GV3P80 is a 3‑pole thermal‑magnetic motor circuit breaker from Schneider Electric TeSys GV3 series. It has an adjustment current range of 70–80A, suitable for 45kW (400V) / 55kW (690V) three‑phase motors. It integrates triple protection (sovraccarico, short‑circuit, mancanza di fase) and isolation function, serving as a core protection component in industrial motor circuits.
- Spiegazione del modello
GV3: TeSys GV3 motor circuit breaker series (frame size 3)
P: Thermal‑magnetic release (triple protection: sovraccarico + short‑circuit + mancanza di fase)
80: Rated current 80A, adjustable range 70–80A (continuously adjustable)
- Specifiche chiave (Full Data)
| Articolo | Specifica |
| Poli | 3P (three‑phase) |
| Adjustment current range | 70–80A (continuously adjustable) |
| Tipo di viaggio | Magnetotermico |
| Short‑circuit trip multiplier | 14×In (1120UN) |
| Breaking capacity Icu | 65kA @ 230V; 50kA @ 400V; 6kA @ 690V |
| Tensione operativa nominale Ue | 690V CA 50/60 Hz |
| Insulation voltage Ui | 690V e |
| Impulse withstand voltage Uimp | 6kV |
| Potenza motore adeguata | 45kW@400V; 55kW @ 690V; 22kW @ 230V |
| Terminali | EverLink screw terminals (25–35mm² cable) |
| Montaggio | Guida DIN (width 55mm), screw mountable |
| Grado di protezione | IP20 (anteriore) |
| Temperatura operativa | -20°C~+60°C (derating factor: 0.8 at +60°C) |
| Resistenza meccanica | 50,000 cicli operativi |
| Electrical endurance | 20,000 cicli (category AC‑3) |
| Funzione di isolamento | Complies with IEC 60947‑1, can be used as safety isolator |
| Certificazioni | CCC, CE, UL, CSA, IEC 60947‑4‑1 |
| Peso | ca. 1.02 kg |
| Dimensioni (L×A×P) | 55 × 105 × 78 mm |
- Funzioni principali & Vantaggi
- Triple Protection
Thermal trip: Overload inverse‑time protection (simulates motor heating characteristics)
Magnetic trip: Short‑circuit instantaneous protection (fixed 14×In)
Protezione dalla mancanza di fase: Automatic trip under three‑phase unbalance (IEC 60947‑4‑1)
- EverLink Terminal Technology
Maintenance‑free, anti‑loosening, oxidation‑resistant, suitable for large‑section cables, reduces wiring failure risks.
- Progettazione della sicurezza
Knob operation, lockable in OFF position (fino a 3 lucchetti)
Clear current scale for precise adjustment
Complies with IEC isolation standards, usable as motor circuit isolator
- Wide Environmental Adaptability
Operating altitude: ≤3000m (no derating required)
Resistenza alle vibrazioni: 10–150 Hz, 0.5ampiezza mm
Shock resistance: 5Gn (11SM); 30Gn (1SM)
- Riferimento alla selezione (TeSys GV3 Series)
| Modello | Adjustment Current | Suitable Power (400V) | Tipo di viaggio | Caratteristiche |
| GV3P65 | 55-65A | 37kW | Magnetotermico | Standard, EverLink terminals |
| GV3P80 | 70–80A | 45kW | Magnetotermico | Questo modello, max adjustment current |
| GV3L80 | 70–80A | 45kW | Magnetico | Short‑circuit protection only |
| GV3ME80 | 40–80A | 45kW | Magnetotermico | 3‑step adjustment (40–50/63–80), economy version |
| GV3P40 | 30–40A | 22kW | Magnetotermico | For small‑medium motors |
- Applicazioni
Avviamento diretto / star‑delta starting circuits for three‑phase asynchronous motors
Main circuit protection for fans, pompe, compressori, trasportatori, macchine utensili
Industrial automation lines, construction equipment motor control
Motor circuits requiring isolation and safety interlock (per esempio., emergency stop loops)
Motors with frequent starting/stopping and fluctuating loads
- Opzioni di sostituzione
- Schneider same series
GV3L80 (short‑circuit only, costo inferiore)
GV3ME80 (simplified adjustment, same mounting space)
- Competitor alternatives
Siemens: 3RV1041‑4JA10 (70–80A, 3P, magnetotermico)
ABB: MS165‑80 (70–80A, 3P, magnetotermico)
Chinese brands: Chint NM1‑125S, Delixi CDM1‑125 (motor protection curve matching required)
- Soluzione di aggiornamento
Schneider GV4P08N (telaio 4, maggiore potere di interruzione, for motors above 55kW)
Suggerimenti per la selezione
- Select adjustment range at 1.1–1.25 × motor rated current
- Confirm breaking capacity meets system short‑circuit current requirements
- For isolation function, prefer models with certified isolation
- For limited wiring space, choose EverLink terminal models to reduce faults
Complete Model List of Schneider Electric TeSys GV Series Motor Circuit Breakers
Schneider TeSys GV series motor circuit breakers include six sub‑series: GV1, GV2, GV3, GV4, GV5, GV6, covering an adjustment range from 0.06A to 800A, suitable for 0.03kW to 400kW (400V) three‑phase motors, with thermal‑magnetic, magnetic, and economy thermal‑magnetic protection types.
- GV1 Series (Miniature, interrotto, replaced by GV2ME)
GV1ME01: 0.1–0.16A
GV1ME02: 0.16–0.25A
GV1ME03: 0.25–0.4A
GV1ME04: 0.4–0.63A
GV1ME05: 0.63–1.0A
GV1ME06: 1.0–1.6A
GV1ME07: 1.6–2.5A
GV1ME08: 2.5–4.0A
- GV2 Series (Piccolo, 0.06–16A, 0.03–15kW/400V)
2.1 GV2P (Magnetotermico, protezione completa, knob)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV2P01 | 0.1–0.16A | 0.06kW |
| GV2P02 | 0.16–0.25A | 0.12kW |
| GV2P03 | 0.25–0.4A | 0.2kW |
| GV2P04 | 0.4–0.63A | 0.37kW |
| GV2P05 | 0.63–1.0A | 0.55kW |
| GV2P06 | 1.0–1.6A | 0.75kW |
| GV2P07 | 1.6–2.5A | 1.5kW |
| GV2P08 | 2.5–4.0A | 2.2kW |
| GV2P10 | 4.0–6.3A | 3kW |
| GV2P14 | 6.3–10A | 4kW |
| GV2P16 | 10–16A | 7.5kW |
2.2 GV2L (Magnetico, short‑circuit only, knob)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV2L01 | 0.1–0.16A | 0.06kW |
| GV2L02 | 0.16–0.25A | 0.12kW |
| GV2L03 | 0.25–0.4A | 0.2kW |
| GV2L04 | 0.4–0.63A | 0.37kW |
| GV2L05 | 0.63–1.0A | 0.55kW |
| GV2L06 | 1.0–1.6A | 0.75kW |
| GV2L07 | 1.6–2.5A | 1.5kW |
| GV2L08 | 2.5–4.0A | 2.2kW |
| GV2L10 | 4.0–6.3A | 3kW |
| GV2L14 | 6.3–10A | 4kW |
| GV2L16 | 10–16A | 7.5kW |
| GV2L20 | 14–20A | 11kW |
| GV2L22 | 18–25A | 15kW |
2.3 GV2ME (Economy thermal‑magnetic, pushbutton, 3‑step)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV2ME01 | 0.1–0.16A | 0.06kW |
| GV2ME02 | 0.16–0.25A | 0.12kW |
| GV2ME03 | 0.25–0.4A | 0.2kW |
| GV2ME04 | 0.4–0.63A | 0.37kW |
| GV2ME05 | 0.63–1.0A | 0.55kW |
| GV2ME06 | 1.0–1.6A | 0.75kW |
| GV2ME07 | 1.6–2.5A | 1.5kW |
| GV2ME08 | 2.5–4.0A | 2.2kW |
| GV2ME10 | 4–6.3A | 3kW |
| GV2ME14 | 6.3–10A | 4kW |
| GV2ME16 | 10–16A | 7.5kW |
2.4 GV2LE (Magnetic with electronic trip, special applications)
GV2LE01 ~ GV2LE22: matching current ratings as GV2L, with electronic trip
- GV3 Series (Medio, 9–80A, 5.5–45kW/400V, 55larghezza mm)
3.1 GV3P (Magnetotermico, protezione completa, EverLink)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV3P13 | 9–13A | 5.5kW |
| GV3P18 | 13–18A | 11kW |
| GV3P25 | 18–25A | 15kW |
| GV3P32 | 23–32A | 18.5kW |
| GV3P40 | 30–40A | 22kW |
| GV3P50 | 40–50A | 30kW |
| GV3P65 | 55-65A | 37kW |
| GV3P73 | 65–73A | 45kW |
| GV3P80 | 70–80A | 45kW |
3.2 GV3L (Magnetico, short‑circuit only)
GV3L25: 18–25A
GV3L32: 23–32A
GV3L40: 30–40A
GV3L50: 40–50A
GV3L65: 55-65A
GV3L80: 70–80A
3.3 GV3ME (Economy thermal‑magnetic, 3‑step)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV3ME40 | 40–50A | 30kW |
| GV3ME63 | 50–63A | 37kW |
| GV3ME80 | 40–80A (3 passi: 40–50/63–80) | 45kW |
- GV4 Series (Grande, 25–115A, 15–55kW/400V, 81larghezza mm)
4.1 GV4P (Magnetotermico, protezione completa)
| Modello | Adjustment Current | Suitable Power (400V) |
| GV4P25 | 25–32A | 18.5kW |
| GV4P40 | 32–40A | 22kW |
| GV4P50 | 40–50A | 30kW |
| GV4P63 | 50–63A | 37kW |
| GV4P80 | 63–80A | 45kW |
| GV4P100 | 80–100A | 55kW |
| GV4P115 | 100–115A | 55kW |
4.2 GV4L / GV4LE (Magnetic type)
GV4L25 ~ GV4L115: matching current ratings as GV4P
GV4LE25 ~ GV4LE115: magnetic with electronic trip
4.3 Special GV4 Models
GV4PB80S: UL489 approved, 63–80A
GV4P02N: 2‑pole thermal‑magnetic, special applications
- GV5 / GV6 Series (Extra‑large, 100–800A, 55–400kW/400V)
GV5P100: 80–100A
GV5P125: 100–125A
GV5P160: 125–160A
GV5P200: 160–200A
GV6P250: 200–250A
GV6P315: 250–315A
GV6P400: 315–400A
GV6P500: 400–500A
GV6P630: 500–630A
GV6P800: 630–800A
- Regole di denominazione dei modelli
| Letter/Number | Senso |
| GV | TeSys GV series motor circuit breaker |
| 1/2/3/4/5/6 | Dimensioni del telaio (1 = smallest, 6 = largest) |
| P | Viaggio magnetotermico (sovraccarico + short‑circuit + mancanza di fase) |
| l | Magnetic trip (short‑circuit only) |
| ME | Economy thermal‑magnetic trip (3‑step, cost‑optimized) |
| IL | Magnetic trip with electronic functions |
| Numero | Current rating (per esempio., 80 = 70–80A) |
- Guida alla selezione rapida
- Select adjustment range at 1.1–1.25 × motor rated current
- For full protection (sovraccarico + short‑circuit + mancanza di fase): choose P series
- If thermal protection exists (per esempio., VFD): choose L series (short‑circuit only)
- Cost‑sensitive, simple adjustment: choose ME series (3‑step)
- Piccoli motori (≤15kW): GV2; medio (15–45kW): GV3; grande (≥55kW): GV4–GV6
- Note
- All models are 3‑pole (3P) for three‑phase asynchronous motors
- Protection characteristics comply with IEC 60947‑4‑1
- Potere di interruzione: GV2/GV3 100kA@400V; GV4 65kA@400V
- Montaggio: 35Guida DIN standard da mm
- Grado di protezione: IP20 (front operating part)