Danfoss 068Z3206 is an internally equalized thermostatic expansion valve of the TX2 type in the T2/TE2 series, designed specifically for R22/R407C refrigerants with 3/8″ × 1/2″ flare connections. It is used for refrigerant flow control in dry evaporators of commercial and industrial refrigeration and air conditioning systems.
- モデルコードの内訳
| コードセグメント | 意味 |
| 068Z | Prefix for Danfoss refrigeration valve product codes |
| 3206 | Specific model identifier, corresponding to TX2 valve body, internal equalizer, R22/R407C, flare connection |
| TX2 | Product series code, internally equalized thermostatic expansion valve in the T2 series; TEX2 (068Z3209) is the externally equalized version |
Core Attributes: No MOP (Maximum Operating Pressure) コントロール, no pre-installed nozzle (matching nozzle must be selected according to system requirements)
- コア技術パラメータ
| パラメータ | 仕様 |
| Refrigerant Compatibility | R22/R407C (not suitable for other refrigerants) |
| Connection Size | Inlet 3/8″ flare, outlet 1/2″ flare |
| Equalization Type | Internal Equalizer |
| Powerhead Capillary | 長さ 59 で (1.5 メートル), diameter 1.5 mm |
| Valve Body Material | 真鍮 |
| 取付方向 | Angle design, mountable horizontally or vertically |
| 温度範囲 | -40°C to +10°C (for freezing, refrigeration and air conditioning applications) |
| Nominal Cooling Capacity | 15.5 kW (4.5 TR) under R22 conditions |
| Equalization Port | 1/4″ flare (internal equalizer) |
| 重さ | 0.68 lbs (308.44 g) |
- 適用動作環境
- System Types: Dry evaporators in commercial refrigeration equipment, industrial water chillers, and air conditioning systems
- 動作条件:
Evaporation temperature: -40°C to +10°C
Working pressure: Complies with standard pressure ratings for R22/R407C systems
Compatible compressors: Reciprocating and scroll compressors
- インストール要件:
Must be installed on the liquid line between the condenser and evaporator
Powerhead must be firmly mounted on the suction line at the evaporator outlet for good thermal contact
Capillary tube shall avoid excessive bending and contact with high-temperature surfaces
- Cross-Brand Reference / 代替モデル
| Replacement Type | モデル | 説明 |
| 直接交換 | 068Z7836 | Equivalent Danfoss replacement model |
| Externally Equalized Version | 068Z3209 (TEX2) | For evaporator systems with high pressure drop |
| Other Sizes in Same Series | 068Z3207/3208/3210 | T2 series products with different connection sizes or equalization types |
| アップグレードされた交換品 | TEZ series (例えば. 067B3366) | For multi-refrigerant compatible systems |
- 公式注文情報
| アイテム | 詳細 |
| Official Model | 068Z3206 (global unified code) |
| 製品名 | Thermostatic Expansion Valve, TX2, R22/R407C, 3/8″×1/2″ Flare, Internal Equalizer |
| Ordering Recommendation | Matching flow nozzle (例えば. 068-2002 シリーズ) must be ordered simultaneously |
| Packing Specification | Single-piece independent package, including valve body, powerhead, capillary tube and mounting accessories |
- Engineering Implementation Points
- Nozzle Selection: Select the appropriate nozzle based on system cooling capacity, evaporation temperature and refrigerant type. If an exact capacity match is unavailable, select the next larger size nozzle.
- インストールに関する注意事項:
Liquid line must be sufficiently subcooled to avoid flash gas affecting valve performance
Powerhead mounting location shall avoid suction line bends and welds
Ensure system cleanliness; a 100μm strainer is recommended to prevent nozzle clogging by contaminants
- Commissioning Points:
Typical superheat setting: 5-8 K, adjustable via the top adjustment screw on the valve body
Perform fine adjustment only after the system runs stably, with no more than 1/4 turn per adjustment
- Partial Complete Model List for T2/TE2 Series
| モデル | タイプ | Equalization | Refrigerant | 繋がり |
| 068Z3206 | TX2 | Internal | R22/R407C | 3/8″×1/2″ flare |
| 068Z3209 | TEX2 | External | R22/R407C | 3/8″×1/2″ flare |
| 068Z3346 | TN2 | Internal | R134a | Flare connection |
| 068Z3400 | TE2 | External | R404A/R507 | Flare connection |
| 068Z2900 | TE2 | External | R744 | Special connection |
- Key Risk Warnings
- Refrigerant Restriction: This model is only suitable for R22/R407C and must not be used with other refrigerants such as R410A, R134a, otherwise valve damage or system failure will occur.
- Equalization Matching: Internally equalized valves are only suitable for systems with low evaporator pressure drop (<0.3 バー). For higher pressure drops, the externally equalized TEX2 (068Z3209) must be used.
- Nozzle Compatibility: Only genuine Danfoss matching nozzles shall be used; non-genuine nozzles may reduce flow control accuracy and service life.
Complete List of Danfoss Thermostatic Expansion Valves
Danfoss thermostatic expansion valves cover multiple series to suit different refrigeration system requirements. Below is a categorized list by core series, including model, refrigerant, connection type, equalization type and key features for easy selection and replacement reference.
- T2/TE2 Series (Replaceable Nozzle, Mainstream Universal Type)
The T2/TE2 series is a classic Danfoss thermostatic expansion valve with a replaceable nozzle design, suitable for dry evaporators in freezing, refrigeration, air conditioning and other applications.
1.1 Internally Equalized (T2)
| モデル | シリーズ | Refrigerant | Connection Size | 温度範囲 | 注意事項 |
| 068Z3206 | TX2 | R22/R407C | 3/8″×1/2″ flare | -40°C~+10°C | No MOP charge |
| 068Z3207 | TX2 | R22/R407C | 3/8″×1/2″ flare | -75°C~-15°C | Low-temperature type, no MOP |
| 068Z3208 | TX2 | R22/R407C | 1/2″×3/4″ flare | -40°C~+10°C | Large bore, no MOP |
| 068Z3346 | TN2 | R134a/R513A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP |
| 068Z3347 | TN2 | R134a/R513A | 3/8″×1/2″ flare | -75°C~-15°C | Low-temperature type, no MOP |
| 068Z3348 | TN2 | R134a/R513A | 1/2″×3/4″ flare | -40°C~+10°C | Large bore, no MOP |
| 068Z3400 | TS2 | R404A/R507A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP |
| 068Z3401 | TS2 | R404A/R507A | 3/8″×1/2″ flare | -75°C~-15°C | Low-temperature type, no MOP |
| 068Z3402 | TS2 | R404A/R507A | 1/2″×3/4″ flare | -40°C~+10°C | Large bore, no MOP |
| 068Z3610 | TZ2 | R410A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP |
| 068Z3611 | TZ2 | R410A | 3/8″×1/2″ flare | -75°C~-15°C | Low-temperature type, no MOP |
| 068Z3612 | TZ2 | R410A | 1/2″×3/4″ flare | -40°C~+10°C | Large bore, no MOP |
1.2 Externally Equalized (TE2)
| モデル | シリーズ | Refrigerant | Connection Size | 温度範囲 | 注意事項 |
| 068Z3209 | TEX2 | R22/R407C | 3/8″×1/2″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3210 | TEX2 | R22/R407C | 1/2″×3/4″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3386 | TEN2 | R134a/R513A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3387 | TEN2 | R134a/R513A | 1/2″×3/4″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3403 | TES2 | R404A/R507A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3404 | TES2 | R404A/R507A | 1/2″×3/4″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3613 | TEZ2 | R410A | 3/8″×1/2″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
| 068Z3614 | TEZ2 | R410A | 1/2″×3/4″ flare | -40°C~+10°C | No MOP, 1/4″ equalization port |
1.3 Solder Type Internal / External Equalized
| モデル | シリーズ | Refrigerant | 繋がり | Equalization | 温度範囲 |
| 068Z3211 | TX2 | R22/R407C | 3/8″×1/2″ solder | Internal | -40°C~+10°C |
| 068Z3212 | TEX2 | R22/R407C | 3/8″×1/2″ solder | External | -40°C~+10°C |
| 068Z3349 | TN2 | R134a/R513A | 3/8″×1/2″ solder | Internal | -40°C~+10°C |
| 068Z3388 | TEN2 | R134a/R513A | 3/8″×1/2″ solder | External | -40°C~+10°C |
| 068Z3405 | TS2 | R404A/R507A | 3/8″×1/2″ solder | Internal | -40°C~+10°C |
| 068Z3410 | TES2 | R404A/R507A | 3/8″×1/2″ solder | External | -40°C~+10°C |
- TE5-55 Series (Industrial Grade, Large Cooling Capacity)
The TE5-55 series is designed for large commercial and industrial refrigeration systems with a wider cooling capacity range, also featuring a replaceable nozzle design.
| モデル | Refrigerant | Connection Size | Cooling Capacity Range | 温度範囲 | Equalization |
| 067G2705 | R410A/R32 | 1/2″×3/4″ solder | 5–15 kW | -60°C~+10°C | External |
| 067G2706 | R410A/R32 | 3/4″×1″ solder | 15–30 kW | -60°C~+10°C | External |
| 067G2707 | R22/R407C | 1/2″×3/4″ solder | 5–15 kW | -60°C~+10°C | External |
| 067G2708 | R22/R407C | 3/4″×1″ solder | 15–30 kW | -60°C~+10°C | External |
| 067G2709 | R404A/R507A | 1/2″×3/4″ solder | 5–15 kW | -60°C~+10°C | External |
| 067G2710 | R404A/R507A | 3/4″×1″ solder | 15–30 kW | -60°C~+10°C | External |
- TGE Series (AC Type, High-Pressure Applications)
The TGE series is specially designed for high-pressure refrigerants (例えば. R410A) with a working pressure up to 46 バー, suitable for air conditioning and heat pump systems.
| モデル | Refrigerant | 繋がり | Cooling Capacity Range | 温度範囲 | Equalization |
| 067B3366 | R410A | 1/2″×3/4″ solder | 12–50 kW | -30°C~+15°C | External |
| 067B3367 | R410A | 3/4″×1″ solder | 50–180 kW | -30°C~+15°C | External |
| 067B3368 | R32 | 1/2″×3/4″ solder | 15–60 kW | -30°C~+15°C | External |
| 067B3369 | R32 | 3/4″×1″ solder | 60–200 kW | -30°C~+15°C | External |
- TU Series (Universal Type, Multiple Configurations)
The TU series offers various configuration options to suit different system requirements.
| モデル | シリーズ | Refrigerant | Superheat Adjustment | 繋がり | Equalization |
| 068Z3720 | TUB | Multi-refrigerant compatible | Adjustable | 3/8″×1/2″ flare | Internal |
| 068Z3721 | TUCE | Multi-refrigerant compatible | Non-adjustable | 3/8″×1/2″ flare | External |
| 068Z3722 | TUS | R404A/R507A | Adjustable | 3/8″×1/2″ flare | Internal |
| 068Z3723 | TUSE | R404A/R507A | Adjustable | 3/8″×1/2″ flare | External |
- Special Series & Accessories
5.1 Nozzle Accessories (Universal for T2/TE2 Series)
| モデル | シリーズ | Suitable Refrigerant | Flow Rating | 注意事項 |
| 068-2002 | TXV | R22/R407C | 0× | Standard flow |
| 068-2003 | TXV | R134a/R513A | 0 | Low flow |
| 068-2004 | TXV | R404A/R507A | 1 | Medium flow |
| 068-2005 | TXV | R410A | 2 | High flow |
5.2 Powerhead & Capillary Tube
| モデル | Suitable Series | 長さ | Diameter | 材料 |
| 068Z3383 | TN2/TEN2 | 1.5 メートル | 1.5 mm | 銅 |
| 068Z3406 | TS2/TES2 | 1.5 メートル | 1.5 mm | 銅 |
| 068Z3615 | TZ2/TEZ2 | 1.5 メートル | 1.5 mm | 銅 |
- Key Selection Parameter Comparison Table
| パラメータ | Selection Key | Recommended Series |
| Refrigerant Type | R22/R407C | TX2/TEX2 |
| R134a/R513A | TN2/TEN2 | |
| R404A/R507A | TS2/TES2 | |
| R410A/R32 | TZ2/TEZ2, TGE | |
| Evaporator Pressure Drop | <0.3 バー | Internally equalized (T2) |
| >0.3 バー | Externally equalized (TE2) | |
| 温度範囲 | -75°C~-15°C | Low-temperature type (TX2-068Z3207 etc.) |
| -40°C~+10°C | Standard type | |
| Connection Type | Easy on-site installation | Flare connection |
| High system tightness required | Solder connection | |
| Cooling Capacity | <15 kW | T2/TE2 series |
| >15 kW | TE5-55 or TGE series |
- Risk Warnings & 注意事項
- Refrigerant Matching: Each model is only compatible with specified refrigerants; improper use causes valve damage and system failure.
- Equalization Selection: Externally equalized valves must be used when evaporator pressure drop >0.3 バー, otherwise flow control accuracy degrades.
- Nozzle Compatibility: Only genuine Danfoss matching nozzles shall be used; non-genuine nozzles may cause unstable performance.
- Installation Requirement: Powerhead must be firmly mounted on the suction line at the evaporator outlet for good thermal contact.
- Commissioning Points: Typical superheat setting is 5-8 K; adjust no more than 1/4 turn each time, and fine-tune only after system stabilization.
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池



















NH42-63-318x560.png)