HINODE (Hinode Electric Manufacturing Co., 株式会社, 日本) Semiconductor Protection Ultra-Fast Fuse. 660GHX series, 125あ, AC/DC 660V, bolt-mount type, widely used for short-circuit protection of power circuits in inverters, rectifiers, コンバーター, DC power supplies and energy storage systems.
モデルの説明
660: Rated voltage AC/DC 660V
GH: Series of cylindrical bolt-mounted high breaking capacity ultra-fast fuses
×: Product suffix for basic version, without microswitch for blown fuse alarm. The alarm version is suffixed with S, 例えば. 660GH125S
125: Rated current 125A
Common shorthand in market: 660GHX125, full marking 660GHX125-125A
コアの電気仕様
| アイテム | パラメータ |
| 定格電圧 | AC660V / DC660V (L/R=10ms) |
| 定格電流 | 125あ |
| 遮断容量 | AC660V: 100の; DC660V: 100の |
| CCC Certified Version (suffix TC) | AC660V: 50の; DC450V: 50の |
| Minimum Breaking Current | AC/DC 660V: 5×イン (625あ) |
| Maximum Arc Voltage | 1400V |
| 動作特性 | Ultra-fast type for semiconductor protection, short-circuit interruption in microseconds |
| 工事 | Ceramic body, bolted mounting lugs at both ends, quartz sand filler |
| コンプライアンス | RoHS, UL/CCC certification optional (suffix UL / TC) |
Outline & インストール
構造: Flange with mounting holes at both ends, bolt-tight mounting, clip mounting is not allowed
Basic cylinder dimension: φ17mm, overall length increases with current rating
取り付け: Matched fuse holder series HT6017
代表的な用途
Power circuit protection for variable frequency drives and servo drives
Short-circuit protection for rectifier bridges, IGBTs and thyristor power semiconductors
DC bus, battery test equipment, low-voltage energy storage converters
冶金, 鉄道輸送, high-power UPS power supplies
選択 & 交換ガイドライン
- 区別: 660GHX125 (警報なし) vs 660GH125S (with blown fuse signal microswitch). Identical outline dimensions and interchangeable holders.
- 国内での交換: Select semiconductor ultra-fast fuses of same rating 660V 125A. 遮断容量, mounting hole pitch and time-current characteristic must be verified. General gG/gL fuses cannot be substituted.
- 交換: Power cut and voltage verification mandatory. After fuse blowout, check for breakdown of power semiconductors; never fit a new fuse and energize directly.
Reference Models in Same Series
660GHX063, 660GHX080, 660GHX100, 660GHX125, 660GHX160, 660GHX200
Domestic Replacement List for HINODE 660GHX125 (660V 125A aR Ultra-Fast Fuse Link) + Mounting Dimension Comparison
Original part: Hinode 660GHX125, cylindrical double-flange bolt-on aR semiconductor protection fuse, φ17mm body, overall length approx.98mm, flanged mounting lugs at both ends, no striker (select striker version for alarm type). AC/DC660V, breaking capacity 100kA, for IGBT/rectifier short-circuit protection.
Core precondition for replacement: Only aR class semiconductor ultra-fast fuses are acceptable. gG general fuses are strictly prohibited for direct substitution. Priority for fully compatible dimensions to fit original HT6017 holder directly; close dimensions require hole pitch verification.
Baseline Dimensions of Original 660GHX125
| アイテム | 寸法 mm |
| Cylinder Outer Diameter | φ17 |
| Overall Length of Fuse Link | 98 |
| Flange Width | 28 |
| 取付穴径 | φ6.5 |
| Center Distance Between Two Mounting Holes | 76 |
| タイプ | Cylindrical bolt-on, aR, no striker (striker version optional for replacing 660GH125S) |
Domestic Replacement Model Comparison Table
| 国内モデル | ブランド | 評価 | タイプ | Body φ |
| RGS4A-660V125A aR | MRO (Mingrong) | AC660V 125A DC660V | aR Semiconductor Ultra-Fast Fuse | φ17 |
| RGS4-660/125 aR | Shanghai Longrong | AC660V 125A DC660V | aR | φ17 |
| RGS4A 690V125A aR | Bomuge | AC690V 125A DC660V | aR | φ17 |
| RS94G-660V125A aR | Sinofuse | AC660V 125A DC660V | aR | φ19 |
| RS77Z-690V125A aR | MRO (Mingrong) | AC690V 125A DC500V | aR | φ20 |
選択 & 交換ノート
- Time-Current Characteristic (TCC Curve): RGS4A/RGS4 have the closest pre-arcing time and current limiting characteristics to 660GHX125. For high-power IGBT circuit replacement, request TCC curves from manufacturer for comparison.
- DC Application: Original fuse supports DC660V (L/R=10ms). RGS4A and RS94G support DC660V. Some domestic models have derated DC rating; DC bus application must confirm DC specifications.
- Blown Fuse Alarm Function
Original 660GHX125: no microswitch → select RGS4A without striker
Original 660GH125S (with alarm) → select RGS4A with striker, paired with holder microswitch for blown fuse signal output
- Breaking Capacity Derating Risk: Original Hinode AC breaking capacity 100kA; domestic RGS4 series is 80kA. For most inverters and DC power supplies, site prospective short-circuit current <80kA and acceptable. Re-evaluation required if prospective short-circuit current >80の.
- Installation Inspection: Even with fully matched dimensions, inspect HT6017 holder copper contact surface for oxidation before replacement; control tightening torque to avoid overheating and nuisance fuse blowout.
Not Recommended Replacements (Avoid Pitfalls)
RT18, RT28 series: gG general purpose protection, not aR semiconductor ultra-fast fuses. Slow short-circuit response will cause IGBT burnout, strictly prohibited for substitution.
RS0, RS3 standard square body fast fuses: 角型ハウジング, fully different flange mounting structure, cannot fit into original holder.
Quick Selection Recommendation
Spare part direct replacement without holder modification: Priority MRO RGS4A-660V125A aR or Longrong RGS4-660/125 aR
DC bus / energy storage application requiring high safety certification: Sinofuse RS94G (verify cabinet mounting clearance)
Fuse Replacement Verification Procedure (Pre-Energization Check + 電源投入テスト, HINODE 660GHX125 → Domestic RGS4A/RGS4)
応用: Fuse replacement for variable frequency drives, rectifier units and DC power circuits. Core objective: Prevent secondary power semiconductor damage from direct energization.
- Power Isolation & Safety Pre-Work (必須)
- Disconnect upstream circuit breaker / contactor and implement Lockout/Tagout (心臓). Fully discharge DC bus and capacitors; verify AC/DC voltage <5V with multimeter.
- Remove blown fuse link and visual inspection:
Ceramic body crack, arc flash or blackening;
Copper terminals of HT6017 fuse holder: 酸化, burn mark or deformation;
Thread damage on holder bolts.
⚠️ Once fuse blows, do not merely replace fuse. Power semiconductors on downstream must be inspected.
- Downstream Power Semiconductor Fault Screening (Critical after Fuse Blowout)
- Rectifier bridge / IGBT module test (multimeter diode mode)
Measure forward and reverse voltage drop of each terminal to confirm short-circuit breakdown.
Check snubber capacitors and DC bus capacitors for bulging, leakage and short circuit.
- Inspect busbars and terminals for short circuit and cable insulation damage.
If IGBT / rectifier bridge breakdown is found: replace damaged power semiconductor first before installing new fuse. Short-circuited devices will blow new fuse instantly or cause explosion upon energization.
- Pre-Installation Verification of New Fuse Link
- Model check: aR semiconductor ultra-fast fuse, rated voltage ≥660V, rated current 125A. Confirm striker status (original 660GHX125 has no striker; avoid mistakenly fitting striker-equipped version).
- Dimension verification: body φ17, overall length 98mm, hole center distance 76mm, flange hole φ6.5; confirm smooth fitting into HT6017 holder.
- 目視検査: ceramic housing crack-free, metal terminals at both ends no dent or deformation.
- 締付トルク: Recommended bolt torque 8~10 N·m. Insufficient torque causes high contact resistance and overheating leading to nuisance blowing; excessive torque cracks ceramic body.
- Cold Insulation Test (De-Energized)
- Disconnect wiring on one side of fuse link, use megger:
Main circuit insulation test to earth (1000Vメガー, pass if ≥100MΩ);
Verify no short circuit between phases or DC positive/negative bus.
- Recheck inter-phase / DC bus positive-negative for short circuit with multimeter.
- Stepwise Power-On Verification (No Full Load Closing at Once)
- No-load energization: Disconnect output side (モーター / 負荷). Apply low trial voltage first (variable transformer preferred), ramp up gradually to rated 660V.
Monitor fuse and holder for abnormal noise, smoke or overheating;
Measure voltage across fuse link; voltage drop shall be extremely low under normal no-load condition.
- No-load operation for 10~30 minutes: Infrared temperature measurement on metal terminals at both ends of fuse link; temperature rise ≤70K is acceptable. Shut down immediately if temperature rises rapidly and inspect contact surface.
- Stepwise load ramp-up: Load at 25%→50%→75%→100% in sequence, hold each step for 15~30 minutes, continuously monitor terminal temperature.
- 記録: Circuit current and fuse terminal temperature for future baseline maintenance reference.
- 状態異常 & Shutdown Criteria
Immediately cut off power if any of the following occurs:
- Fuse blows the moment of closing;
- Continuous rapid temperature rise at terminals;
- Arc, burning smell or ceramic body discoloration;
- Abnormally high circuit current.
- Long-Term Inspection after Commissioning
- Periodic infrared thermal inspection, focus on fuse flange terminals;
- Annual power-off inspection for oxidation of holder contact surface and re-torque;
- Retain TCC curves of original and replacement fuse for future failure analysis.
補足: Replacement Boundary Risk Statement
Domestic RGS4 series AC breaking capacity is 80kA vs original Hinode 100kA.
If site prospective short-circuit current >80の, this domestic model is not applicable; re-evaluation or continue using imported fuse required.