Honeywell DC120L10001000 Limit Controller

Nome e cognome: Honeywell UDC120L10001000, a UDC1200 Micro-Pro 1/16 DIN Limit Controller. It is not a conventional PID temperature controller. It is designed for safety over-limit protection with latching alarm function. Decodifica del codice modello: DC120L 10001000 DC120L: UDC1200 series Limit Controller (differentiated from DC1201/1202 conventional PID controllers) 1: Uscita principale 1, SPDT Relay 0: Nessun ausiliario ...

  • Dettagli del prodotto

Nome e cognome: Honeywell UDC120L10001000, a UDC1200 Micro-Pro 1/16 DA Limit Controller. It is not a conventional PID temperature controller. It is designed for safety over-limit protection with latching alarm function.

  1. Decodifica del codice modello: DC120L 10001000

DC120L: UDC1200 series Limit Controller (differentiated from DC1201/1202 conventional PID controllers)

1: Uscita principale 1, SPDT Relay

0: No auxiliary output

0: Nessuna comunicazione

1: Universal Power Supply 90–264VAC (50/60Hz)

0: No second output

0: No optional extras

0: No additional alarm

  1. Specifiche principali
ArticoloParametro
Dimensione complessiva48×48×110 mm (1/16 DA)
Ritaglio del pannello45×45 mm
Alimentazione elettrica90~264V AC, 50/60Hz, Power Consumption ≤4W
IngressoIngresso universale: Thermocouple K/J/R/S/B/E/N/T; Termoresistenza Pt100; 4-20mA linear signal
Precisione0.1% of full scale ±1 LSD
Uscita principaleSPDT Relay, Contact Rating 3A@240VAC
Periodo di campionamento250SM
DisplayDual 4-digit LED, simultaneous PV/SP display + status LED
PesoMassimo. 210G
CertificazioniCE, RoHS
  1. Funzioni chiave (Main Differences Between Limit Controller & Normal PID Controller)
  2. Over-limit Latching Protection: When the measured value exceeds the set limit value, the relay actuates and latches. Manual reset is required for recovery. Applied for over-temperature safety cut-off of ovens, furnaces and heat treatment equipment (safety temperature limiter).
  3. Universal sensor input supporting thermocouples, RTDs and analog signals.
  4. Sensor break detection: TC/RTD break triggers alarm output.
  5. Password-protected parameters to prevent unauthorized modification of limit values on site.
  6. No PID automatic regulation. Only upper / lower limit safety protection (cannot be used for continuous temperature regulation).
  7. Scenari applicativi tipici

Over-temperature safety protection loops for industrial ovens, heat treatment furnaces, aging test chambers, environmental chambers, boiler auxiliaries, plastic extruders and food baking equipment. Often used together with conventional PID temperature controllers (PID controller handles regulation; DC120L serves as independent safety temperature limiting).

  1. Installazione & Linee guida per il cablaggio
  2. Panel snap-in mounting, max panel thickness 6mm; keep heat dissipation gaps front and rear.
  3. Relay contacts are dry contacts with external load power supply. Do NOT connect high voltage to instrument internal terminals.
  4. Route sensor cables separately away from power cables to reduce interference.
  5. Unlock via password before commissioning to modify temperature limits. Manual key reset is required after latch activation.
  6. Alternativa / Optional Models
  7. Stessa serie: Other DC120L suffix versions (DC120L10011000 with RS485 communication)
  8. Alternative domestiche: Yudian AI series limit controllers, Hongrun NHR-1100 (funzioni simili, latch logic needs verification)
  9. Legacy Honeywell replacement: DC1000 series limit type (gradually phased out)
  10. Risoluzione dei problemi comuni

Sensor error displayed: Check TC/RTD polarity, wire breakage and cold junction compensation.

No latch after over-limit: Confirm function mode is set to Limit latch mode instead of ordinary alarm mode.

Relay fails to actuate: Verify contact load rating, terminal wiring and instrument power supply.

Parameters cannot be modified: Instrument password locked, enter unlock password.

  1. HS Code Reference (For Foreign Trade)

9032890090 Other automatic regulating or controlling instruments and apparatus

Tabella comparativa: Honeywell DC120L (UDC120L10001000) vs UDC1202 PID Temperature Controller

Elemento di confrontoDC120L (Limit Controller)UDC1202 (PID Process Controller)
Posizionamento centraleSafety over-limit protection instrument (independent safety temperature limiting)Process temperature automatic regulation instrument (main temperature control)
Control AlgorithmNo PID algorithm, only limit logic; Over-limit Latch functionPID/PD/On-off / Three-position stepping valve control; Auto-tune supported
Latch Function✅ Standard: Relay latches after over-limit actuation, manual reset mandatory for release (safety cut-off)❌ Ordinary alarm without latch; output recovers automatically once temperature drops
Funzione di uscitaOutput for safety cut-off only, no continuous regulationMain output for continuous temperature control: Relè / RSS / 4-20Uscita analogica mA
Dimensione complessiva48×48 mm, 1/16 DA, panel cutout 45×45mm48×48 mm, 1/16 DA, panel cutout 45×45mm (fully interchangeable for panel mounting)
Ingresso universale✅ Thermocouple, Pt100, 4-20mA linear signal✅ Thermocouple, Pt100, 4-20mA linear signal
Alimentazione elettrica90~264VAC wide range90~264VAC wide range
Precisione0.1% of full scale ±1 LSD0.1% of full scale ±1 LSD
Utilizzo tipicoOver-temperature safety protection for ovens, heat treatment furnaces and test chambers, independent safety loop (safety redundancy)Closed-loop regulation of normal process temperature to maintain setpoint
Combination ApplicationUsed with PID controller: UDC1202 for main temperature control, DC120L as secondary independent safety protectionSole unit for automatic temperature control; not responsible for safety temperature limiting
Manuale / La moda automobilisticaNo manual/auto control mode, only limit value settingAutomatic PID regulation, manual output, manual/auto switch available
Alarm TypesOnly over-limit safety latch alarmUpper limit, limite inferiore, deviazione, band alarms and more configurable alarm types
Communication OptionRS485 Modbus optional (this DC120L10001000 unit has no communication)RS485 Modbus optional
Punti chiave della selezioneApplications requiring independent temperature limit loop and latching trip per safety specificationsConventional temperature control scenarios requiring automatic constant temperature closed-loop regulation
Osservazioni importantiCannot replace PID controller for temperature regulation, safety protection onlyCannot replace safety limit instrument; non-latching alarm fails safety requirements for some equipment

Selection Recommendation Summary

  1. Equipment requiring safety redundancy, hard over-temperature cut-off and fault latching: Dual-instrument scheme: UDC1202 (main temperature control) + DC120L (independent temperature limit) (widely used for heat treatment, ovens and aging chambers)
  2. Only conventional constant temperature control required with no mandatory safety latch requirement: Select UDC1202 directly
  3. Only over-temperature protection required without automatic temperature control: Select DC120L alone

Honeywell DC120L10001000 (UDC120L Limit Controller) Documento tecnico

Nome completo del prodotto: Honeywell UDC1200 Micro-Pro DC120L Limit Controller

Document Type: Datasheet / Technical Specification Manual (English Engineering Version)

Modello applicabile: DC120L10001000 (Uscita relè, No Communication, 90~264VAC Power Supply)

Posizionamento del prodotto: Independent safety limit instrument, no PID regulation, over-limit latching trip, applied for equipment over-temperature safety protection

  1. Model Code Definition DC120L 1 0 0 1 0 0 0
Segmento di codiceDescrizioneConfiguration of This Model
DC120LUDC1200 series Limit ControllerLimit type, no PID algorithm
1prima cifra 1Main Output Type1=SPDT Relay Output
2seconda cifra 0Uscita ausiliaria0=No auxiliary output
3rd digit 0Communication Option0=No RS485 Modbus communication
4esima cifra 1Power Supply Specification1=Universal AC 90~264VAC, 50/60Hz
5esima cifra 0Second Output0=No second output
6esima cifra 0Optional Function0=No optional extras
7esima cifra 0Alarm Option0=No additional alarm output
  1. Elettrico & Specifiche meccaniche
ArticoloValoreOsservazioni
Dimensione complessiva48mm × 48mm × 110mm1/16 DIN panel mount
Ritaglio del pannello45mm × 45mmMax panel thickness 6mm
Alimentazione elettrica90~264V AC, 50/60HzWide-range universal AC supply
Consumo energetico≤4WBasso consumo energetico
Peso≤210g
Periodo di campionamento250SM (4 volte al secondo)
Precisione della misurazione0.1% of full scale ±1 LSDCold junction compensation ±1℃ for thermocouples
Impedenza di ingresso>10MΩ (TC/RTD); 5OH (4-20mA)
Uscita principaleSPDT Relay, 3A@240VACDry passive contacts
CertificazioniCE, RoHSIndustrial certifications
Sensor Break DetectionTC / RST / 4-20mA break diagnosis supportedBreakage triggers limit action

Universal Input Types (Supported Sensors)

Termocoppia: K, J, R, S, B, E, N, T

RST: Pt100 (DIN43760 0.00385)

Linear Analog: 4~20mA, 0~20mA, 0~10 V, 1~5V

  1. Descrizione delle funzioni principali
  2. Limit Latch Protection【Core Feature】

When measured PV exceeds setpoint SP, relay actuates and latches in trip state. No automatic recovery upon temperature drop; manual key reset required. Meets hard cut-off safety requirements for ovens and heat treatment furnaces.

Configurable for high limit or low limit mode.

  1. Sensor Break Diagnosis

Breakage of thermocouple, RTD or 4-20mA signal triggers limit output action to prevent runaway caused by sensor failure.

  1. Parameter Password Lock

Parameter menu protected by password to prevent unauthorized modification of safety limit values. Password unlock required to edit SP, input type and latch mode.

  1. Dual 4-digit LED Display

Upper screen: PV real-time measured value; Lower screen: SP set limit value. Status LED indicates output/alarm/latch status.

  1. No PID Automatic Control

This instrument has no PID regulation function and cannot act as primary temperature controller. It serves only for independent safety over-limit protection, forming dual-loop safety temperature control system when paired with UDC1202 PID controller.

  1. Definizione del cablaggio dei terminali (DC120L Basic Version)

Nota importante: Relay contacts are passive dry contacts. Do NOT connect load power supply to instrument internal power terminals.

  1. l, N: Instrument power supply, 90~264VAC
  2. Sensor input terminals: Termocoppia / Pt100 / 4-20mA
  3. Main output relay: COM common, NO normalmente aperto, NC normalmente chiuso

Typical wiring: Use NC normally closed contact. Contact closes under normal temperature; opens upon over-temperature latch to cut heating circuit.

Wiring Recommendation: Use shielded twisted pair for sensor cables, routed separately from power cables to reduce interference.

  1. Specifiche di installazione
  2. Panel snap mounting, max panel thickness 6mm; reserve heat dissipation gap for side-by-side multi-unit installation.
  3. Temperatura ambiente operativa: 0~50℃; ambient humidity: 20~80%RH, no condensation and corrosive gas.
  4. Keep away from high-power contactors, frequency converters and strong electromagnetic interference sources.
  5. Messa a terra: Instrument chassis grounding; single-end grounding for shield layer.
  6. Operazione & Configuration Overview

6.1 Enter Parameter Menu

Press 【UP】+【SETUP】 simultaneously, inserire la password (common password:10/20) to unlock and enter configuration mode.

6.2 Key Configurable Parameters

Input type code (sensor model selection)

Full scale upper/lower range

Limit SP (safety protection threshold)

Limit mode: high limit latch / low limit latch

Latch enable/disable

Action logic for sensor break

Password setting & parameter locking

6.3 Latch Reset

After over-limit latch trip, perform manual reset via keys on operator interface to restore relay contacts to normal state.

  1. Scenari applicativi tipici

Independent over-temperature safety protection loops for industrial ovens, hot air furnaces, heat treatment furnaces, aging test chambers, environmental chambers, plastic extruders and food baking equipment.

Standard scheme: UDC1202 (PID main temperature control) + DC120L (independent temperature limit protection) dual-instrument redundant control complying with equipment safety standards.

  1. Tabella di diagnosi dei guasti
Fenomeno di guastoDirezione della risoluzione dei problemi
Sensor error displayedCheck sensor wiring polarity and breakage; verify input code matches sensor; controllare la messa a terra dello schermo
No latch after over-limitConfirm Latch function enabled in parameters; confirm limit mode instead of ordinary alarm mode
Relay fails to actuateCheck contact load rating; verify COM/NO/NC relay wiring; confirm instrument power supply
Parameters cannot be modifiedInstrument password locked, input unlock password; confirm not in read-only mode
Reading driftSeparare i cavi dei sensori dai cavi di alimentazione; check grounding; verify cold junction compensation for TC
  1. Alternative Model Information

Same Honeywell series: DC120L10011000 (version with RS485 communication)

Alternative domestiche: Yudian AI series limit controllers, Hongrun NHR-1100 (latch logic requires verification)

Legacy replacement: DC1000 series limit controller (interrotto)

  1. HS Code for Foreign Trade

Codice SA: 9032890090 Other automatic regulating or controlling instruments and apparatus

  1. Note sulla sicurezza
  2. This instrument is a safety limit protection device, cannot be used alone for process temperature control.
  3. External contactor is recommended for safety circuit. Relay contact capacity is limited and cannot directly drive high-power heating loads.
  4. Periodic over-temperature test on safety circuit is required to verify latch trip function.
  5. Disconnect power before instrument disassembly and wiring, comply with local electrical safety regulations.