Harmony RM22-L Level Control Relay (Conductive Electrode Liquid Level Monitoring)
Interpretazione del modello: RM22 series modular control relay; LG = liquid level single detection; 11 = 1 contatto di scambio (C/O); MR = power supply 24~240V AC/DC; MT version for 380~415V AC power supply
✅ Funzioni principali
Designed for conductive liquids (acqua, liquami, ecc.) for automatic liquid level control. Two operating modes available:
- Fill Mode (Fornitura d'acqua) : When liquid level falls below Min electrode → relay energizes, starts fill pump; when liquid level reaches Max electrode → relay de-energizes, stops pump.
- Drain Mode (Sump Pumping) : When liquid level reaches Max electrode → relay energizes, starts drain pump; when liquid level drops below Min electrode → relay de-energizes, stops pump.
It adopts resistance probe detection, judging liquid level based on liquid conductivity, not float switch. Adjustable detection sensitivity.
📋 Electrical Specifications
Tensione di alimentazione: 24~240 V CA/CC (universale per AC & DC), 50/60Hz; operating range 20.4~264V
Consumo energetico: AC 5VA / DC 1.5W
Contatto di uscita: 1 changeover contact 1C/O (11-12 normalmente chiuso, 11-14 normalmente aperto), AC-15/DC-13, 8A@250VAC
Ritardo all'accensione: 0.6S
Probe circuit: Massimo. 12V AC at electrodes, electrode current ≤1mA; maximum probe cable length 1000m
Sensibilità: St standard sensitivity 5kΩ~100kΩ, continuously adjustable via potentiometer
Montaggio: Guida DIN, width 22.5mm
Protezione: Sealing transparent protective cover to prevent on-site misadjustment; built-in diagnostic test button + status LED indicator
📌Definizione terminale
| terminale | Descrizione |
| A1,A2 | Relay working power supply |
| minimo | Low liquid level electrode |
| Massimo | High liquid level electrode |
| C | Common reference electrode (reference pole) |
| 11 | Contact common terminal |
| 12 | Normally closed NC |
| 14 | Normally open NO |
Wiring note: 3 electrodes inside tank: C common pole, Min minimum liquid level, Max maximum liquid level. Only applicable to conductive liquids; not for insulating oil and other non-conductive media.
🛠️ Applicazioni tipiche
Approvvigionamento idrico & drainage tanks, pozze di liquami, torri di raffreddamento, water purification equipment, automatic pump start/stop, DIN rail mounting inside control cabinet.
⚠️ Differenziazione del modello & Riferimento sostitutivo
- RM22LG11MR: 24~240 V CA/CC, single changeover contact
- RM22LG11MT: 380~415V AC power supply version
- RM22LA32MR: Dual-contact version, two-channel output
Sostituzione dell'eredità: RM35LM series (interrotto, replace with RM22LG for new projects)
Principio di funzionamento di Schneider RM22LG11MR
Principio fondamentale: AC resistive conductive liquid level detection (Tipo di conduttività)
A low-voltage AC sensing signal is applied between electrodes. The device measures liquid resistance between two electrodes and compares it with the sensitivity threshold set on the front panel. The internal circuit drives output relay action.
Low voltage AC signal on probe side to avoid electrolytic corrosion of electrodes caused by DC.
- Detection Circuit
The relay outputs low voltage AC sensing signal (approx.12V AC, corrente <1 mA) tra C (elettrodo comune), minimo (basso livello), Massimo (alto livello).
Elettrodo sommerso dal liquido → il liquido conduttivo forma un percorso tra C e l'elettrodo, bassa resistenza;
Elettrodo esposto sopra il liquido → circuito aperto, resistenza estremamente elevata;
Il potenziometro imposta la soglia di sensibilità (5kΩ~100kΩ) : Resistenza misurata < soglia → liquido rilevato; resistenza>soglia → nessun liquido rilevato.
👉 Valido solo per liquidi conduttivi. Non applicabile per l'olio, acqua ultrapura (conduttività molto bassa) e liquidi isolanti.
- Due modalità operative (3-controllo del livello del liquido a punti con logica di memoria a isteresi)
1) Fill Mode (Trucco dell'acqua)
Livello del liquido sotto l'elettrodo Min: Circuito C-Min aperto → il relè interno si eccita, 11-14 NO chiude, starts fill pump.
Il livello del liquido aumenta, immerge Min ma non raggiunge Max: C-Min conduttivo, la memoria interna mantiene lo stato, la pompa continua a funzionare.
Il livello del liquido raggiunge l'elettrodo Max: C-Max conductive → relay resets, 11-14 si apre, la pompa si ferma.
If liquid level drops but remains above Min, pump will not start. Two-point start/stop prevents frequent pump cycling.
2) Drain Mode (Drenaggio della coppa)
Il livello del liquido raggiunge l'elettrodo Max: C-Max conductive → relay energizes, 11-14 NO chiude, starts drain pump.
Liquid level falls, leaves Max but still higher than Min: memory holds status, pump keeps draining.
Livello del liquido sotto l'elettrodo Min: C-Min open → relay resets, la pompa si ferma.
- Single Level Mode (Opzionale, 2 elettrodi)
Use only C+Max or C+Min for single-point alarm / controllare. Small delay can be enabled to suppress false triggering caused by liquid wave and foam.
- Internal Signal & Produzione
- A1/A2 supplies power to relay (24~240V AC/DC wide range), power circuit is electrically isolated from probe measurement circuit;
- Measurement circuit continuously acquires resistance between electrodes;
- Logic unit judges status based on mode and electrode signals, unità 1 contatto di scambio (1C/O, 11 comune,12 NC,14 NO);
- Front panel LED indicates output status; il pulsante di test integrato simula lo stato per la messa in servizio del loop.
- Caratteristiche principali del progetto
- Rilevamento CA: Nessuna tensione CC applicata agli elettrodi, impedisce l'elettrolisi, generazione di bolle, corrosione degli elettrodi e incrostazioni accelerate.
- Soglia di resistenza regolabile: Adattarsi alle acque reflue / acqua pulita con diversa conduttività tramite manopola di sensibilità.
- Logica della memoria di isteresi: Richiede il riconoscimento dell'alto & punti di basso livello, evita frequenti commutazioni del relè causate da piccole fluttuazioni del liquido.
- Lunghezza massima del cavo dell'elettrodo fino a 1000 m. Fare attenzione alle interferenze parassite della capacità per cavi lunghi; il falso trigger tende a verificarsi con un'impostazione di sensibilità elevata.
- Corrispondenza dei guasti basata sul principio
Ridimensionamento dell'elettrodo → la resistenza del liquido equivalente supera la soglia → il liquido è presente ma il dispositivo non segnala alcun liquido;
Conductive foam layer → electrode not touching actual liquid level but circuit conducts → false liquid level detection;
Poor contact of C electrode → measurement reference lost, all liquid level detection invalid.
Troubleshooting for Schneider RM22LG11MR
Pre-diagnosis method: T test button on front panel. Press T when powered on to toggle relay output status, to distinguish unit failure or external electrode / guasto al cablaggio.
Colpa 1: No response after power on, power LED off
Sintomo: A1/A2 supply voltage normal, no LED light, relay no action
Cause
- Cablaggio A1/A2 allentato, poor terminal contact; wrong polarity for DC supply
- Input voltage out of 24~240V AC/DC operating range
- Internal power circuit damaged (lightning surge, transient overvoltage, cortocircuito)
Soluzioni
- Spegnimento, measure voltage at A1/A2, stringere i terminali; check polarity for DC supply
- Verify supply within rated range; check upstream MCB and fuse
- Sostituire l'unità se il LED è ancora spento con la tensione di alimentazione corretta
Colpa 2: Il relè non funziona quando l'elettrodo è immerso (rilevato liquido ma nessuna risposta)
Sintomo: Il liquido copre l'elettrodo Max/Min, stato del relè invariato, la pompa non si avvia/non si arresta
Cause
- Elettrodo ricoperto da scaglie / fanghi, la resistenza equivalente al liquido supera la soglia di sensibilità
- Contatto difettoso dell'elettrodo comune C (più frequente), riferimento di misura perso
- Cavo dell'elettrodo rotto, cablaggio allentato ai terminali Min/Max/C
- La sensibilità è impostata troppo bassa (soglia di resistenza troppo piccola perché le acque reflue possano condurre)
- Conduttività media troppo bassa (acqua ultrapura, liquido isolante, non adatto a questo modello)
Soluzioni
- Rimuovere gli elettrodi, pulito / incrostazioni e fanghi di lucidatura; manutenzione regolare degli elettrodi
- Elettrodo C di controllo prioritario: assicurarsi che C sia immerso nel liquido e che il cablaggio sia sicuro
- Spegnimento, testare la continuità del cavo, serrare i terminali Min/Max/C
- Aumentare la sensibilità in modo appropriato (alzare la soglia di resistenza, adjustable from 5kΩ~100kΩ)
- For low-conductivity water / olio, use float level switch instead
Colpa 3: Relay false action when liquid level below electrode (detects liquid with no actual liquid), pump starts unexpectedly
Sintomo: Liquid level below electrodes, relay reports liquid present, pump starts mistakenly
Cause
- Conductive foam / scum on liquid surface closes electrode circuit (common in sewage tank)
- Long electrode cable, stray capacitance causes false trigger (>300m is high risk)
- Sensitivity set too high, minor leakage triggers detection
- Electrode cable routed in parallel with power cable, interferenza elettromagnetica
- Terminal condensation / leakage between electrodes
Soluzioni
- Raise electrode mounting position to avoid foam; install foam baffle
- Reduce sensitivity; use shielded cable for long signal wire, shield single-end grounded; separate from power cables
- Clean terminal condensation, improve cabinet moisture resistance
Colpa 4: Avvio-arresto frequente della pompa, chiacchiere dei relè / oscillazione
Sintomo: Livello del liquido stabile entro l'intervallo, il relè si eccita e si diseccita ripetutamente, la pompa esegue cicli rapidi
Cause
- Forte turbolenza del liquido, la superficie del liquido spazza ripetutamente gli elettrodi; conduzione intermittente tramite schiuma
- Elettrodi sporchi, resistenza dell'elettrodo instabile
- Modalità operativa errata, logica di isteresi disabilitata (è collegato solo un elettrodo singolo)
Soluzioni
- Estendere gli elettrodi, installare il manicotto anti-sovratensione; montare gli elettrodi nella zona tranquilla del serbatoio
- Elettrodi puliti, ottimizzare la sensibilità ed evitare impostazioni critiche
- Cablaggio standard a 3 elettrodi (C+Min+Max), abilitare la logica della memoria di isteresi incorporata, evitare il controllo a punto singolo
Colpa 5: LED del relè normale ma contatto di uscita nessuna azione, la pompa non si avvia
Sintomo: Il LED indicatore di livello è corretto, ma contattore a valle / la pompa non funziona
Cause
- Cablaggio errato dei contatti di uscita (11/12/14 terminali mal collegati)
- Il carico dei contatti supera gli 8 A nominali, erosione da contatto / saldatura / circuito aperto
- Nessuna alimentazione sul circuito di controllo a valle
Soluzioni
- Spegnere e verificare il cablaggio dei contatti: 11 comune, 12 NC,14 NO
- Premere il pulsante T test e misurare la continuità tra 11-14; circuito aperto = contatto danneggiato, sostituire il relè
- Controllare l'alimentazione di controllo della pompa / contattore
Colpa 6: Saldatura dei contatti, la pompa funziona continuamente e non può fermarsi
Sintomo: Il livello del liquido raggiunge la posizione di arresto, l'uscita rimane chiusa, la pompa non può spegnersi
Cause
- Sovraccarico a lungo termine, l'arco elettrico provoca la saldatura dei contatti
- Nessun assorbimento di sovratensione per la bobina del contattore, indietro I campi elettromagnetici danneggiano i contatti
Soluzioni
- Sostituire immediatamente RM22LG11MR se i contatti sono saldati
- Aggiungi smorzatore RC o diodo a ruota libera per carico induttivo (bobina del contattore) per proteggere i contatti interni da 8A
Sequenza consigliata per la risoluzione dei problemi in loco
- Accendere, controllare il LED di alimentazione; LED spento → ispezionare l'alimentazione A1/A2
- Premere il pulsante di prova T e osservare la commutazione dell'uscita
L'uscita viene commutata da T: Unità sana, guasto nell'elettrodo, cavo o mezzo liquido
Nessuna risposta da parte di T: Unità relè danneggiata, sostituire direttamente
- Verify C common electrode fully immersed and wiring tightened
- Clean electrodes and adjust sensitivity knob
- Check if signal cable runs together with power cable; use shielded cable for long distance
- Confirm mode selection: Fill (fornitura d'acqua) / Drenare (drenaggio)
Manutenzione preventiva
- Sewage application: Clean electrodes every 3~6 months to prevent scaling
- Keep electrode cable length within 500m where possible; reduce sensitivity and adopt shielded cable if longer
- Ensure cabinet moisture-proof to avoid terminal condensation leakage
- Install surge absorption device for inductive load (contattore) to protect 8A contacts
Schneider RM22 Harmony Modular Monitoring Relay Full Series List
Caratteristiche comuni della serie: Montaggio su guida DIN, width 22.5mm (RM22TG20:17.5mm); equipped with T test button, status LED, sealable transparent cover; valutazione dei contatti: 8A@250VAC; suffix MR=24~240V AC/DC universal supply; MT=380~415V AC supply
- RM22L Conductivity Level Monitoring Relay (series of your model)
Conductive electrode liquid level detection for high/low level control of water tank and sewage sump
|RM22LG11MR|1C/O (1 cambio)|24~240 V CA/CC|Modello standard, your reference unit, sensitivity 5k~100kΩ|
|RM22LG11MT|1C/O|380~415 V CA|High voltage supply level relay|
|RM22LA32MR|2C/O (2 cambio)|24~240 V CA/CC|Dual-channel output, 3 sensitivity levels: LS/St/HS|
|RM22LA32MT|2C/O|380~415 V CA|Dual-contact high voltage supply level relay|
- RM22T 3-phase Power Monitoring Relay (Sequenza di fasi / perdita di fase / 3-squilibrio di fase / sovratensione & sottotensione)
Monitor 3-phase power supply for motor, pompa dell'acqua, air compressor protection
|RM22TA31|2C/O|Sequenza di fasi, perdita di fase, 3-squilibrio di fase|200~240 VCA|
|RM22TA33|2C/O|Sequenza di fasi, perdita di fase, 3-squilibrio di fase|380~480 VCA|
|RM22TU21|2C/O|Sequenza di fasi, perdita di fase, sottotensione|200~240 VCA|
|RM22TU23|2C/O|Sequenza di fasi, perdita di fase, sottotensione|380~480 VCA|
|RM22TR31|2C/O|Sequenza di fasi, perdita di fase, sbilanciare, overvoltage/undervoltage with delay|200~240 VCA|
|RM22TR33|2C/O|Sequenza di fasi, perdita di fase, sbilanciare, overvoltage/undervoltage with delay|380~480 VCA|
|RM22TG20|2C/O|Sequenza di fasi, perdita di fase (versione compatta,17.5mm)|183~528VAC|
- RM22U Single-phase / DC Voltage Monitoring Relay (Sovratensione & Undervoltage monitoring)
AC/DC single-phase voltage monitoring for DC panel and single-phase power protection
|RM22UA32MR|2C/O|1~100V AC/DC|24~240 V CA/CC|
|RM22UA33MR|2C/O|15~500V AC/DC|24~240 V CA/CC|
|RM22UA33MT|2C/O|15~500V AC/DC|380~415 V CA|
|RM22UB34MR|2C/O|Wide range single phase voltage|24~240 V CA/CC|
- RM22J Current Monitoring Relay (AC current monitoring, sovraccarico / sottocorrente)
Work with current transformer CT for motor load current monitoring
|RM22JA21MR|1C/O|0.1~5A AC|24~240 V CA/CC|
|RM22JA32MR|2C/O|0.1~5A AC|24~240 V CA/CC|
- Regola di codifica del modello (RM22XXYYZZ)
- RM22: Series code Harmony modular monitoring relay
- XX: Function group
LG: Livello del liquido, single sensitivity
IL: Livello del liquido, multi-range sensitivity
TA/TU/TR/TG: 3-phase power monitoring
UA/UB: Single-phase voltage monitoring
E: Current monitoring
- AA: Contact quantity
11: 1 contatto di scambio (1C/O)
32: 2 contatti di scambio (2C/O)
- Z.Z: Power supply code
SIG: 24~240V AC/DC universal (most widely used in engineering)
MT: 380~415V AC 3-phase high voltage supply
- Legacy Model Replacement (RM35 → RM22)
RM35LM old level relay → RM22LG / RM22LA
RM35TA/TU old 3-phase protection relay → RM22TA/TR/TU
RM35 series discontinued, select RM22 for new projects
- Tabella di selezione rapida
| Applicazione | Modello consigliato |
| Cisterna / sump conductivity level, single pump start-stop | RM22LG11MR (il tuo modello di riferimento) |
| Liquid level control requiring two independent alarm/output channels | RM22LA32MR |
| 3-motore di fase: perdita di fase + sequenza di fasi + protezione dagli squilibri | RM22TA33 |
| 3-phase power: perdita di fase + sequenza di fasi + Sopra & undervoltage full protection | RM22TR33 |
| Motor load current monitoring (CT sensing) | RM22JA21MR |
| Pannello CC, single phase over & undervoltage alarm | RM22UA33MR |
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore




















NH42-63-318x560.png)



