ABB-MCCB-XT6S-3P-800 - Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari

interruttore automatico/

ABB-MCCB-XT6S-3P-800

Model Code Interpretation (ABB SACE Tmax XT Series) Code Segment Description Details ABB‑MCCB Brand & Type ABB Molded Case Circuit Breaker XT6S Series & Rating XT6 series (800A frame), S = standard breaking capacity (22IL). Also available: L = high (50IL), H = ultra‑high (65IL) 3P Number of Poles 3‑pole, for three‑phase circuit protection 800 ...

  • Dettagli del prodotto

Model Code Interpretation (ABB SACE Tmax XT Series)

Code SegmentDescrizioneDetails
ABB‑MCCBMarca & TipoInterruttore automatico scatolato ABB
XT6SSerie & RatingXT6 series (800A frame), S = standard breaking capacity (22IL). Also available: L = high (50IL), H = ultra‑high (65IL)
3PNumber of Poles3‑pole, for three‑phase circuit protection
800Corrente nominaleRated operational current 800A; adjustable range varies by trip unit type
Complete Model Examples1SDA100740R1XT6S 800 TMA 800‑8000 3p F F (Thermal‑magnetic trip)XT6S 800 EkipDip LS/I 800A 3p F F (Electronic trip)
1SDA100741R1
  1. Parametri tecnici fondamentali (XT6S 800A 3P Standard Configuration)
Categoria dei parametriSpecificaOsservazioni
Corrente del fotogramma800UNSuitable for rated current settings from 630A to 800A
Rated Operational Voltage690V e, 750A DCComplies with IEC 60947‑2
Rated Insulation Voltage1000VEnsures safe insulation performance
Rated Impulse Withstand Voltage8kVSurge voltage immunity
Capacità di interruzioneIcu = 22kA @ 400VType S standard breaking capacity, for general industrial environments
Ics = 11kA @ 400V (50% terapia intensiva)
Mounting TypeFisso (F) / Plug‑in (P) / Drawer (D)Standard: Fisso (F); other types available on request
Connection TypeCollegamento frontale (F) / Rear connection (R)Standard: Collegamento frontale (F), easy for panel installation and maintenance
Ingress ProtectionIP30Complies with EN 60529; dust‑protected, finger‑protected
Operating Temperature-25℃ ~ +70 ℃Standard range; derating required above 40℃
  1. Trip Unit Types & Funzioni di protezione (Key Configuration Differences)
  2. Thermal-Magnetic Trip Unit (TMA)

Funzioni di protezione: Protezione da sovraccarico (l) + instantaneous short-circuit protection (IO)

Current Settings: Overload 0.8-1.0×In (640-800UN), instantaneous 4000-8000A (5-10×In)

Application: Simple power distribution systems, no complex settings required, conveniente

Modello completo: XT6S 800 TMA 800-8000 3pFFF (1SDA100740R1)

  1. Electronic Trip Unit (EkipDip LS/I)

Funzioni di protezione: Adjustable overload (l) + short-time delay short-circuit (S) + instantaneous short-circuit (IO) protection

Current Settings: L = 0.4-1.0×In (320-800UN), S = 1.0-10×In (800-8000UN), I = 5-10×In (4000-8000UN)

Additional Features: Supports remote control, indicazione di guasto, communication expansion (with Ekip Com module)

Application: Complex power distribution systems requiring precise protection settings; suitable for motors and transformers

Modello completo: XT6S 800 EkipDip LS/I 800A 3p F F (1SDA100741R1)

  1. Caratteristiche principali & Advantages (XT6S Series)
  2. Design modulare: Interchangeable thermal-magnetic / electronic trip units; 3 breaking capacity levels for flexible system matching
  3. Installation Flexibility: Fisso, plug-in, and drawer mounting; front/rear connection options to save panel space
  4. Sicurezza & Reliability: UL 100% rated, IEC certified; mechanical life 20,000 operazioni, electrical life 5,000 operazioni
  5. Smart Expansion: Electronic trip versions support Ekip Com modules for Profinet, EtherNet/IP and other protocols
  6. Eco-Design: Conforme alla direttiva RoHS, free of hazardous substances, high recyclability
  7. Manutenzione facile: Modular components enable quick replacement and reduced downtime
  8. Complete Model Matrix (XT6S 800A 3P Full Configurations)
Trip TypeCapacità di interruzioneModello completo (Order Code)
Thermal‑Magnetic (TMA)S (22IL)1SDA100740R1XT6S 800 TMA 800‑8000 3p F F
Thermal‑Magnetic (TMA)S (22IL)1SDA102846R1XT6S 800 TMA In=800A 3p F F UL (UL certified)
Elettronico (EkipDip)S (22IL)1SDA100741R1XT6S 800 EkipDip LS/I 800A 3p F F
Elettronico (EkipM)S (22IL)1SDA100747R1XT6S 800 EkipM Dip I 800A 3p F F (Motor protection)
Elettronico (EkipG)S (22IL)1SDA102847R1XT6S 800 EkipG Dip LS/I 800A 3p F F (Advanced protection)
  1. Applicazioni & Raccomandazioni per la selezione

Applicazioni tipiche

Main power distribution in industrial plants (secondary protection for 630-800kW transformers)

Large motor control centers (MCC), protecting 75-90kW three-phase motors (parallel groups)

UPS output protection in data centers

Main distribution boards in commercial buildings

Inverter output protection in PV power stations

Selection Guidelines

  1. Abbinamento del potere di interruzione: Select S/L/H versions based on system short-circuit current
  2. Trip Selection: Magnetotermico (TMA) for simple distribution; electronic (Ekip) for complex systems
  3. Mounting Type: Fixed for new installations; plug-in/drawer for frequent maintenance
  4. Rated Current Setting: Match total load current; recommended 1.1-1.2× load current
  5. Environmental Adaptation: No derating at -10℃~+40℃; derate 1% per °C above 40℃
  6. Modelli alternativi & Brand Comparison (Market Reference 2026)

ABB Same-Series Alternatives

Alternative ModelMain DifferenceApplication
XT6L 800 3PHigher breaking capacity 50kASystems with high short‑circuit current
XT6H 800 3PUltra‑high breaking capacity 65kAIndustrial busbars, Isc > 50IL
XT6S 630 3PSmaller frame current 630ALoad current ≤ 630A

Other Brand Alternatives

MarcaAlternative ModelEquivalent Breaking CapacityPrice Comparison
SchneiderNSX630N‑800A 3P25IL (similar to S type)5–8% lower than ABB
Siemens3VA6880‑6EL32‑0AA025IL (similar to S type)Comparable to ABB, richer smart functions
EatonZM800M3‑V080025IL (similar to S type)3–5% lower than ABB
CintoNM1‑800S/330025IL (similar to S type)30–40% lower than ABB, conveniente
  1. 2026 Market Price Reference (RMB, 13% VAT included)
ConfigurationPremier Distributor PriceGeneral Distributor PriceBulk Price (≥5 units)Osservazioni
Thermal‑Magnetic (TMA)18,000–22,00016,000–20,00015,000–18,0001SDA100740R1
Elettronico (EkipDip)22,000–26,00020,000–24,00019,000–22,0001SDA100741R1
Elettronico (EkipM)24,000–28,00022,000–26,00021,000–24,0001SDA100747R1 (Motor protection)
Price Factors• Channel: Authorized distributors offer stable pricing; unauthorized channels 10–15% cheaper but no warranty
• Lead time: In stock +3–5%; 4–6 week lead time at better prices
• Services: Installation support +500–1000 RMB; 3‑year extended warranty +8–10%
  1. Installazione & Maintenance Notes
  2. Installation Environment

Temperatura operativa: -10℃ ~ +40 ℃ (derate 1% per °C above 40℃)

Umidità relativa: ≤95%, non-condensing

Altitudine: ≤2000m (derate above 2000m)

  1. Specifiche di cablaggio

Conductor size: ≥185mm² copper cable for sufficient current carrying capacity

Requisito di coppia: Main terminal bolt torque 70Nm for reliable connection

  1. Maintenance Intervals

Routine inspection: Once monthly, check appearance and tightness

Periodic maintenance: Once yearly, clean, test trip functions, verify ON/OFF performance

  1. Selection Summary
  2. Load Evaluation: Select 800A rated current based on total three-phase current, within frame limit
  3. Short-Circuit Analysis: Calculate system short-circuit current to choose S/L/H breaking capacity
  4. Protection Requirements: Thermal-magnetic for basic distribution; electronic for precise protection and monitoring
  5. Installation Conditions: Choose mounting/connection based on panel space and maintenance needs
  6. Budget Consideration: Balance cost and reliability; electronic trip units recommended for critical circuits

ABB MCCB Model List & Order Codes

  1. Overview of ABB MCCB Series

ABB molded case circuit breakers mainly include two series: Tmax XT Series (high-end industrial, SACE Tmax XT1-XT7) and Formula Series (economic, Formula A1-A3), covering 16A-1600A for various applications.

  1. Model Naming Rules (Tmax XT Series Example)
PositionCodeDescrizioneOptions
1XT[1–7]Serie & Dimensioni del telaioXT1(160UN), XT2(160UN), XT3(250UN), XT4(250UN), XT5(630UN), XT6(1000UN), XT7(1600UN)
2C/N/L/H/MBreaking Capacity ClassC=15kA, N=25kA, L=36/50kA, H=65kA, M=100kA
3NumberCorrente del fotogramma160/250/630/800/1000/1200/1600UN
4TMD/TMA/Ekip…Trip TypeTMD = Thermal‑magnetic (distribution)
TMA = Thermal‑magnetic (motor)
EkipDip = Basic electronic
EkipC = Advanced electronic
5Number/RangeCorrente nominale / Setting Rangee.g. 800‑8000 (thermal‑magnetic), 800UN (electronic)
63P/4PPoli3P = Three‑phase, 4P = Three‑phase + N
7F/P/DMontaggioF=Fixed, P=Plug‑in, D=Drawer
8F/RConnectionF=Front, R=Rear
91SDA…R1Official Order CodeABB standard order number
  1. Tmax XT Series (SACE Tmax XT1-XT7) Model List & Order Codes
  2. XT1 Series (Frame 160A, 16-160A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT1C 160 TMD R16‑160 FF 3P1SDA067393R115ILThermal‑magnetic (dist)16‑160A3PFixed/Front
XT1N 160 TMD R100 FF 4P1SDA067461R125ILThermal‑magnetic (dist)100UN4PFixed/Front
XT1H 160 TMA R125‑1250 FF 3P1SDA067462R165ILThermal‑magnetic (motor)125UN3PFixed/Front
XT1L 160 EkipDip LS/I R160 FF 3P1SDA067463R150ILElettronico160UN3PFixed/Front
  1. XT2 Series (Frame 160A, Premio)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT2N 160 TMD R63 FF 3P1SDA100730R125ILThermal‑magnetic (dist)63UN3PFixed/Front
XT2L 160 EkipC LSIG R100 FF 3P1015286950ILAdvanced Electronic100UN3PFixed/Front
XT2H 160 EkipM I R125 FF 3P1SDA100735R165ILMotor Electronic125UN3PFixed/Front
XT2N 160 TMA R160‑1600 FF 4P1SDA100736R125ILThermal‑magnetic (motor)160UN4PFixed/Front
  1. XT3 Series (Frame 250A, 16-250A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT3N 250 TMD R200 FF 3P1SDA100737R125ILThermal‑magnetic (dist)200UN3PFixed/Front
XT3L 250 EkipDip LS/I R250 FF 3P1SDA100738R150ILBasic Electronic250UN3PFixed/Front
XT3H 250 TMA R225‑2250 FF 3P1SDA100739R165ILThermal‑magnetic (motor)225UN3PFixed/Front
  1. XT4 Series (Frame 250A, Premio)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT4N 250 TMD R160 FF 3P1SDA100740R125ILThermal‑magnetic (dist)160UN3PFixed/Front
XT4L 250 EkipC LSIG R200 FF 3P1015303750ILAdvanced Electronic200UN3PFixed/Front
XT4H 250 EkipM I R250 FF 4P1SDA100742R165ILMotor Electronic250UN4PFixed/Front
  1. XT5 Series (Frame 630A, 250-630A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT5N 630 TMD R630‑6300 FF 3P1SDA100743R125ILThermal‑magnetic (dist)630UN3PFixed/Front
XT5L 630 EkipDip LS/I R630 FF 3P1SDA100744R150ILBasic Electronic630UN3PFixed/Front
XT5H 630 EkipC LSIG R500 FF 3P1SDA100745R165ILAdvanced Electronic500UN3PFixed/Front
  1. XT6 Series (Frame 800/1000A, 630-1000A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT6S 800 TMA 800‑8000 FF 3P1SDA100740R122ILThermal‑magnetic (motor)800UN3PFixed/Front
XT6S 800 EkipDip LS/I 800A FF 3P1SDA100741R122ILBasic Electronic800UN3PFixed/Front
XT6L 1000 TMD 1000‑10000 FF 3P1SDA100746R150ILThermal‑magnetic (dist)1000UN3PFixed/Front
  1. XT7 Series (Frame 1200/1600A, 1000-1600A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
XT7M 1200 EkipC LSIG 1200A FF 3P1SDA100748R1100ILAdvanced Electronic1200UN3PFixed/Front
XT7M 1600 TMD 1600‑16000 FF 3P1SDA100749R1100ILThermal‑magnetic (dist)1600UN3PFixed/Front
  1. Formula Series (Economic, A1-A3) Model List & Order Codes
  2. A1 Series (Frame 125A, 16-125A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
A1N125 TMF125/1250 FF 3P1011644825ILThermal‑magnetic (dist)125UN3PFixed/Front
A1C125 TMF63/630 FF 4P1011644915ILThermal‑magnetic (dist)63UN4PFixed/Front
  1. A2 Series (Frame 250A, 16-250A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
A2N250 TMF250/2500 FF 3P1011645025ILThermal‑magnetic (dist)250UN3PFixed/Front
A2L250 MA200/2000 FF 3P1011645136ILMagnetic (motor)200UN3PFixed/Front
  1. A3 Series (Frame 400A, 250-400A adjustable)
Model ExampleOrder CodeCapacità di interruzioneTrip TypeCorrente nominalePoliMount/Conn
A3N400 TMF400/4000 FF 3P1011645225ILThermal‑magnetic (dist)400UN3PFixed/Front
A3L400 TMF315/3150 FF 4P1011645336ILThermal‑magnetic (dist)315UN4PFixed/Front
  1. Special Function Models
Special FunctionCodeExample ModelOrder CodeDescrizione
DC ApplicationDCXT4L 250 EkipDip DC 200A FF 3P1SDA100750R1For DC circuit protection
Enhanced Environment383XT6S 800 TMA 800‑8000 FF 3P 3831SDA100751R1Operating temp -25℃~+70℃
Motor ProtectionMA/MXT2N 160 MA100/600‑1400 FF 3P10152868Dedicated motor trip unit
Drawer MountingDXT5N 630 TMD 630‑6300 FD 3P1SDA100752R1Drawer type for easy maintenance
  1. Selection & Ordering Guidelines
  2. Capacità di interruzione: Select C/N/L/H/M according to system short-circuit current for safe fault interruption
  3. Trip Unit Selection

Distribution: TMD thermal-magnetic or EkipDip basic electronic

Motor protection: TMA thermal-magnetic or EkipM dedicated electronic

Complex systems: EkipC advanced electronic with full LSIG protection

  1. Mounting Type: Fisso (F) lowest cost; Plug-in (P) for easy replacement; Drawer (D) for frequent maintenance
  2. Order Code Verification: ABB official codes start with 1SDA…R1 or 101…; purchase via authorized channels to avoid counterfeits
  3. Quick Selection Chart (By Current Range)
Current RangeRecommended SeriesTypical ModelSample Order Code
16–160AXT1/XT2/A1XT2N 160 TMD R100 FF 3P1SDA100730R1
160–250AXT3/XT4/A2XT4L 250 EkipDip 200A FF 3P1SDA100738R1
250–630AXT5/A3XT5N 630 TMD 630‑6300 FF 3P1SDA100743R1
630–1000AXT6XT6S 800 EkipDip 800A FF 3P1SDA100741R1
1000–1600AXT7XT7M 1200 EkipC 1200A FF 3P1SDA100748R1