requirements, stable lead time demand. A series is discontinued with rising premium and shrinking stock.

Weakness: Audible coil noise relatively high; fewer accessory choices vs LC1D; large frame stock volatile.

✅ Preferred applications for Schneider LC1D (TeSys D)

  1. Nuovi progetti, OEM batch equipment, standard control cabinets: Linee di trasporto, macchine per l'imballaggio, general fans & pompe, HVAC chillers. Good versatility, stable supply and favorable bulk pricing.
  2. Ascensore, crane auxiliary circuits, door motors, freno & star-point control: Mature industry adoption, numerosi contatti ausiliari, interblocchi meccanici, timer blocks and mirror NC contacts.
  3. Solutions requiring complex accessory combinations: Interblocco meccanico, pneumatic timer, soppressore di sovratensioni, extra auxiliary blocks, reversing contactor sets and star-delta modules. TeSys D has the broadest accessory range among the three brands.
  4. Wide coil selection demand: AC24V, DC24V, DC110V, wide voltage coils, ideal for direct PLC DC output driving.
  5. Export equipment with multi-certification requirements: UL, CSA, marine approvals widely available.
  6. Standard AC-3 duty, operation frequency ≤300 times/hour, without frequent jogging or heavy surges for general motors.

❌ Not recommended for LC1D

Continuous operation above 690V

High-frequency AC-4 heavy duty with repeated current surges (lower contact margin than old A series at same rating)

Direct replacement into legacy ABB cabinets (requires rework of mounting, busbars and thermal relay interface)

Tabella comparativa

ArticoloABB Old A SeriesSchneiderLC1D
Load PreferenceAC-4, jogging, retromarcia, shock loads, high AC-1 resistive, 690V circuitsStandard AC-3 motor, general fan/pump, HVAC, elevator, trasportatore
Forza fondamentaleOversized contact margin, elevata tenuta al cortocircuito, 1000Isolamento V, matched ABB protection suiteMassive accessory library, full coil portfolio, stable stock, competitive bulk price
Stato della fornituraInterrotto, residual stock onlyActive mainstream product, stable lead time; largest frames gradually phased out
Cabinet RetrofitDirect swap with AX; first choice for old ABB cabinet maintenanceNot drop-in; high modification cost
Project FitManutenzione dell'eredità, critical heavy-duty process machinesNew panel build, OEM mass production, standard cabinets, attrezzature per l'esportazione
Livello di rumoreRelatively highModerare, newer D variants improved
EcosistemaTA thermal relay, CA5 auxiliary blocks, limited accessoriesLRD thermal relay, full LA accessory range, ready reversing & star-delta kits

Guida alla selezione rapida

Old ABB cabinet repair, crane/crusher frequent reversing, 690V motor, no busbar change → Prefer A stock or AX

New cabinet, mass OEM, elevator/HVAC, reversing/star-delta, budget focus, stable supply → LC1D

Heavy shock loads and long-term stocking: Avoid A on new projects; choose AX. LC1D if budget limited and margin acceptable.

Distinzione importante: AX is the compatible upgrade for A (stessa impronta, conservative performance de-rating). LC1D is only electrically equivalent, not mechanically interchangeable.

I can provide AC-4 derating margin recommendation for A, AX and LC1D if you require.