Interrotto (Siemens stopped delivery effective Oct 01, 2023), legacy obsolete model. Factory recommended replacement: 3RW5055-6AB14
- Ripartizione del numero d'ordine
3RW: SIRIO avviatore morbido serie
40: Basic soft starter, bypass integrato, 2-phase thyristor control (Phase L1, L3)
55: S6 frame, rated current code 134A
6: Morsetti a vite
BB: Configurazione standard
4: Alimentazione di controllo AC230V
- Specifiche elettriche principali
| Articolo | Parametro |
| Modello | 3RW4055-6BB44 |
| Telaio | S6 |
| Corrente operativa nominale Ie (40℃) | 134 UN |
| Rated motor power @400V,40℃ | 75 kW |
| Main circuit voltage Ue | AC 200~460V |
| Controllare l'offerta | CA 230 V |
| Frequenza | 50/60Hz |
| Built-in bypass contactor | ✅ Sì. Bypasses thyristors after start to reduce heat generation |
| Protezione da sovraccarico del motore | ✅ Integrated motor overload protection (Classe 10) |
| Current limiting function | ✅ Adjustable current limit |
| PTC thermistor motor protection | ❌ Non supportato |
| Inside-delta connection | ❌ Non supportato, standard external connection only |
| Classe di protezione | IP00 |
| Dimensioni complessive (A × L × P) | 198 × 120 × 250 mm |
| Peso | 4.976 kg |
- Ambiente & Condizioni di installazione
- Temperatura ambiente: -25℃ ~ +60 ℃. Declassamento richiesto sopra i 40 ℃; rated current reduces to 100A at 60℃
- Altitudine di installazione: Max 5000m. Derating required above 1000m; main circuit upper limit reduced to 460V above 2000m
- Max cable length from soft starter to motor: 300M
- Installation clearance: ≥100mm superiore, ≥5mm side, ≥75mm bottom
- Grado di inquinamento: 3 (CEI 60947-4-2)
- Descrizione della funzione
2-phase thyristor voltage regulation soft start, bypass integrato. Mechanical contacts carry load current during continuous operation for low power loss
Adjustable start ramp and current limit; external reset supported
Integrated equipment fault protection and motor overload protection; fault relay outputs (95/96, 95/98)
Single direction start, no braking output; no communication interface (3RW40 series without Modbus/Profinet)
Typical loads: pompe dell'acqua, tifosi, compressors and general loads. Not suitable for frequent heavy-duty starting
- Selezione & Opzioni di sostituzione
- Factory direct upgrade model: 3RW5055-6AB14 (New 3RW5 generation)
Same rating 134A /75kW@400V, AC230V control, terminali a vite; protezione rafforzata, optional communication module
- Domestic alternative candidates (same current rating): Renle, Xipu, Cinto, Delixi soft starters, 134Una classe.
- Guida alla risoluzione dei problemi (General for 3RW40 series)
- No power-up display: Check 230V control supply and terminal wiring
- Overload trip during startup: Verify motor rated current setting; derating required under high ambient temp or frequent start-stop
- No torque on start: Inspect main incoming power, thyristors and bypass contacts
- Inciampi frequenti: Check harmonic distortion and whether semiconductor fast fuses are fitted upstream
Tabella comparativa: 3RW4055-6BB44 VS 3RW5055-6AB14
3RW4055-6BB44: Discontinued legacy unit; 3RW5055-6AB14: Factory recommended replacement, terminale a vite, bypass integrato, 2-phase thyristor soft starter
| Elemento di confronto | 3RW4055-6BB44 | 3RW5055-6AB14 | Osservazioni |
| Ordine n. | 3RW4055-6BB44 | 3RW5055-6AB14 | Official direct replacement by Siemens |
| Serie di prodotti | SIRIUS 3RW40 (Basic Soft Starter) | SIRIUS 3RW50 (New Generation Basic Soft Starter) | 3RW40 discontinued since Oct 2023 |
| Rated operational current Ie @40℃ | 134 UN | 143 UN | New model with larger current margin |
| Rated motor power @400V,40℃ | 75 kW | 75 kW | Both for standard 75kW loads |
| Main circuit voltage Ue | AC 200~460 V | AC 200~480 V | New model extended upper limit to 480V |
| Controllare l'offerta | Fixed AC230V | Wide range AC110~250V | Key difference: universal control supply for 110V/220V |
| Thyristor control phases | 2-controllo di fase (L1, L3) | 2-controllo di fase (L1, L3) | Same topology, no modification required for primary power circuit |
| Built-in bypass contactor | ✅ Sì | ✅ Sì | Thyristor bypass after start for low running loss |
| Protezione da sovraccarico | Integrated motor overload Class10 | Integrated electronic overload Class10 | Same protection class |
| PTC thermistor motor protection | ❌ Non supportato | ❌ Non supportato | Neither has PTC input |
| Inside-delta connection | ❌ Non supportato | ❌ Non supportato | Standard external connection only |
| Sosta morbida | Basic ramp only | Sosta morbida + pump ramp down | Pump-friendly function on new model |
| Adjustable current limit range | 130%~400% | 130%~700% | Wider limit range for new model |
| Uscita analogica | ❌ None | ✅ Built-in 4~20mA (configurable to 0~10V) | Transmit current/load signal to PLC |
| Porta di comunicazione | ❌ No communication, non-expandable | ✅ Optional Profinet/Modbus communication module | Legacy model has no communication capability |
| Fault history | Basic fault relay only | Fault log available (with optional HMI module) | New model can retrieve historical faults |
| I/O digitali | Fixed relay outputs (95/96,95/98) | Programmable DI/DO, 3 programmable outputs +1 fixed changeover contact | More flexible secondary control logic |
| Operator unit | Dip-switch setting on board | Dip-switch + optional external HMI module | Legacy no display; new HMI for parameter & current reading |
| Classe di protezione | IP00 | IP00 | For cabinet mounting only |
| Dimensione (H × W × D mm) | 198 × 120 × 250 | 200 × 120 × 240 | Stessa larghezza, similar height, shorter depth; fori di montaggio compatibili |
| Peso netto | 4.976 kg | 4.0 kg | New model lighter |
| Temperatura ambiente | -25℃ ~ +60 ℃ | −25℃ ~ +60℃ | Derating required at high temperature for both |
| Max motor cable length | 300 M | 300 M | Identico |
| Installation clearance | ≥100mm superiore, ≥5mm side, ≥75mm bottom | ≥100mm superiore, ≥5mm side, ≥75mm bottom | Same installation space requirement |
| Grado di inquinamento | 3 (IEC60947-4-2) | 3 (IEC60947-4-2) | Identico |
| Ciclo vitale | Interrotto, spare parts limited | In produzione, regular stock | Preferred model for retrofit & nuovi progetti |
Replacement Implementation Key Points (Engineering Focus)
- Primary power circuit: Pienamente compatibile. Incoming and motor terminal positions basically match; direct replacement without re-routing power cables.
- Secondary control circuit
Legacy unit fixed AC230V supply; new model accepts AC110~250V wide range. Existing 230V control circuit works directly.
Relay logic is similar, but new DO channels are user configurable. Verify fault/run relay logic after power-on.
New 4~20mA analog output can be left unconnected if not required.
- Parameter re-setting: Corrente nominale del motore, start ramp and current limit must be re-programmed in new soft starter; parameters from old unit cannot be reused directly.
- Protection scheme: Selection principle for upstream semiconductor fast fuses unchanged; retain original short-circuit protection.
Application Difference Summary
3RW4055: For existing legacy equipment, simple soft start only, no monitoring, nessuna comunicazione, no analog output.
3RW5055: Preferred for new projects and retrofits. Pump ramp-down recommended for pump applications. Supports communication and 4-20mA current feedback to PLC for SCADA monitoring.
- 3RW40 (Discontinued Legacy Series|2-phase thyristor, bypass integrato, series of target model)
Main circuit AC200~460V, bypass integrato, Class10 motor overload protection. Suffix defines terminal type, control supply and PTC option; @40℃, rated motor power at 400V.
| Ordine n. | Telaio | Cioè(UN) | Motor Power @400V(kW) | Osservazioni |
| 3RW4024-1BB04 | S0 | 12.5 | 5.5 | Screw terminal AC230V |
| 3RW4026-1BB04 | S0 | 25 | 11 | Screw terminal AC230V |
| 3RW4027-1BB04 | S0 | 32 | 15 | Screw terminal AC230V |
| 3RW4028-1BB04 | S0 | 38 | 18.5 | Screw terminal AC230V |
| 3RW4036-1BB04 | S2 | 45 | 22 | Screw terminal AC230V |
| 3RW4037-1BB04 | S2 | 63 | 30 | Screw terminal AC230V |
| 3RW4038-1BB04 | S2 | 72 | 37 | Screw terminal AC230V |
| 3RW4046-1BB04 | S3 | 80 | 45 | Screw terminal AC230V |
| 3RW4047-1BB04 | S3 | 106 | 55 | Screw terminal AC230V |
| 3RW4055-6BB44 | S6 | 134 | 75 | Screw terminal AC230V (target model) |
| 3RW4056-6BB44 | S6 | 171 | 90 | Screw terminal AC230V |
| 3RW4072-6BB44 | S12 | 210 | 110 | Screw terminal AC230V |
| 3RW4073-6BB44 | S12 | 250 | 132 | Screw terminal AC230V |
| 3RW4074-6BB44 | S12 | 315 | 160 | Screw terminal AC230V |
| 3RW4075-6BB44 | S12 | 370 | 200 | Screw terminal AC230V |
| 3RW4076-6BB44 | S12 | 470 | 250 | Screw terminal AC230V |
| 3RW4077-6BB44 | S12 | 570 | 315 | Screw terminal AC230V |
Supplementare: Same current ratings also available with spring-cage terminals (suffix 2BBxx), 24V control supply, PTC thermistor version (TBxx). Table above lists only mainstream models with screw terminal & AC230V control supply same as 3RW4055-6BB44.
Series feature: 2-phase L1/L3 control, bypass integrato, nessuna comunicazione, no analog output; 3RW405~407 (S6/S12) support PTC motor thermal protection.
- 3RW50 (New Generation Replacement Series|Successor of 3RW40, Active Production)
Main circuit AC200~480V, bypass integrato, 2-phase thyristor, wide control supply AC110~250V; built-in 4~20mA analog output, optional Profinet/Modbus module, pump soft stop function.
| Ordine n. | Telaio | Cioè(UN) | Motor Power @400V(kW) | Osservazioni |
| 3RW5024-6AB14 | S0 | 12.5 | 5.5 | Terminale a vite, wide range control supply |
| 3RW5026-6AB14 | S0 | 25 | 11 | Terminale a vite, wide range control supply |
| 3RW5027-6AB14 | S0 | 32 | 15 | Terminale a vite, wide range control supply |
| 3RW5028-6AB14 | S0 | 38 | 18.5 | Terminale a vite, wide range control supply |
| 3RW5036-6AB14 | S2 | 45 | 22 | Terminale a vite, wide range control supply |
| 3RW5037-6AB14 | S2 | 63 | 30 | Terminale a vite, wide range control supply |
| 3RW5038-6AB14 | S2 | 72 | 37 | Terminale a vite, wide range control supply |
| 3RW5046-6AB14 | S3 | 80 | 45 | Terminale a vite, wide range control supply |
| 3RW5047-6AB14 | S3 | 106 | 55 | Terminale a vite, wide range control supply |
| 3RW5055-6AB14 | S6 | 143 | 75 | Screw terminal AC110~250V (Official replacement for 3RW4055-6BB44) |
| 3RW5056-6AB14 | S6 | 171 | 90 | Terminale a vite, wide range control supply |
| 3RW5072-6AB14 | S12 | 210 | 110 | Terminale a vite, wide range control supply |
| 3RW5073-6AB14 | S12 | 250 | 132 | Terminale a vite, wide range control supply |
| 3RW5074-6AB14 | S12 | 315 | 160 | Terminale a vite, wide range control supply |
| 3RW5075-6AB14 | S12 | 370 | 200 | Terminale a vite, wide range control supply |
| 3RW5076-6AB14 | S12 | 470 | 250 | Terminale a vite, wide range control supply |
| 3RW5077-6AB14 | S12 | 570 | 315 | Terminale a vite, wide range control supply |
Supplementare: 3RW50 same current ratings also available with spring-cage terminals (2AB14), 24V control supply and PTC version (TBxx).
- Brief Introduction of Other Soft Starter Series in Same Family (Riferimento alla selezione)
- 3RW30: Entry-level basic model, 2-fase, bypass integrato, low power range, no PTC, nessuna comunicazione; lower grade than 3RW40
- 3RW44: Legacy high-performance type (interrotto). Supports inside-delta connection, 3-phase thyristor, rich protections, suitable for heavy duty
- 3RW52: New generation high performance. Supports inside-delta, 3-phase thyristor, for heavy-duty fans & compressori; replacement for legacy 3RW44
- 3RW55: High-end safety version including F safety variant, for high safety integrity applications
- Order Number Coding Quick Reference (3RW40 / 3RW50)
Take `3RW4055-6BB44` as example
3RW: SIRIUS soft starter
40: Codice della serie
55: Codice di valutazione attuale
6: Terminale a vite (2 = spring-cage terminal)
BB / AB: Base hardware revision
4: Main voltage code
4: Control supply code
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore