Nome del prodotto: Motor Operating Mechanism
Compatibile con: ComPacT NSX / EasyPact CVS 400~630A moulded case circuit breakers
✅ Specifiche chiave
Tensione di controllo: 110…230V AC 50/60Hz, 110…230V DC (AC/DC universale)
Funzione: Remote electrical closing and opening, local manual handle retained
Reference number: LV435010
Alternative in the same series: LV435005 (400V AC version motor mechanism)
Montaggio: Front-mounted accessory, fitted directly on the front of the circuit breaker
Caratteristiche: New-generation ComPacT green label version, optimized wiring structure to reduce cabinet wiring time
📌 Note sulla selezione
- Compatibile solo con 400/630 frame size NSX/CVS; not for 100/160/250 dimensioni del telaio
- Motor mechanism ≠ shunt release / sganciatore di minima tensione: the motor mechanism uses a motor-charged spring for closing and opening
- Equipped with manual emergency operation; local closing/opening available after power loss
- Additional auxiliary contacts such as OF, SD, SDE can be fitted for signal feedback
LV435010 Cross Reference Table for NSX400/630 MT Motor Mechanism
LV435010 = New-generation ComPacT green label motor mechanism, 110…230V AC/DC universal, replacement for the older LV432641; LV435005 corresponds to the older LV432642 (380~415 V CA)
| Tipo | Obsolete Old Part No. | Valutazione della tensione | Direct New Replacement |
| NSX400/630 MT Motor Mechanism | LV432641 | 220~240 V CA (Solo aria condizionata) | LV435010 (110–230V AC/DC universal) |
| NSX400/630 MT Motor Mechanism | LV432642 | 380~415 V CA | LV435005 |
| Older Compact NS (not NSX) | 32641 / 32841 | 220V e | LV432641 (which can be upgraded further to LV435010) |
✅ Mounting Compatibility (Critico)
- Fully compatible mechanical mounting footprint: Older black-label NSX400/630, new ComPacT NSX and CVS400/630 can all accept LV435010 directly, no breaker modification or adapter bracket required
- OF/SD/SDE auxiliary contacts: Existing older auxiliary contacts can be reused without replacement
- Different terminal definitions! (Insidia comune)
LV432641: AC-only terminals, no wide DC compatibility; chiusura, opening and common terminals are arranged differently
LV435010: Shared terminal block for AC and DC, supports both AC and DC power supply; updated terminal marking. Rewiring is mandatory for direct replacement; plug-and-play is not possible
- Front panel appearance: Older version with grey-black panel; new version with green ComPacT marking, integrated lock toggle and front quick-connect terminals, cutting cabinet wiring workload by around 40%
⚠️ Replacement Risks & Precauzioni
Not plug-and-play: Meccanicamente intercambiabile, electrically incompatible on secondary wiring. Always verify schematic before replacement
LV435010 has a wider voltage range: 110V~230V AC 50/60Hz + 110~230V DC; LV432641 only supports 220/240V AC and cannot run on DC
Minor improvements to mechanical endurance, charging time and power consumption; functional logic (pulse-controlled closing/opening, manual charging, local pushbuttons) remains consistent
For legacy Compact NS (not NSX), LV432641 is the transitional choice; LV435010 is not officially recommended for direct fitting on Compact NS
📌 Related Parts in the Same Series
LV435010: 110–230 V CA/CC (primary replacement for LV432641)
LV435005: 380–415V AC (replacement for LV432642)
The LV435010 MT motor mechanism has no built-in signal contacts. OF/SD/SDE/SDV are all passive changeover contacts (1NA+1NC) installed on the circuit breaker body. The contact component is the same part S29450 (standard) / S29452 (low-level low-consumption), and different functions are realised by fitting them into designated slots.
- Four Basic Signal Contacts (NSX400/630, compatible with MT motor mechanism)
- OF Closing/Opening Auxiliary Contact (Position Contact)
Funzione: Indicates the actual closed/open status of the breaker main contacts; toggles synchronously for electric closing, electric opening and manual operation
Applicazione: Remote position feedback, incastro, status indication lamps
Valutazione: Standard contact 5A; low-consumption contact for low-current PLC circuits (minimum 1mA@24VDC)
Maximum quantity on NSX400/630: 4 sets of OF
- SD Trip Indication Contact (General Trip)
Triggered by: All trip events
✅ Overload, cortocircuito, earth-fault and residual-current trips
✅ MX shunt trip, MN undervoltage trip
✅ Manual TEST button trip, withdrawable unit separation trip, manual trip via motor mechanism
Does not distinguish between fault trip and command trip; SD activates whenever the breaker moves to the intermediate tripped position
- SDE Electrical Fault Trip Contact (Fault Discrimination)
Triggered only by: Trips caused by protective faults
✅ Overload, cortocircuito, guasto a terra, corrente residua
❌ Not triggered by MX shunt trip, MN undervoltage trip or TEST button
Typical site practice: SD for general alarm, SDE for protective fault alarm, enabling the SCADA system to tell remote command trips apart from fault trips
SDE on NSX400/630 requires no extra adapter (100/250 frame sizes need an adapter)
- SDV Residual-Current Vigi Dedicated Contact
Triggered only by Vigi module residual current protection activation; unaffected by other faults
Valid only when fitted with VigiPacT residual current accessory
- Extended Fault Classification Contacts SDx (for advanced trip units)
SDx fault classification module works with Micrologic 5/6/4/7 trip units to output detailed fault types: ritardo da molto tempo, ritardo di breve durata, earth fault and residual current. Used for precise fault identification by upper control systems; not a basic changeover contact, classified as a signal module.
- MT Motor Mechanism Exclusive Signals (Separate from breaker contacts, frequent source of confusion)
The LV435010 terminal block carries two dedicated status signals from the motor mechanism (not OF/SD):
PF: Ready-to-close (charged spring contact): Closes when spring charging completes; opens when uncharged or after spring discharge, used to interlock the closing command
Motor running feedback: Motor operation signal for detection of active closing/opening cycles
⚠️ Quick distinction:
OF/SD/SDE/SDV = Circuit breaker status
PF charged contact = MT motor mechanism spring status
- Component Codes & Mounting Capacity (NSX400/630)
Standard contact: S29450 (1NA+1NC, general circuits)
Low-consumption contact: S29452 (low-current PLC / DCS circuits)
Maximum configuration: 4×OF + 1×SD +1×SDE +1×SDV (with Vigi)
Cross-generation compatibility: S29450 contacts used with older LV432641 are fully reusable with LV435010
- Common Configuration Schemes
Basic remote control: DI + PF (posizione + charged status)
Alarm discrimination: DI + SD + SDE (most common for SCADA)
Con protezione differenziale: DI + SD + SDE + SDV
ComPacT NSX / EasyPact CVS MT Motor Mechanism Compatibility List (New Green Label MT, Schneider Ufficiale)
Compatibile: NSX (legacy black label + new green label), CVS; NSXm 100/160m cannot be fitted with MT motor mechanism
Model grouping: MT100/160/250 (piccola cornice); MT400/630 (large frame, LV435010 family)
| Frame Group | Motor Mechanism Part No. | Valutazione della tensione | Compatible Breaker Body | Obsolete Replacement Reference |
| MT100/160/250 | LV435001 | 110…230V AC/DC | NSX100/160/250, CVS100/160/250 | LV431541 |
| MT100/160/250 | LV435002 | 380…415V AC | NSX100/160/250, CVS100/160/250 | LV431542 |
| MT100/160/250 | LV435009 | 24A DC | NSX100/160/250, CVS100/160/250 | LV431543 |
| MT400/630 | LV435010 | 110…230V AC/DC | NSX400/630, CVS400/630 | LV432641 |
| MT400/630 | LV435005 | 380…415V AC | NSX400/630, CVS400/630 | LV432642 |
| MT400/630 | LV435006 | 24A DC | NSX400/630, CVS400/630 | LV432643 |
Supplementare: Communicable MTc Motor Mechanism (BSCM Modbus interface)
| Dimensioni del telaio | Parte n. | Voltaggio | Compatible Body |
| MTc 100/250 | LV435021 | 110…230V AC/DC | NSX100/160/250 |
| MTc 400/630 | LV435020 | 110…230V AC/DC | NSX400/630 |
MTc requires BSCM communication module. Supports bus command for closing/opening and reading mechanism & breaker status. CVS breakers do not support MTc
Important Compatibility Notes
- Mounting form: Fixed and withdrawable NSX/CVS of the same frame size are both compatible; 3P and 4P are interchangeable, no polarity distinction
- Trip unit compatibility: TMD thermal-magnetic and Micrologic electronic trip units (2.2/5.2/6.2/2.3/5.3/6.3 ecc.) are all compatible; motor mechanism is independent of protection type
- Shared accessories: OF/SD/SDE contacts S29450 (standard), S29452 (low-consumption), compatible across generations
- Legacy Compact NS (not NSX): Not compatible with new LV4350xx motor mechanisms; only older LV4326xx series is applicable
- NSX DC photovoltaic moulded case breakers: Same-frame MT motor mechanisms (LV435001 / LV435010 etc.) are also compatible
Riepilogo veloce
LV4350xx = New green label MT (current active range, optimized wiring, wide AC/DC input)
LV4315xx / LV4326xx = Older black label MT (gradualmente eliminato, mostly AC-only variants)
LV435010 (NSX400/630 MT Motor Mechanism) Standard Mounting Procedure
Applicabile: New ComPacT NSX400/630, CVS400/630; fisso / withdrawable versions. Lockout-tagout primary circuit before work. The sequence is also a reference for older LV432641 (mechanical structure identical, only terminals differ)
Pre-requisite warning: OF/SD/SDE/SDV contacts, MX shunt release and MN undervoltage release must be fitted into the breaker slots BEFORE mounting the motor mechanism. No internal accessories can be added once the motor mechanism is installed
Fare un passo 1: Prepare the circuit breaker
- Move the breaker handle to closed position, press the red Trip button to put the breaker into free-trip position
- Move the main handle to OFF (aprire)
- Remove the extended operating handle, keep the short original handle
- Loosen the front cover screws and remove the breaker front cover; peel the trip unit nameplate label and affix it to the reserved label area on the motor mechanism housing
Fare un passo 2: Pre-fit internal accessories (sequence cannot be reversed)
Fit required accessories: DI, SD, SDE, SDV, MX, MN
SDE on NSX400/630 needs no SDE adapter; 100/250 frame sizes require an adapter
Fare un passo 3: Pre-set the motor mechanism (critico)
- Pull out the side manual charging lever and stroke repeatedly until the yellow CHARGED indicator appears in the viewing window (carica a molla)
- Toggle the side selector switch to MANU (Manuale) modalità
- Check that the driving slider inside the mechanism is correctly engaged; do not force assembly
Fare un passo 4: Align and fasten
- Align the driving slot of the motor mechanism over the short breaker handle and seat flush
- Tighten with the 3 supplied mounting screws (3 screws for NSX400/630; 4 screws for 100/250), tighten diagonally and evenly to avoid jamming from uneven stress
- Ispezione: No gaps or warping, handle transmission moves freely without binding
Fare un passo 5: Manual dry test (no power applied)
Keep MANU mode active:
- Press ON pushbutton on mechanism → breaker closes reliably
- Press OFF pushbutton on mechanism → breaker opens reliably
- Repeat charging and switching 3 volte, confirm smooth operation, nessun grippaggio o rumore anomalo
If malfunctioning: Loosen screws, re-align. Do not energise for troubleshooting
Fare un passo 6: Secondary wiring (LV435010 new wide-voltage motor mechanism)
Terminal block includes: Motor drive terminals + PF charged-state passive contacts
- Wire per the schematic printed on the mechanism housing: Closing pulse, opening pulse, comune, Alimentazione elettrica, PF feedback
- Nota: LV435010 terminal assignment differs from LV432641; old wiring harness cannot be reused directly
- Use appropriate wire gauge for control cables, route away from high-temperature primary busbars
- Dress cables and fit the transparent front cover
Fare un passo 7: Electrical functional test (AUTO mode)
- Switch MANU to AUTO mode
- Apply control supply (110–230 V CA/CC)
- Send remote closing pulse: Motor charges spring then closes breaker; PF contact status changes accordingly
- Send remote opening pulse: Electric opening
- Verify SCADA feedback signals: OF position, PF charged status, SD/SDE fault signals
- Prova di perdita di potenza: Manual charging and local pushbutton operation remain functional without control power
Fare un passo 8: Chiusura, sealing and handover
Opzionale: Padlock in open position for maintenance lockout
Lead seal accessory available
Record charging time and signal feedback status, apply identification labels in cabinet
⚠️ Critical Pitfall Checklist
- ❌ Never work with energised primary circuit
- ❌ Do not fit OF/SDE contacts after installing the motor mechanism; contact compartment becomes inaccessible
- ❌ Do not force the manual charging lever when in AUTO mode
- ❌ For withdrawable breakers: Mount the motor mechanism only in test or disconnected position, never in connected service position
- ❌ Yellow window = spring charged; blank = uncharged. PF contact only indicates spring status and does not equal breaker closing permission
- MTc communication version (with BSCM): Fit BSCM module and communication ribbon cable first, then follow the above mounting sequence
Supplementare: Replacement Difference (LV432641 → LV435010)
Mounting holes match perfectly, original screws can be reused;
Only change: Secondary terminal definitions, rewiring is mandatory; old control wiring cannot be reused directly