- Panoramica del prodotto
Modello: BMXCPS3500
Serie: Modicon X80 Rack-mounted Alimentazione elettrica (Compatible with M340 / M580 PLCs)
Posizionamento: 36W standard AC input backplane power supply for medium & large X80 racks, with isolated 24V sensor output built-in
Modello derivato: BMXCPS3500H (Versione per ampie temperature, -25℃ ~ +70 ℃)
Scomposizione del codice modello
BMX-CPS-3500
BMX: Modicon X80 platform series
CPS: Control Power Supply rack power module
3500: 36W wide AC voltage high-power variant
- Specifiche elettriche principali
2.1 Input Ratings (AC)
Nominal Voltage: 100~240 V CA
Full Wide Voltage Range: 85~264V AC (Universal for global power grids)
Frequenza: 47~63Hz (50/60Compatibile con Hz)
Corrente in ingresso: 1.04A @115V / 0.52A @240V
Corrente di spunto: 30A @120V / 60A @240V (Built-in soft start)
Potenza apparente: 120VA
Input Fuse: Non-replaceable internal fuse
2.2 Three Isolated DC Outputs (Total Rated Power: 36W)
| Output Channel | Voltaggio | Corrente nominale | Energia | Applicazione |
| Logic Power | 3.3A DC | 4.5UN | 15W | processore, bus backplane, I/O logic chips |
| Main Rack 24V | 24A DC | 1.3UN | 31.2W | Moduli CPU, digital/analog I/O, moduli di comunicazione |
| Isolated Sensor 24V | 24A DC | 0.9UN | 21.6W | 4-20mA transmitters, field sensors, valvole |
> Key Limitation: All three channels cannot run at full load simultaneously; maximum total output power of the unit is 36W.
2.3 Meccanico & Specifiche ambientali
Dimensioni complessive: 242.4 × 35 × 110 mm (Single-slot X80 rack module)
Peso netto: 0.36kg
Classe di protezione: IP20 (Solo per installazione in armadio)
Standard Operating Temperature: 0℃ ~ +60 ℃
Wide-temperature Model 3500H: -25℃ ~ +70 ℃ (Automatic power derating at high temperatures)
Temperatura di conservazione: -40℃ ~ +85 ℃
Umidità: 5%~95% di umidità relativa, senza condensa
MTBF: 4.3 milioni di ore (Continuous operation at 25℃)
2.4 Sicurezza & Certificazioni EMC
CE, UL508, CSA, RCM, EAC, ATEX explosion-proof certification
Standard conformi: IN 61131-2, IN 61000-6-2/6-4, IN 61010-2-201
- Front Panel Interfaces & Funzioni
- 5-pin Main Terminal Block
L/N: AC mains input
PE: Terra protettiva
24V+/0V: Isolated sensor power output (0.9UN)
- 2-pin Alarm Relay Terminal Block
Passive dry contact; contacts open upon power failure; connect to upper-level alarms or audible/visual annunciators
- Dual LED Status Indicators
OK (Verde): Main rack power normal; Off = Backplane power fault
24V SENSOR (Verde): Sensor 24V output normal; Off = Short circuit / overload on sensor circuit
- RESET Button: Cold restart of the rack, quick reset for CPU and backplane bus
- Built-in Protection Mechanisms
Lato ingresso: Overcurrent fusing, soppressione dei picchi
Lato di uscita: Sovratensione (OVP), Sovracorrente (OCP), short-circuit latch-off, sovratemperatura (OTP)
Independent isolated short-circuit protection for sensor circuit, no impact on PLC rack power supply
Fault Latch: After clearing short circuit, power cycle or press RESET to restore operation
- X80 Power Supply Selection Comparison within the Same Series
| Modello | Tipo di ingresso | Potenza totale | Sensor 24V Current | Applicable Rack Scale |
| BMXCPS2000 | 85~264V AC | 20W | 0.45UN | Small racks ≤12 slots |
| BMXCPS3500 | 85~264V AC | 36W | 0.9UN | Medio & large multi-rack systems |
| BMXCPS3500H | 85~264V AC | 36W | 0.9UN | Severe high/low temperature sites |
| BMXCPS4002 | 24A DC | 40W | 1.6UN | DC-powered control cabinets, on-board equipment |
Selection Conclusion for Replacement
- Downward Replacement: BMXCPS2000 can be used if total load <20W, but sensor power capacity is halved; not directly interchangeable for high-load systems.
- Upward Replacement: No higher-power AC-input X80 power supply available. Multiple BMXCPS3500 units shall be configured for separate racks in multi-rack systems.
- Low-temperature Applications: BMXCPS3500H is mandatory for field temperatures below 0℃; standard 3500 will derate or trigger faults at low temperatures.
- Scenari applicativi tipici
- Medio & large Modicon M340/M580 PLC control systems
- Main control cabinets for water treatment, metallurgia, chimico, packaging machinery and building automation
- Projects requiring independent isolated 24V power for transmitters, flow meters and pressure sensors
- Centralized power supply for multi-expansion racks (BMXXBP series backplanes)
- Matrice di risoluzione dei problemi
| Fenomeno di guasto | Causa ultima | Handling Procedures |
| Both LEDs fully off | No AC input, cablaggio allentato, fusibile interno bruciato | 1. Measure L/N voltage; 2. Stringere i terminali; 3. Replace module if fuse blown |
| LED OK spento, Sensor LED on | Total rack load exceeds 36W, backplane short circuit | 1. Calculate total power consumption of all modules; 2. Remove redundant I/O modules; 3. Inspect backplane for short circuit |
| Only 24V Sensor LED off | Cortocircuito / overload on sensor circuit | 1. Disconnect external sensor cables; 2. Locate short circuit in field wiring; 3. Restart power supply after recovery |
| Indicators flicker after running for a period | Ambient temperature over 60℃, scarsa dissipazione del calore | Install cabinet cooling fan, replace with 3500H wide-temperature model, reduce rack load |
| Alarm relay remains open | Protection triggered on any output channel | Power off for 5 minutes to cool down, inspect short circuit and overloaded loads |
- Installazione & Divieti di cablaggio (Regole dure)
- Do not share the same circuit with high-power inverters and contactors; separate isolated power supply is required.
- Sensor 24V cables shall not be routed in the same trunking as power cables to avoid interference.
- The module must be reliably connected to PE protective earth; otherwise EMC interference may cause false alarms.
- Total load of a single 3500 unit is strictly limited to 36W max; separate power supplies must be used for multiple racks.
- Do not plug/unplug the module during operation (no hot-swap design); replace only after power cut-off.
- Compatible Backplanes
Fully compatible with all BMXXBP X80 backplanes: BMXXBP0400 / 0600 / 0800 / 1200, ecc.
Incompatibile: Old-generation Quantum BMEXBP series backplanes; mixed use is forbidden.
Complete Installation Specification for Schneider BMXCPS3500
- Core Installation Structure (Two Layers)
1.1 Base Layer: 35mm Montaggio su guida DIN standard (Cabinet Rear Panel)
The unit is equipped with a built-in DIN35 standard snap-on base, compatible with national standard 35mm electrical mounting rails (AM1 ED rail).
Module width: 35mm, single-slot occupation; dimensioni: 242.4 (H) × 35 (W) × 110 (D) mm
Snap structure: Dual upper & lower elastic snaps for rail fastening without screws; top/bottom latches prevent detachment
Rail mounting steps:
- Secure 35mm DIN rail to cabinet rear panel, ensure rail is level and undeformed
- Hook the module’s bottom snap onto the lower edge of the rail first, then push the upper part of the module upward until a “clic” sound confirms full engagement
- Fully lock both upper and lower snaps; no vertical looseness under pulling force. Per rimuovere, pry open upper/lower snaps with a flat screwdriver.
1.2 Strato superiore: X80 Dedicated Backplane Slot Installation (Core Rack Power Connection)
BMXCPS3500 must be inserted into BMXXBP series X80 rack backplanes to supply power to CPU and I/O backplanes; standalone operation without backplane is not allowed.
Compatible Backplane Models
Only compatible: BMXXBP0400 / 0600 / 0800 / 1200 (including H wide-temperature variants)
Mixed Use Forbidden: Old BMEXBP…02 Quantum backplanes with mismatched physical connectors.
Standard Backplane Mounting Procedure (Power Off Mandatory, Hot Swap Prohibited)
- Cut off power to the whole unit and disconnect AC input
- Align the metal guide slots on the rear of the power module with upper/lower rails of the rack backplane, slide horizontally smoothly to the bottom of the slot
- After full insertion, backplane bus gold fingers are fully mated; front face of the module aligns flush with other I/O modules
- Built-in left & right locking latches on the module, snap inward to lock onto the rack and prevent loosening under vibration
- Power supply shall be installed in the 1st leftmost slot of the rack as priority (Official recommended layout); one CPS3500 for each independent backplane in multi-rack systems.
- Mounting Attitude & Tilt Restrictions
- Standard Attitude: Vertical upright installation (cabinet rear panel vertical, module vertical top-to-bottom) for vertical convection cooling airflow, optimal heat dissipation
- Allowable Tilt: Full-load operation permitted within ±30° panel tilt; derating required if tilt exceeds 30°, cabinet internal temperature ≤40℃
- Severamente proibito: Horizontal flat or upside-down mounting – airflow blocked, frequent overtemperature tripping, drastically shortened service life.
- Mandatory Heat Dissipation Clearance Requirements (Hard Installation Gaps)
The module relies on natural air cooling via top & bottom ventilation holes; clearances must be reserved:
Above & below the module: ≥20mm free space, unobstructed by cable ducts or other components
Sinistra & right sides of the module: ≥10mm, no tight contact with adjacent modules
Horizontal distance between heat-generating components (inverter, contattori) and power supply inside cabinet ≥50mm
Cooling fan recommended for sealed small cabinets; replace with BMXCPS3500H wide-temperature model if ambient temperature >55℃.
- Terminal Accessory Installation (Wiring Matching Parts)
Standard factory supply: Screw-type terminal block BMXXTSCPS10; Spring push-in terminal block BMXXTSCPS20 available as separate order.
- 5-pin main power terminal (L/N/PE/24V circuit/Sensor 24V): Insert horizontally into lower front interface of module, lock via built-in snap
- 2-pin alarm dry contact terminal: Adjacent to the right of 5-pin terminal, used for fault alarm output
- Terminal Removal: Pinch both side snaps of terminal and pull straight outward; diagonal pulling is prohibited to avoid broken pins.
- Ambiente di installazione & Protection Specifications
- Classe di protezione IP20, solo installazione in armadio; no direct exposure to outdoor environment, dust or moisture.
- Flat, burr-free mounting surface; firmly fixed DIN rail; rail end stops required for high-vibration operating conditions.
- PE protective earth wire must be reliably connected to cabinet earth bar to reduce EMC interference.
- No power derating required for altitude ≤2000m; 10% load derating mandatory above 2000m.
- Divieti di installazione (Absolute Forbidden Operations)
- Plug/unplug module or wiring terminals while powered – risk of burning backplane bus and power supply.
- Unlocked fixing latches cause poor backplane contact and system shutdown under long-term vibration.
- Insufficient top/bottom heat dissipation space or close contact with cable ducts triggers overtemperature protection under high temperature.
- Upside-down / flat mounting blocks cooling airflow.
- Mixed use of old BMEXBP backplanes with mismatched physical connectors; forced insertion damages gold fingers.
- Single power supply driving multiple independent backplanes leads to overload protection triggered when total power exceeds 36W.
- Supplementary Redundant Power Supply Installation (Multi-Power Scenarios)
Per alimentazione ridondante, install one BMXCPS3500 in two separate slots of the same rack, each fed by an independent AC circuit. The backplane performs automatic redundant switching. Reserve ≥15mm heat dissipation gap between the two power supplies.
Contattore,interruttore automatico,inverter solare,contatore elettrico,sensore,Codificatore,PLC