注記: The last character is letter O, not digit 0; belongs to XTCG sub-series of Eaton XT-range IEC 接触器.
モデルコードのデコード
| コードセグメント | 説明 |
| XT | イートン XT‑range IEC control series |
| C | コンタクタ |
| G | XTCG series, screw‑terminated 3‑pole motor contactor |
| 18 | AC‑3 rated operational current:18A for main circuit |
| C | Frame size C, 45 mm width housing |
| 0 | No built‑in auxiliary contacts (0NO+0NC) |
| へ | コイル: AC220V 50/60Hz (A=AC, O=code for 220VAC coil) |
Full definition: 3-ポール, AC-3 18A, no-built-in auxiliary contacts, AC220Vコイル, screw-terminal AC contactor.
コアの電気パラメータ
| アイテム | 仕様 |
| Main Poles | 3P‑NO (three normally‑open main contacts) |
| AC‑3 Rated Operational Current | 18A @400V motor load |
| AC‑1 Resistive Load | 32あ |
| 定格絶縁電圧 Ui | 690V |
| コイル電圧 | AC220V 50/60Hz |
| 補助接点 | None onboard; external accessories XTCGXF*** required |
| 機械的耐久性 | ≥10 000 000 operations |
| AC‑3 Electrical Endurance | ≥1 000 000 operations |
| 取り付け | DIN35 rail mounting or screw‑on backplate mounting |
| 端子 | ネジ締め端子 |
| 認証 | CCC, CE, UL, CSA, IEC60947‑4‑1 |
物理的な & 環境条件
Housing width: 45 mm
動作温度:-25℃~+60℃, condensation and icing forbidden
保管温度:-40℃~+85℃
重さ: 約. 0.21 kg
典型的なアプリケーションシナリオ
- Three-phase motor start-stop control (≤7.5kW @400V motor)
- ファン, ウォーターポンプ, コンベア, エアコンプレッサー, 包装機械
- 空調設備 & cabinet OEM assembly; can be paired with XTOD thermal overload relay for motor overload protection
List of Compatible Accessories
Auxiliary contact block: XTCGXFAC (1NO+1NC etc.), サイドマウント
サーマルリレー: XTOD018 (0.1-18A motor protection coverage)
Mechanical interlock module: XTCG-MV, for reversing circuit
サージキラー: ラジコン / varistor module for coil side
Direct-Replacement Models & 交換ノート
- Same-series alternative: XTCG018C00DT (different coil code; verify coil voltage, not a drop-in replacement)
- Cross-series alternative: XTCE018C00A0 (Eaton XTCE series, functionally equivalent; check accessory compatibility)
⚠️Pitfall reminder: XTCG018C00AO has no onboard auxiliary contacts. External auxiliary-contact accessory must be fitted if PLC feedback signals are required, otherwise control circuits cannot function.
Non-Applicable Operating Conditions
Switching frequency>1200 cycles/hour
Heavy corrosive gas / heavy dust environment without proper protection
DC-coil applications (this unit is AC-coil type)
Brief Wiring Instructions
- 主回路: L1-L2-L3 supply side; T1-T2-T3 load (モーター) 側
- Coil terminals A1/A2 connect to AC220V
- 補助接点は内蔵されていません; all logic feedback signals shall be obtained from externally fitted auxiliary-contact accessories.
XTCG018C00AO (Frame C) 取り付け & 全体の寸法 (ユニット: mm)
All XTCG-C frame models (009-032あ) share identical housing dimensions. Supports DIN35 rail mounting AND screw-on back-plate mounting.
全体の寸法 (without fitted accessories)
| アイテム | 価値 | 備考 |
| Width W | 45 | Reference for cabinet layout spacing |
| Height H | 85 | Total height including upper & lower terminals |
| Depth D | 97.4 | Depth inside cabinet panel after rail‑mounted |
Overall dimension: 45(W) × 85(H) × 97.4(D) mm
Screw-on back-plate cut-out dimensions (DIN rail unused, direct screw-fix onto cabinet back-plate)
Horizontal mounting-hole centre-to-centre spacing: 35 mm
Vertical mounting-hole centre-to-centre spacing: 76 mm
Fastener hole diameter: Φ4.5 (M4ネジ)
Hole-to-edge margin: approx.4.5 mm top & 底.
DIN Rail Installation Information
- Standard DIN-35-7.5 rail (universal electrical 35 mm rail)
- Back-side snap-in clip for direct rail-clip mounting; tool-free assembly & disassembly.
⚠️Dimension change after accessory installation
- Side-mount auxiliary-contact block XTCGXF: width increases by 10 mm, total width 55 mm
- Bottom-mount thermal overload relay XTOD: overall height increases by approx.42.5 mm
- Mechanical interlock XTCG-MV: two contactors side-by-side with zero gap; total width = direct sum (45+45=90 mm)
Installation Boundary Conditions
- Cooling clearance: ≥10 mm top & 底; no mandatory clearance side-to-side (multiple units may be mounted adjacent to each other)
- Do not mount tightly against closed cabinet partitions; ambient temperature-25℃~+60℃, condensation prohibited.
- Maximum permitted conductor size: main circuit 6 mm²; coil circuit 2.5 mm².
Cross-model reference
Models XTCG009C / XTCG025C / XTCG032C share identical housing, cut-out and rail-mount dimensions; only internal contact current rating differs. Varied coil voltage codes (AO/DT etc.) produce no change in physical dimensions.
Operating Voltage Differentiation for Eaton XTCG018C00AO
Two separate voltage systems exist for contactors: 主回路 (主な連絡先) and coil control circuit. Do not confuse them.
- コイル制御電圧 (suffix code AO)
Coil rated voltage: AC 220V 50/60Hz
端子: A1, A2
Permissible coil operating voltage range: 0.85~1.1×Ue, つまり. AC187V ~ AC242V
⚠️This is an AC coil. DC supply is strictly forbidden.
- 主回路 (main contacts for motor loads)
| パラメータ | 価値 |
| 定格使用電圧Ue | マックス. AC690V |
| Common operating voltages | AC230V / 400V / 500V / 690V |
| 定格絶縁電圧Ui | 690V |
| Impulse withstand voltage Uimp | 6 kV |
The 18A AC-3 rating is specified at 400V. Main circuit can operate within 0-690V AC; allowable current varies with applied voltage.
Key Supplementary Notes
- Suffix code `AO` exclusively denotes AC220V coil. Changing suffix code (例えば. DT=AC380V) only alters coil voltage; main-circuit voltage capability remains unchanged.
- Voltage outside permitted coil operating range causes faults: undervoltage → pull-in failure / chattering; overvoltage → coil overheating & burnout.
- Main-circuit current derating applies at elevated ambient temperatures.
XTCG018C00AO Coil Troubleshooting Guide
Coil specification: AC220V 50/60Hz; Terminals A1/A2; permissible operating range AC187V-242V; DC supply prohibited.
故障 1: Contactor does not pull-in at all, zero acoustic response
Probable Root-Causes
- No voltage on control circuit: 0V measured across A1/A2; upstream relay / PLC出力 / fuse / 壊れたワイヤー / loose terminal.
- Coil supply voltage below 0.85Ue (<187V): insufficient voltage for pull-in.
- Coil open-circuit burnout: infinite resistance reading between A1-A2 via multimeter.
- 機械的焼き付き: foreign-object ingress, corroded iron-core, mis-fitted add-on accessories causing mechanical jamming.
Remedial Steps
- Power-off safety confirmation; measure live voltage across A1/A2 terminals.
- 電源オフ; disconnect coil wiring; measure DC resistance of coil standalone. Typical resistance of C-frame AC220V coil: 1300-1500 Ω. Infinite resistance = burned-open coil; near-zero resistance = short-circuited coil.
- Manually actuate contactor armature; verify smooth movement. If sticking, remove foreign debris; inspect fit of auxiliary-contact / interlock accessories.
- Verify continuity of control-circuit fuse, PLC outputs and intermediate relays.
故障 2: Contactor chatters / loud buzzing noise, unstable pull-in
Probable Root-Causes
- Marginal low coil voltage; long-run / thin-gauge control wiring creates excessive voltage drop.
- Iron-core mating surfaces contaminated with oil, dust or iron-particles; enlarged magnetic air-gap.
- Supply-waveform distortion, harmonic distortion caused by VFD interference.
- Degraded coil with partial turn-to-turn short-circuit.
Remedial Steps
- Live measurement of A1/A2 voltage; must stay within AC187-242V. Increase control-cable cross-section for long-distance control loops.
- 電源オフ; clean iron-core mating surfaces of iron-dust and debris. Do NOT apply lubricant grease or oil.
- コイル抵抗を測定する; significantly-lower-than-nominal resistance indicates turn-to-turn short-circuit; replace full contactor unit.
- Fit RC-type coil surge suppressor in case of severe electromagnetic interference.
Fault3: Coil persistent overheating / rapid burnout
Probable Root-Causes
- Wrong supply voltage: AC380V applied to AC220V coil — most frequent burnout cause.
- Continuous supply voltage>1.1Ue (>242V), long-term over-voltage operation.
- Mechanical jamming prevents full armature closure; large residual air-gap keeps coil current high continuously.
- Accidental DC power supply to AC coil: instant burnout.
Remedial Steps
- Double-check actual supply voltage; match AO-coded AC220V coil rating strictly.
- Verify free mechanical movement; confirm full armature closure.
- Confirm AC-only supply; never drive with DC source.
Burnt-out coil: XTCG-series coils are non-field-replaceable individually. Replace complete contactor assembly.
Fault4: Contactor fails to release after de-energization (stuck closed)
Distinguish main-contact welding versus coil residual-voltage / mechanical-seizure non-release.
- Residual voltage persists across A1/A2 after coil de-energization (PLC leakage current, residual voltage from parallel indicator lamps).
- 機械的焼き付き; return-spring fatigue.
- Main-circuit short-circuit event resulting in welded main contacts.
Remedial Steps
- Measure residual voltage across de-energized A1/A2. Residual>30V prevents release; fit RC snubber for voltage dissipation.
- Disconnect main-circuit power; test manual return-action of mechanism. Replace unit if spring failure occurs.
- Inspect main-contacts for burn-welding. Welded contacts require full-unit replacement; do not refurbish by polishing contacts for continued service.
⚠️Hard-forbidden Operations
- Never apply DC voltage to AC220V AC-coil; instant burnout risk.
- Do not short-circuit terminals A1/A2 for test purposes.
- Do not repeatedly apply power to already-burned coil; secondary cabinet-damage risk.
- Never apply oil / grease onto iron-core mating surfaces; oil traps ferrous dust and causes buzzing / stuck-closed failure.
Quick-Reference Test Matrix
| Measurement Item | Acceptable Reference Value | Fault Judgment |
| Live coil operating voltage | AC187‑242V | <187V: pull‑in failure;>242V: overheating burnout |
| Coil DC resistance(A1‑A2) | 1300‑1500 Ω | Infinite = open‑circuit; far‑lower reading = turn‑to‑turn short‑circuit |
| Residual voltage A1‑A2 (power‑off) | <10 V | >30 V risk of release failure |
Supplementary note: No auxiliary contacts built-in. External side-mount auxiliary-contact block XTCGXF is mandatory for status feedback signals.