Pepperl+Fuchs WE77/Ex-2 Installation & Guida al cablaggio
WE77/Ex-2: Dual-channel NAMUR isolated switch amplifier (intrinsically safe barrier). Must be installed in safe-area control cabinet only. Blue terminals = intrinsically safe side (connect to field explosion-proof sensors). White/red terminals = non-intrinsically safe side (connect to PLC and power supply).
Nome del prodotto: Isolated Intrinsically Safe Switch Amplifier
Nota: WE77/Ex-2 is an obsolete legacy model. Recommended replacement for new projects: KFA6-SR2-Ex2
- Definizione del codice modello
WE77: Famiglia di prodotti, NAMUR switch amplifier
Ex: Intrinsically safe explosion-proof design
2: Dual-channel version (WE77/Ex-1 = single-channel)
Two power supply variants:
- WE77/Ex-2 115V: 115Alimentazione CA
- WE77/Ex-2 230V: 230V (220V) Alimentazione CA, most common in China
- Funzioni principali
Intrinsically safe isolated barrier for NAMUR sensors and dry contact mechanical switches located in hazardous areas. It isolates and transmits binary switch signals from hazardous area to control system in safe area. Equipped with LB Lead Breakage detection, supports reverse operation mode. Each channel has independent relay change-over contact output.
Lato campo: Intrinsically safe circuit EEx ia IIC, suitable for Zone0/1/2 hazardous locations
Control side: Passive relay dry contact output (non-intrinsically safe)
Supported inputs: NAMUR proximity sensors (EN60947-5-6), passive mechanical contacts
- Specifiche elettriche principali
Intrinsically Safe Parameters (Lato campo)
U₀: 13.5 A DC
I₀: 62 mA
P₀: 125 mW
Explosion group: IIB / IIC
Permitted external values: IIB: Co=0.929µF, Lo=5mH; IIC: Co=0.23µF, Lo=3mH
NAMUR Input
Open circuit voltage ≈8V DC, short-circuit current ≈8mA
Switching threshold: 1.2~2.1mA, hysteresis approx.0.2mA
Lead breakage detection: Fault alarm upon cable disconnection
Uscita relè (1 SPDT change-over contact per channel)
Valutazione dei contatti: 250V AC /4A; 24VDC/4A
Tempo di risposta: Pull-in ≈10ms, Drop-out ≈20ms
Frequenza di commutazione massima: <10Hz
Vita meccanica: 10⁷ switching cycles
Alimentazione elettrica
230Versione V: 198~253 V CA, 45~65Hz; Power dissipation approx.2.5W
115Versione V: 103.5~126V AC, 45~65Hz
- Meccanico & Dati ambientali
Dimensione: 40(W) ×104(H) ×110(D) mm
Peso: approx.410g
Montaggio: DIN rail clip mounting
Protezione della custodia: IP20 (solo per installazione in armadio)
Temperatura ambiente: -25℃ ~ +60 ℃
Terminali: Morsetti a vite
- Informazioni sulla certificazione
Certificato ATEX: PTB 02 ATEX 2065 / PTB Ex-79/2043X
Explosion marking: II (1) GD [EEx ia] IIC
- Terminal Assignment (WE77/Ex-2)
Channel1 field input: terminale 1(-), 2(+)
Channel2 field input: terminale 8(+), 9(-)
Channel1 relay output: 10/11/12 (change-over contact)
Channel2 relay output: 13/14/15 (change-over contact)
Alimentazione elettrica: 17, 18
- Applicazione
Chimico, farmaceutico, olio & gas hazardous locations: Signal isolation for NAMUR proximity sensors, explosion-proof limit switches, explosion-proof level switches. Relay signals are sent to PLC/DCS DI modules.
- Pezzi di ricambio & Note di sostituzione
- WE77/Ex-2 no longer recommended for new projects by manufacturer. Sostituzione diretta: KFA6-SR2-Ex2 (dual-channel NAMUR safety barrier, uscita relè, equivalent function, smaller footprint)
- For maintenance of existing systems: Only surplus / stock spare parts available. Confirm 115V or 230V variant before procurement, the two versions are not interchangeable.
- Single-channel equivalent: WE77/Ex-1, replacement KFA6-SR1-Ex
- Risoluzione dei problemi comuni
- No input response: Check for LB lead breakage alarm on NAMUR loop; verify external capacitance/inductance does not exceed intrinsic safety limits
- Relay fails to switch: Confirm power supply variant matches device rating; verify input current falls within NAMUR operating range
- Frequent false lead breakage alarm: Excessive cable length with high distributed capacitance/inductance, or damaged cable insulation
- Installazione meccanica
- Guida DIN: Montaggio su guida DIN standard da 35 mm. Hook top clip onto rail, press module down to lock. Per rimuovere: Lift bottom latch and pull outward.
- Ambiente operativo
Temperatura ambiente: -25℃ ~ +60 ℃, cabinet ventilation required; keep away from heat sources, vibration and corrosive gas
Classe di protezione IP20, solo per uso in armadietti interni, not for open or humid direct exposure
Mounting clearance: Small gaps between adjacent modules recommended for heat dissipation
- Mandatory Explosion Protection Rules
✅ Unit must be mounted in safe area, NEVER install in Zone0/1/2 hazardous areas
✅ Intrinsically safe cables (blu) and non-intrinsically safe cables (energia, uscita relè) must run in separate trunking/conduits, cannot share same conduit
- Terminal Table
| Terminal Group | Terminale n. | Descrizione | Circuit Classification |
| Channel1 Field NAMUR Input (Blue IS Terminals) | 1(-), 2(+) | Channel1: NAMUR proximity sensor / explosion-proof dry contact | Intrinsically safe EEx ia IIC |
| Channel2 Field NAMUR Input (Blue IS Terminals) | 8(+), 9(-) | Channel2: NAMUR proximity sensor / explosion-proof dry contact | Intrinsically safe EEx ia IIC |
| Channel1 Relay Change-over Output | 10, 11, 12 | 11 Comune, 10 NC Normalmente Chiuso, 12 NONormalmente aperto | Non-intrinsically safe relay |
| Channel2 Relay Change-over Output | 13, 14, 15 | 14 Comune, 13 NC Normalmente Chiuso, 15 NONormalmente aperto | Non-intrinsically safe relay |
| Alimentazione elettrica | 17, 18 | AC power input: Select 115V /230V variant, non intercambiabile | Non-intrinsically safe |
Importante: NAMUR field wiring is polarity sensitive. Reversed polarity will trigger LB lead breakage fault and unit malfunction.
- Wiring Schemes
Schema 1: NAMUR Proximity Sensor (Più comune)
Channel1: 2-wire NAMUR sensor → Terminals 1(-), 2(+)
Channel2: 2-wire NAMUR sensor → Terminals 8(+), 9(-)
NAMUR loop includes LB lead breakage monitoring: Rottura del cavo, short circuit or reversed polarity will trigger channel fault LED.
Schema 2: Explosion-proof Passive Dry Contact (Interruttore di limite)
Dry contact directly connected to IS terminals, lead breakage detection remains active. No external supply for contact; WE77/Ex-2 provides approx.8V/8mA IS drive internally.
Relay Output Wiring (to PLC DI)
Each channel is SPDT passive change-over contact, no external supply required
Channel1: 11 Comune, 12 NO, 10 NC
Channel2: 14 Comune, 15 NO, 13 NC
Contact maximum rating: 250V e / 4UN; 24VDC /4A. Do not overload to avoid contact burnout.
Cablaggio di alimentazione
Terminali 17 & 18 for AC supply:
WE77/Ex-2 230V version: AC 198~253V (Mainland China standard)
WE77/Ex-2 115V version: AC 103.5~126V
⚠️ Hardware differs between two power versions, NON intercambiabile.
- Selezione del cavo (Explosion Compliance Mandatory)
- Intrinsically safe side (Blue terminals to field instrument): Blue IS cable recommended, conductor cross-section ≥0.5mm², rated voltage ≥500V
- Intrinsically safe loop must be verified for maximum permitted cable capacitance Co and inductance Lo:
IIC application: Co ≤0.23µF, Lo ≤3mH
IIB application: Co ≤0.929µF, Lo ≤5mH
Excessive cable length causes distributed capacitance/inductance over-limit, invalidating intrinsic safety certification.
- Cavo schermato: Shield single-point earthed at control room end, shield floating at hazardous area side to prevent earth loop current.
- Procedura di cablaggio (Safety Sequence)
- Spegnimento! Isolate all power sources and confirm zero voltage before wiring
- Connect field intrinsically safe cables first (blue terminals), verify polarity
- Connect relay output cables to PLC DI modules
- Connect module power terminals 17 &18 scorso
- Tighten all screw terminals, no loose strands or exposed copper causing short circuit
- Controllo pre-accensione: IS cables separated from power cables, no mixed routing
- Power-on commissioning: Power on without field load first and check channel LEDs. Connect field sensors, test switching action and LB fault function.
- Messa in servizio & LED Indication
Independent LED per channel: Illuminated when valid input signal present; LB lead breakage fault will extinguish LED / trigger fault alarm
Modalità operativa: Reversible mode available (relay de-energizes when input activates), configurable per project requirement
Lead breakage test: Disconnect field sensor wire, module shall detect line fault and activate LB alarm.
- Critical Prohibitions & Insidie comuni
- ❌ Megger insulation test is forbidden on intrinsically safe terminals! High voltage from megger will destroy internal IS circuit and permanently damage unit. Remove all IS wiring before any cable high voltage test.
- ❌ Never route 220V power cables or non-IS signal wires into blue intrinsically safe terminals; intrinsic safety protection will be destroyed.
- ❌ IS circuits and non-IS circuits cannot share same cable or trunking.
- ❌ Do not install WE77/Ex-2 in hazardous area.
- ❌ Do not exceed Co/Lo intrinsic safety limits, explosion certification will be invalid.
- ❌ Do not overload relay contacts; damaged relay contacts cannot be repaired separately, full module replacement required.
- Earthing Instruction
WE77/Ex-2 is transformer-isolated safety barrier; galvanic isolation between IS side and control side. Module housing connected to cabinet protective earth as standard, resistenza di terra ≤4Ω. Isolated barrier does NOT require dedicated intrinsic safety earth like zener barriers.
- Post Power-On Quick Fault Diagnosis
- No LED illumination after power-up: Check voltage at terminal 17/18, confirm 115V/230V model match, check loose power terminals.
- Persistent LB fault alarm: ①NAMUR polarity reversed; ②broken cable; ③cable distributed capacitance/inductance over-limit; ④field sensor damaged.
- Sensor switches but relay does not toggle: Verify NAMUR current within operating range; check NO/NC contact selection.
- Unintended relay chattering/false switching: Fluttuazione di potenza, electromagnetic interference. Use shielded cable and separate strong/weak signal wiring.
WE77/Ex-2 Intrinsically Safe Blue Terminals & Non-Intrinsically Safe Relay Terminal Current Parameters
Distinguish between intrinsic safety certified maximum short-circuit current Io (explosion parameter) and NAMUR normal operating current. Non-intrinsically safe side is relay contact rated current.
🔵 Blue Terminals: Intrinsically Safe Field Input Side
WE77/Ex-2 230V version (Mainland China mainstream)
- Intrinsic safety maximum short-circuit current Io = 62mA (certified explosion parameter. In short-circuit condition, module limits output current below this value to maintain explosion safety)
- NAMUR normal operating current: Open circuit ≈8V DC, static short-circuit current ≈8mA; Switching threshold 1.2~2.1mA per NAMUR standard
Note for 115V WE77/Ex-2 variant: Io=31mA. Always confirm power supply version during selection.
⚠️ Importante: 62mA is the safety limit short-circuit current, NOT normal working current. Under normal NAMUR sensor operation, loop current is only a few milliamps.
⚪ White Terminals: Non-intrinsically Safe Relay Output (Terminali 10/11/12,13/14/15)
SPDT change-over contact rated load current (carico resistivo) per channel
CA 250 V: 4UN (cosφ>0.7)
CC 24 V: 4UN
DC 60V: 0.6UN
CC 220 V: 0.1UN
Max contact power rating: 500VA; Overload will cause contact erosion, module non-repairable.
Ulteriori: Module Power Terminals (17,18)
Total power dissipation approx.2.5W. For 230V AC supply, power loop current is low, ca.0.01UN.
Summary Table
| Terminal Group | Articolo | Valore | Osservazioni |
| Blue IS Terminals (230Modello V) | Intrinsic safety limit short-circuit current Io | 62mA | Explosion protection short-circuit limit |
| Blue IS Terminals | NAMUR normal short-circuit current | ≈8mA | NAMUR sensor operating current |
| White Non-IS Relay Contacts | Rated current at AC250V / DC24V | 4UN | Carico resistivo, independent per channel |