Model Code Explanation Code Segment Description FBs Prefix for standard Fatek PLC series 40 Punti I/O totali: 40 (24 input + 16 uscite) MC High-performance main unit, different from MA/MB economy type and MN high-speed NC type R Output type: Uscita relè. Large contact capacity, suitable for AC and DC loads 2 Mark for 2nd ...

  • Dettagli del prodotto

Spiegazione del codice modello

Segmento di codiceDescrizione
FBsPrefix for standard Fatek PLC serie
40Punti I/O totali: 40 (24 input + 16 uscite)
MCHigh-performance main unit, different from MA/MB economy type and MN high-speed NC type
RTipo di uscita: Uscita relè. Large contact capacity, suitable for AC and DC loads
2Mark for 2nd generation upgraded version
ACAlimentazione elettrica: Wide voltage range 100~240VAC
  1. Specifiche principali
CategoriaSpecifiche dettagliate
Configurazione I/O24-channel 24VDC digital inputs, 16-channel relay outputs
High-speed Inputs6 channels @ 200KHz high-speed counting + 2 channels @ 20KHz medium-speed counting + 16 general inputs
High-speed OutputsRelay outputs do not support high-speed pulse. Only transistor models (T/J) provide 6 channels @ 200KHz + 2 channels @ 20KHz
Communication PortsIntegrato 1 integrated RS232/USB port (Port0), expandable up to 5 communication ports in total
Memoria del programma8KB (standard), expandable to 16KB
Data Memory4KB (standard), expandable to 8KB
High-speed Counter4 groups of Hardware High-speed Counters (HHSC), massimo. 200KHz; 4 groups of Software High-speed Counters (SHSC), massimo. 5KHz
Temporizzatori0.1ms high-precision high-speed timers, supporting multiple timing modes
Instruction SetSopra 300 instructions, supporting multi-input & multi-output structures for high programming efficiency
Alimentazione elettrica100~240VAC, 50/60Hz, consumo energetico ca. 15W
Ambiente operativoTemperatura: -20~75°C; Umidità: 10~90%RH (senza condensa)
DimensioniMontaggio su guida DIN standard, ca. 100×100×75mm (refer to official data for exact size)
CertificazioniCE, Certificato UL, compliant with industrial safety standards
  1. Cross-brand Equivalent Comparison
MarcaModello equivalentePrincipali differenze
SiemensS7-200 SMART SR40FBs-40MCR2-AC features higher high-speed counting frequency (200KHz vs 100KHz) and a more streamlined instruction set
MitsubishiFX3U-40MR/ES-AFatek has built-in USB + RS232 dual ports (Mitsubishi requires extra expansion); Fatek delivers better high-speed counting performance
OmronCP1E-N40DR-ALarger program memory (8KB vs 6KB); stronger communication expansion capability (massimo. 5 porti)
Schneider ElectricM221C40RPiù conveniente; superior high-speed counting and pulse output performance
  1. Full Model List of FBs-MC Series
ModelloPunti di I/OTipo di uscitaAlimentazione elettricaCaratteristiche principali
FBs-10MCR2-AC10 (6IN/4OUT)RelèACEconomy compact type, non-expandable
FBs-14MCR2-AC14 (8IN/6OUT)RelèACEconomy compact type, non-expandable
FBs-20MCR2-AC20 (12IN/8OUT)RelèACBasic functional type, espandibile
FBs-24MCR2-AC24 (14IN/10OUT)RelèACBasic functional type, espandibile
FBs-32MCR2-AC32 (16IN/16OUT)RelèACHigh-performance type with built-in high-speed counting
FBs-40MCR2-AC40 (24IN/16OUT)RelèACHigh-performance type, 6 channels 200KHz high-speed inputs
FBs-60MCR2-AC60 (36IN/24OUT)RelèACHigh-performance type with large I/O capacity
FBs-40MCT2-AC40 (24IN/16OUT)Transistor (NPN)ACHigh-performance type, 6 channels 200KHz high-speed outputs
FBs-40MCJ2-AC40 (24IN/16OUT)Transistor (PNP)ACHigh-performance type with PNP output
FBs-40MCR2-D2440 (24IN/16OUT)RelèDC24VDC powered version
  1. Difetti comuni & Risoluzione dei problemi
Fenomeno di guastoPossibili causePassaggi per la risoluzione dei problemi
Power indicator offDamaged power cable, faulty power module, tensione di ingresso anomala1. Check power cable and socket
2. Verify input voltage within 100~240VAC
3. Inspect bulging capacitors on power module
4. Replace power module for test
No response at input pointsCablaggio errato, defective sensor, faulty PLC input module1. Check sensor power and wiring
2. Measure input voltage (nominal 24VDC) with multimeter
3. Replace sensor for test
4. Check PLC input indicators
No action at output pointsCablaggio errato, faulty load, damaged relay contacts1. Check load power and wiring
2. Measure output terminal voltage
3. Replace load for test
4. Check PLC output indicators
5. Replace relay module (se applicabile)
Errore di comunicazioneParametri di comunicazione non corrispondenti, faulty cable, damaged port1. Check baud rate, data bits and parity bits
2. Inspect cable connection and shielding
3. Replace communication cable
4. Check communication indicators
5. Try alternative communication ports
Perdita del programmaLow battery voltage, incomplete program saving, memory failure1. Check battery voltage (≥3V required)
2. Re-download program and save to EEPROM
3. Replace battery
4. Inspect memory module
  1. Applicazione & Casi di settore

Scenari applicabili

  1. Macchine per l'imballaggio: Control conveyors, cutting, labeling and other actions; realize precise counting and positioning via high-speed counting function
  2. Macchinari tessili: Control looms and knitting machines; support multi-axis synchronous operation
  3. Food Processing: Manage filling, sealing and sterilization processes; execute scheduled tasks via built-in calendar
  4. Machine Tool Control: Control spindle and feed of small machine tools for basic positioning
  5. Automazione degli edifici: Regulate air conditioning, lighting and elevators; realize centralized monitoring via communication ports

Scenari non consigliati

  1. High-precision high-speed positioning: Applications requiring pulse output over 200KHz (MN series recommended)
  2. Controllo del carico ad alta potenza: Single output load exceeding relay rated capacity (typically 2A/250VAC)
  3. Severe electromagnetic interference: Environments without proper shielding, which may affect normal operation
  4. Extreme temperature: Operating temperature beyond -20~75°C

Casi applicativi tipici

Caso 1: Automatic Packaging Line Control System

Attrezzatura: Automatic packaging machine, trasportatore, labeler

Funzioni: Product counting, fixed-length film cutting, labeling position control, allarme guasto

Highlights: Precise counting via 6-channel 200KHz high-speed inputs; HMI interaction via RS232 communication; scheduled production with built-in calendar

Caso 2: Small Wastewater Treatment System

Attrezzatura: Pompe dell'acqua, valvole, level sensors, pH sensors

Funzioni: Automatic pump start/stop based on liquid level; automatic chemical dosing according to pH value; automatic standby switch upon fault

Highlights: High-power pumps and valves controlled by relay outputs; data transmission to host computer via communication expansion modules; periodic backwashing via built-in timers

  1. Linee guida per la selezione & Regole di riferimento rapido
  2. Suggerimenti per la selezione: Match I/O points to demands; select output type by load (relay for AC/DC universal use, transistor for high-speed pulse); choose power supply per on-site condition; select series by functions (MC: ad alte prestazioni, MA: economia, MN: high-speed positioning)
  3. Regole veloci:

R = Relay, T = NPN Transistor, J = PNP Transistor

AC = AC power supply, D24 = 24VDC power supply

2 = 2nd generation with enhanced functions and stability

MC series is standard equipped with 200KHz high-speed counter and real-time calendar

Relay Output Specifications for FBs-40MCR2-AC

Tipo di uscita: Relè, 16 channels in total

Rated Current per Point: 2UN (carico resistivo)

Rated Voltage Range:

AC: ≤ 250VAC

DC: ≤ 30VDC

Massimo. Carico resistivo:

AC: 500VA (250V × 2A)

DC: 60W (30V × 2A)

Recommended Inductive Load: ≤ 80VA (to prevent contact ablation)

Mechanical Lifespan: ca. 100,000 cycles under full load

Prec:

Prossimo:

Lascia una risposta