SIEMENS 3RW4055-6BB44 Soft Starter - Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Di Contatto |

 SIEMENS 3RW4055-6BB44 Soft Starter - Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore

PLC/

SIEMENS 3RW4055-6BB44 Soft Starter

Interrotto (Siemens stopped delivery effective Oct 01, 2023), legacy obsolete model. Factory recommended replacement: 3RW5055-6AB14 Order Number Breakdown 3RW: SIRIUS soft starter series 40: Basic soft starter, bypass integrato, 2-phase thyristor control (Phase L1, L3) 55: S6 frame, rated current code 134A 6: Screw terminals BB: Configurazione standard 4: Control supply AC230V Core Electrical Specifications ...

  • Dettagli del prodotto

Interrotto (Siemens stopped delivery effective Oct 01, 2023), legacy obsolete model. Factory recommended replacement: 3RW5055-6AB14

  1. Ripartizione del numero d'ordine

3RW: SIRIO avviatore morbido serie

40: Basic soft starter, bypass integrato, 2-phase thyristor control (Phase L1, L3)

55: S6 frame, rated current code 134A

6: Morsetti a vite

BB: Configurazione standard

4: Alimentazione di controllo AC230V

  1. Specifiche elettriche principali
ArticoloParametro
Modello3RW4055-6BB44
TelaioS6
Corrente operativa nominale Ie (40℃)134 UN
Rated motor power @400V,40℃75 kW
Main circuit voltage UeAC 200~460V
Controllare l'offertaCA 230 V
Frequenza50/60Hz
Built-in bypass contactor✅ Sì. Bypasses thyristors after start to reduce heat generation
Protezione da sovraccarico del motore✅ Integrated motor overload protection (Classe 10)
Current limiting function✅ Adjustable current limit
PTC thermistor motor protection❌ Non supportato
Inside-delta connection❌ Non supportato, standard external connection only
Classe di protezioneIP00
Dimensioni complessive (A × L × P)198 × 120 × 250 mm
Peso4.976 kg
  1. Ambiente & Condizioni di installazione
  2. Temperatura ambiente: -25℃ ~ +60 ℃. Declassamento richiesto sopra i 40 ℃; rated current reduces to 100A at 60℃
  3. Altitudine di installazione: Max 5000m. Derating required above 1000m; main circuit upper limit reduced to 460V above 2000m
  4. Max cable length from soft starter to motor: 300M
  5. Installation clearance: ≥100mm superiore, ≥5mm side, ≥75mm bottom
  6. Grado di inquinamento: 3 (CEI 60947-4-2)
  7. Descrizione della funzione

2-phase thyristor voltage regulation soft start, bypass integrato. Mechanical contacts carry load current during continuous operation for low power loss

Adjustable start ramp and current limit; external reset supported

Integrated equipment fault protection and motor overload protection; fault relay outputs (95/96, 95/98)

Single direction start, no braking output; no communication interface (3RW40 series without Modbus/Profinet)

Typical loads: pompe dell'acqua, tifosi, compressors and general loads. Not suitable for frequent heavy-duty starting

  1. Selezione & Opzioni di sostituzione
  2. Factory direct upgrade model: 3RW5055-6AB14 (New 3RW5 generation)

Same rating 134A /75kW@400V, AC230V control, terminali a vite; protezione rafforzata, optional communication module

  1. Domestic alternative candidates (same current rating): Renle, Xipu, Cinto, Delixi soft starters, 134Una classe.
  2. Guida alla risoluzione dei problemi (General for 3RW40 series)
  3. No power-up display: Check 230V control supply and terminal wiring
  4. Overload trip during startup: Verify motor rated current setting; derating required under high ambient temp or frequent start-stop
  5. No torque on start: Inspect main incoming power, thyristors and bypass contacts
  6. Inciampi frequenti: Check harmonic distortion and whether semiconductor fast fuses are fitted upstream

Tabella comparativa: 3RW4055-6BB44 VS 3RW5055-6AB14

3RW4055-6BB44: Discontinued legacy unit; 3RW5055-6AB14: Factory recommended replacement, terminale a vite, bypass integrato, 2-phase thyristor soft starter

Elemento di confronto3RW4055-6BB443RW5055-6AB14Osservazioni
Ordine n.3RW4055-6BB443RW5055-6AB14Official direct replacement by Siemens
Serie di prodottiSIRIUS 3RW40 (Basic Soft Starter)SIRIUS 3RW50 (New Generation Basic Soft Starter)3RW40 discontinued since Oct 2023
Rated operational current Ie @40℃134 UN143 UNNew model with larger current margin
Rated motor power @400V,40℃75 kW75 kWBoth for standard 75kW loads
Main circuit voltage UeAC 200~460 VAC 200~480 VNew model extended upper limit to 480V
Controllare l'offertaFixed AC230VWide range AC110~250VKey difference: universal control supply for 110V/220V
Thyristor control phases2-controllo di fase (L1, L3)2-controllo di fase (L1, L3)Same topology, no modification required for primary power circuit
Built-in bypass contactor✅ Sì✅ SìThyristor bypass after start for low running loss
Protezione da sovraccaricoIntegrated motor overload Class10Integrated electronic overload Class10Same protection class
PTC thermistor motor protection❌ Non supportato❌ Non supportatoNeither has PTC input
Inside-delta connection❌ Non supportato❌ Non supportatoStandard external connection only
Sosta morbidaBasic ramp onlySosta morbida + pump ramp downPump-friendly function on new model
Adjustable current limit range130%~400%130%~700%Wider limit range for new model
Uscita analogica❌ None✅ Built-in 4~20mA (configurable to 0~10V)Transmit current/load signal to PLC
Porta di comunicazione❌ No communication, non-expandable✅ Optional Profinet/Modbus communication moduleLegacy model has no communication capability
Fault historyBasic fault relay onlyFault log available (with optional HMI module)New model can retrieve historical faults
I/O digitaliFixed relay outputs (95/96,95/98)Programmable DI/DO, 3 programmable outputs +1 fixed changeover contactMore flexible secondary control logic
Operator unitDip-switch setting on boardDip-switch + optional external HMI moduleLegacy no display; new HMI for parameter & current reading
Classe di protezioneIP00IP00For cabinet mounting only
Dimensione (H × W × D mm)198 × 120 × 250200 × 120 × 240Stessa larghezza, similar height, shorter depth; fori di montaggio compatibili
Peso netto4.976 kg4.0 kgNew model lighter
Temperatura ambiente-25℃ ~ +60 ℃−25℃ ~ +60℃Derating required at high temperature for both
Max motor cable length300 M300 MIdentico
Installation clearance≥100mm superiore, ≥5mm side, ≥75mm bottom≥100mm superiore, ≥5mm side, ≥75mm bottomSame installation space requirement
Grado di inquinamento3 (IEC60947-4-2)3 (IEC60947-4-2)Identico
Ciclo vitaleInterrotto, spare parts limitedIn produzione, regular stockPreferred model for retrofit & nuovi progetti

Replacement Implementation Key Points (Engineering Focus)

  1. Primary power circuit: Pienamente compatibile. Incoming and motor terminal positions basically match; direct replacement without re-routing power cables.
  2. Secondary control circuit

Legacy unit fixed AC230V supply; new model accepts AC110~250V wide range. Existing 230V control circuit works directly.

Relay logic is similar, but new DO channels are user configurable. Verify fault/run relay logic after power-on.

New 4~20mA analog output can be left unconnected if not required.

  1. Parameter re-setting: Corrente nominale del motore, start ramp and current limit must be re-programmed in new soft starter; parameters from old unit cannot be reused directly.
  2. Protection scheme: Selection principle for upstream semiconductor fast fuses unchanged; retain original short-circuit protection.

Application Difference Summary

3RW4055: For existing legacy equipment, simple soft start only, no monitoring, nessuna comunicazione, no analog output.

3RW5055: Preferred for new projects and retrofits. Pump ramp-down recommended for pump applications. Supports communication and 4-20mA current feedback to PLC for SCADA monitoring.

  1. 3RW40 (Discontinued Legacy Series|2-phase thyristor, bypass integrato, series of target model)

Main circuit AC200~460V, bypass integrato, Class10 motor overload protection. Suffix defines terminal type, control supply and PTC option; @40℃, rated motor power at 400V.

Ordine n.TelaioCioè(UN)Motor Power @400V(kW)Osservazioni
3RW4024-1BB04S012.55.5Screw terminal AC230V
3RW4026-1BB04S02511Screw terminal AC230V
3RW4027-1BB04S03215Screw terminal AC230V
3RW4028-1BB04S03818.5Screw terminal AC230V
3RW4036-1BB04S24522Screw terminal AC230V
3RW4037-1BB04S26330Screw terminal AC230V
3RW4038-1BB04S27237Screw terminal AC230V
3RW4046-1BB04S38045Screw terminal AC230V
3RW4047-1BB04S310655Screw terminal AC230V
3RW4055-6BB44S613475Screw terminal AC230V (target model)
3RW4056-6BB44S617190Screw terminal AC230V
3RW4072-6BB44S12210110Screw terminal AC230V
3RW4073-6BB44S12250132Screw terminal AC230V
3RW4074-6BB44S12315160Screw terminal AC230V
3RW4075-6BB44S12370200Screw terminal AC230V
3RW4076-6BB44S12470250Screw terminal AC230V
3RW4077-6BB44S12570315Screw terminal AC230V

Supplementare: Same current ratings also available with spring-cage terminals (suffix 2BBxx), 24V control supply, PTC thermistor version (TBxx). Table above lists only mainstream models with screw terminal & AC230V control supply same as 3RW4055-6BB44.

Series feature: 2-phase L1/L3 control, bypass integrato, nessuna comunicazione, no analog output; 3RW405~407 (S6/S12) support PTC motor thermal protection.

  1. 3RW50 (New Generation Replacement Series|Successor of 3RW40, Active Production)

Main circuit AC200~480V, bypass integrato, 2-phase thyristor, wide control supply AC110~250V; built-in 4~20mA analog output, optional Profinet/Modbus module, pump soft stop function.

Ordine n.TelaioCioè(UN)Motor Power @400V(kW)Osservazioni
3RW5024-6AB14S012.55.5Terminale a vite, wide range control supply
3RW5026-6AB14S02511Terminale a vite, wide range control supply
3RW5027-6AB14S03215Terminale a vite, wide range control supply
3RW5028-6AB14S03818.5Terminale a vite, wide range control supply
3RW5036-6AB14S24522Terminale a vite, wide range control supply
3RW5037-6AB14S26330Terminale a vite, wide range control supply
3RW5038-6AB14S27237Terminale a vite, wide range control supply
3RW5046-6AB14S38045Terminale a vite, wide range control supply
3RW5047-6AB14S310655Terminale a vite, wide range control supply
3RW5055-6AB14S614375Screw terminal AC110~250V (Official replacement for 3RW4055-6BB44)
3RW5056-6AB14S617190Terminale a vite, wide range control supply
3RW5072-6AB14S12210110Terminale a vite, wide range control supply
3RW5073-6AB14S12250132Terminale a vite, wide range control supply
3RW5074-6AB14S12315160Terminale a vite, wide range control supply
3RW5075-6AB14S12370200Terminale a vite, wide range control supply
3RW5076-6AB14S12470250Terminale a vite, wide range control supply
3RW5077-6AB14S12570315Terminale a vite, wide range control supply

Supplementare: 3RW50 same current ratings also available with spring-cage terminals (2AB14), 24V control supply and PTC version (TBxx).

  1. Brief Introduction of Other Soft Starter Series in Same Family (Riferimento alla selezione)
  2. 3RW30: Entry-level basic model, 2-fase, bypass integrato, low power range, no PTC, nessuna comunicazione; lower grade than 3RW40
  3. 3RW44: Legacy high-performance type (interrotto). Supports inside-delta connection, 3-phase thyristor, rich protections, suitable for heavy duty
  4. 3RW52: New generation high performance. Supports inside-delta, 3-phase thyristor, for heavy-duty fans & compressori; replacement for legacy 3RW44
  5. 3RW55: High-end safety version including F safety variant, for high safety integrity applications
  6. Order Number Coding Quick Reference (3RW40 / 3RW50)

Take `3RW4055-6BB44` as example

3RW: SIRIUS soft starter

40: Codice della serie

55: Codice di valutazione attuale

6: Terminale a vite (2 = spring-cage terminal)

BB / AB: Base hardware revision

4: Main voltage code

4: Control supply code

Prec:

Prossimo:

Lascia una risposta