キーエンス GS-11N5 Non-contact Safety Interlock Switch (GS Series Standard Type, NPN出力, 5m Pre-cabled)
応用: Non-contact interlock detection for equipment safety guards/protective doors. Used together with GS series actuators (magnetic heads). Applied to machine tools, automated production lines and robot safety fencing.
✅ モデルコードの説明
GS: GS series non-contact safety interlock switch
11: Standard main unit model
N: NPN OSSD safety output (P stands for PNP)
5: 5m pre-fitted cable with bare wire ends (GS-11N10 is the 10m cable variant)
📋 Core Electrical & Sensing Specifications
- 電源: DC24V ±20%, クラス 2 電源
- 出力: Dual OSSD NPN safety transistor outputs + 1 auxiliary non-safety AUX output (最大. 50ミリアンペア)
- 検出距離 (with GS actuator)
正面取付: Sao(オフ→オン)=10mm; Sar(オン→オフ)=18mm
側面取り付け: Sao(オフ→オン)=6mm; Sar(オン→オフ)=14mm
- 応答時間
Detected → Not detected: 20ms +2ms ×(number of cascaded units −1)
Not detected → Detected: 30ms +25ms ×(number of cascaded units −1)
- カスケード: まで 30 直列のユニット
- マックス. door actuation frequency: 3Hz
- 安全認証
EN ISO13849-1: PLe / カテゴリ4
IEC61508: SIL3; EN ISO14119 Type4 safety switch
- 保護: Reverse power polarity protection, 出力短絡保護, サージ保護
🧵 Cable Pin Definition (8-core bare-end cable)
| ワイヤーの色 | 信号 | 説明 |
| 茶色 | ピン2 | DC24Vプラス |
| 青 | Pin7 | 0VGND |
| 黒 | ピン5 | OSSD1 (安全出力 1, NPN) |
| 白 | ピン6 | OSSD2 (安全出力 2, NPN) |
| Red/Black | ピン8 | Safety Input 1 |
| Red/White | ピン4 | Safety Input 2 |
| グレー | ピン1 | AUX auxiliary output (非安全性, for PLC status feedback) |
| 水色 | ピン3 | 未使用, must be individually insulated |
配線上の注意: Dual OSSD outputs connect to safety relay / safety PLC; AUX is only for status monitoring, MUST NOT be wired into safety circuit.
📌セレクション & マッチングアクセサリー
GS-11N5 is only the switch body. GS series actuator (magnetic head) 別途注文する必要があります, 例えば. GS-A10, GS-A20. No mechanical contact between actuator and main unit; detection relies on magnetic field.
Peer models comparison:
GS-11N5: NPN, 5メートルケーブル
GS-11N10: NPN, 10メートルケーブル
GS-11P5: PNP, 5メートルケーブル
GS-11P10: PNP, 10メートルケーブル
⚠️インストール & メンテナンスガイドライン
- The gap between main unit and actuator must stay within rated sensing range. Reserve clearance for vibration-prone sites to prevent false triggering.
- Do not install close to strong magnets to avoid magnetic interference.
- For cascaded configuration, total response time increases with series quantity; safety circuit assessment must include delay.
- Enclosure IP rating: 産業環境に適した, avoid continuous immersion.
- Troubleshooting priority: 電源をチェックしてください, cable breakage, actuator position offset first. Mismatch of dual OSSD channels usually indicates fault.
📎 Alternative Products
Similar non-contact safety gate switches: Schneider XCS-DMP, Pilz PSENmag, Omron D40A series. Note differences in safety level, OSSD type and cascading capability; direct replacement into safety circuit is not allowed.
GS-11N5 Troubleshooting Checklist (LEDインジケーター + 現象 + 救済策)
GS-11N5 equipped with tri-color LED: 緑 / オレンジ / 赤. Judge fault by LED status first.
Never short OSSD channels for testing. Lock-out & tag-out equipment before modifying safety circuits.
- LED Status Definition
| LEDステータス | 意味 |
| Solid Green | 普通: actuator detected, door closed, dual OSSD channels conductive |
| Solid Orange | Power OK, actuator not detected (ドアが開いています), OSSD cut off |
| 赤一色 | 内部故障 / OSSD channel mismatch / 短絡, safety circuit locked |
| Flashing Red | Cascading circuit fault / wrong safety input wiring |
| LEDなし | 電源がありません, broken power wire, 逆極性 |
- Step-by-step Troubleshooting (from simple to complex)
2.1 Power Check (priority when no LED)
- Measure Brown(24V+) and Blue(0V), confirm DC24V within 19.2~28.8V
- Check reverse polarity. Built-in reverse protection prevents burnout but unit will not operate.
- Inspect cable root for bending damage (5m cable model most prone to wire breakage at root).
- Confirm Class2 power supply with sufficient capacity and no voltage drop.
2.2 センシングギャップ & アクチュエーター (solid orange LED, door closed but no detection)
- Confirm actuator is GS series (GS-A10 / GS-A20). Other brand magnetic heads cannot be used.
- 正面取付: gap ≤10mm for activation; >10mm cannot trigger; >18mm permanently off.
- 側面取り付け: Sao=6mm, Sar=14mm, stricter gap requirement.
- Check loose mounting brackets, vibration shift, deformed metal cover squeezing main unit/actuator.
- Check nearby strong magnets, inverters or high-current cables causing magnetic interference.
2.3 Safety Input Wiring (Most common pitfall for non-cascaded use)
For GS-11N5 (NPN), when not cascaded, the two safety inputs must be shorted to 0V (青い線)
Red/Black (Safety Input1) and Red/White (Safety Input2) short to 0V;
✘ Wrong: フローティング / connected to 24V → red fault LED.
カスケード: OSSD outputs of previous GS connect to safety inputs of next unit, channel-to-channel matching.
2.4 OSSD Dual Channel Fault (Solid Red LED)
症状: OSSD1 and OSSD2 status mismatch, safety relay reports channel error
- Disconnect load and measure Black(OSSD1) and White(OSSD2) 別途.
- Check OSSD cable short to ground or inter-wire short; OSSD short-circuit protection triggers latch-up.
- Wiring resistance limit: total loop resistance ≤2.5Ω; long/thin cables may trigger fault.
- Capacitive load limit: 最大. 2.2μF; parasitic capacitance of long cables may cause timing mismatch between channels.
- Check cross-wiring between safety relay / safety PLC channels. OSSD1 and OSSD2 must not be swapped.
2.5 AUX Auxiliary Output (Status feedback only, 非安全性)
Gray AUX follows door state, only for PLC monitoring, must not be inserted into safety circuit
ドアが閉まった: AUX ON; Door open: AUX OFF
AUX abnormality does not affect OSSD safety function, only status indication.
- Quick Fault Reference Table
| 故障現象 | 考えられる原因 | 救済策 |
| Door fully closed, orange LED remains, safety circuit open | Gap exceeds Sao, mounting offset, wrong actuator | Adjust gap, fasten bracket |
| Red LED on at power-up, リセットできません | Wrong safety input wiring (NPN not shorted to 0V); OSSD short | Check Red/Black & Red/White wiring; disconnect load to retest OSSD |
| Intermittent safety fault, random tripping | Cable root breakage; gap drift under vibration; cable voltage drop | ケーブルを交換する; reinforce mounting; increase wire gauge |
| Cascaded units, downstream unit red LED | Wrong cascading wiring; excessive total response time | Disconnect cascade one by one to locate faulty unit; evaluate total safety delay |
| Normal briefly after power cycle, fault soon recurs | Hidden short in output loop; excessive cable parasitic capacitance | ケーブル長を短くする, add termination to reduce capacitance |
- Criteria for Main Unit Damage Replacement
Replace GS-11N5 if any condition below is met:
- 力, wiring and actuator are fully verified correct, red LED latched and cannot reset.
- Actuator within qualified sensing distance, green LED fails to light up.
- OSSD channel mismatch persists even after all external loads disconnected.
⚠️ Safety Precautions
- Shut down equipment and cut off power before safety circuit test.
- Do not short OSSD safety outputs for commissioning.
- Perform full safety function verification after switch replacement.
- マックス. 30 units for cascading; longer chain brings larger response delay, which must be included in safety assessment.
GS-11N5 Wiring Example for Safety PLC
前提条件: GS-11N5 is NPN OSSD dual safety output. This case: 単体, non-cascaded, widely used for safety gates on automated lines.
Safety PLC examples: KEYENCE KV-S04 / Pilz PNOZmulti / Siemens F-PLC. Principle is universal, terminal numbers vary by brand.
⚠️重要: OSSD is safety transistor output, NEVER short OSSD for testing. Lock-out & tag-out before modifying safety circuit.
- GS-11N5 Cable Assignment (単体, non-cascaded)
| ワイヤーの色 | 信号 | Wiring Target | 備考 |
| 茶色 | DC24V+ | 24V Power Positive | Main unit power supply |
| 青 | 0V(GND) | 24V Power Negative | Main unit power supply |
| 黒 | OSSD1 (Safety Channel1 NPN) | Safety PLC Safety Input CH1 | NPN: pulled to 0V when door closed |
| 白 | OSSD2 (Safety Channel2 NPN) | Safety PLC Safety Input CH2 | Dual independent channels, connect to two separate safety inputs |
| Red/Black | Safety Input1 | Short to Blue(0V) | Mandatory for non-cascaded use; floating wire triggers red fault LED |
| Red/White | Safety Input2 | Short to Blue(0V) | Mandatory for non-cascaded use |
| グレー | AUX Auxiliary Output | Standard PLC Digital Input (non-safety point) | Door status monitoring only, must not connect to safety circuit |
| 水色 | 未使用 | Insulate separately, no connection | Do not ground or connect to 24V |
NPN OSSD Characteristics:
✅ Door closed (actuator in place): OSSD1 & OSSD2 turn ON → Black & White ≈0V
✅ Door open: OSSD1 & OSSD2 OFF → high impedance, near 24V
- Safety PLC Side Wiring Logic (Dual-channel Safety Input)
Two common safety PLC input types:
タイプA: Sourcing safety input (High level active)
GS-11N5 NPN OSSD cannot directly drive sourcing safety input
✅ Solution: Pull-up resistors (2.2kΩ /0.5W recommended) on Black & White wires to DC24V.
When door closed, OSSD pulls signal low. PLC detects consistent low level on both channels as safe state.
タイプB: Sinking safety input (Low level active, 推奨)
Direct connection for GS-11N5, no extra resistors needed
Safety PLC internal: safety input terminals pulled up to 24V
Black OSSD1 → Safety Input CH1
White OSSD2 → Safety Input CH2
ドアが閉まった: OSSD ON, CH1 & CH2 pulled to 0V, dual-channel consistent, safety circuit enabled
Door open: OSSD OFF, CH1 & CH2 return to 24V, safety circuit de-energized
- AUX Auxiliary Output Wiring (標準PLC)
Gray AUX (NPN):
AUX emitter internally connected to 0V; collector requires external 24V pull-up to standard PLC DI
Standard DI wiring: 24V → DI terminal; Gray wire to DI common
ドアが閉まった: AUX ON → DI ON; Door open: AUX OFF → DI OFF
使用法: HMI door status display, alarm indication; must not be used for safety stop logic
- Cascading Overview (Multiple GS-11N5 in series to Safety PLC)
Used for multiple safety doors in series detection, 最大. 30 単位
- OSSD1 (黒) of previous GS → Safety Input1 (Red/Black) of next GS
- OSSD2 (白) of previous GS → Safety Input2 (Red/White) of next GS
- Last GS-11N5: OSSD1 & OSSD2 connect to dual safety inputs of safety PLC
- Safety Inputs of first GS shorted to 0V
注記: Total response time accumulates in cascade; safety evaluation must calculate total delay. Any door open will cut off OSSD for the whole chain.
- Safety PLC Program Configuration Points
- チャンネルモード: Set as Dual-channel safety input, enable cross monitoring for channel discrepancy
- Discrepancy tolerance time: 20~50ms typically, do not set excessive value
- Fault action: Channel mismatch → safety stop, ラッチ故障, reset signal required
- Do not use AUX signal for safety stop logic; use only for diagnostic alarm
- After program download, full function test: door closed allow run, door open immediate stop, single wire break triggers safety fault
- Site Commissioning Checklist
- 電源前のチェック: Red/Black & Red/White shorted to 0V (単体), Light Blue insulated
- LED test: Actuator near → solid green; actuator removed → solid orange; no red LED
- PLC signal: CH1 & CH2 go low simultaneously when door closed; high when door open
- Fault simulation: Disconnect Black or White wire individually; PLC must detect channel mismatch and trigger safety fault
- Cable parasitic capacitance: Use shielded cable for wiring >20メートル, shield grounded at single end to prevent false OSSD action
- よくある落とし穴
- ❌ Red/Black & Red/White floating for single unit: immediate red latch-up, frequent beginner wiring mistake
- ❌ AUX Gray wire connected to safety PLC safety channel: safety certification invalid, major hazard
- ❌ NPN OSSD directly to sourcing safety input: reversed logic, cannot work properly
- ❌ Safety PLC set to single channel mode: loss of cross-channel fault detection, safety rating downgraded
KEYENCE GS Series Safety Gate Switch Full Model List
GS series is divided into three categories: GS-10 Non-locking non-contact magnetic safety switch (GS-11N5 belongs to this group), GS-50 Solenoid locking (Power-to-release), GS-70 Solenoid locking (Power-to-lock)
Model coding rule:
N=NPN出力; P = PNP出力
5 = 5m bare cable; 10 = 10m bare cable; PC = M12 connector (0.3m short pre-cable)
11=標準; 10=Basic; 13=High-function; 51/71=Locking standard; 53/73=Locking high-function
- Non-contact Type (No solenoid lock, magnetic safety switch GS10 Series)
Only for door position detection, no locking function; PLe / 猫4 / SIL3, まで 30 cascaded units
| モデル | タイプ | 出力 | Cable Style | 説明 |
| GS-10PC | 基本タイプ | PNP | M12コネクタ | ベーシックモデル, simplified function, no EDM |
| GS-11N5 | 標準タイプ | NPN | 5m bare cable | 対象モデル, 8-core bare wire |
| GS-11N10 | 標準タイプ | NPN | 10m bare cable | NPN,10メートルケーブル |
| GS-11P5 | 標準タイプ | PNP | 5m bare cable | PNP,5メートルケーブル |
| GS-11P10 | 標準タイプ | PNP | 10m bare cable | PNP,10メートルケーブル |
| GS-11PC | 標準タイプ | PNP | M12コネクタ | M12コネクタバージョン |
| GS-13P5 | High-function | PNP | 5m bare cable | Support EDM external device monitoring, 手動リセット |
| GS-13PC | High-function | PNP | M12コネクタ | High-function, M12コネクタ |
- Solenoid Lock GS-50 Series (Power-to-release: Locked when powered, unlocked on power loss)
Locking logic: Keep energized to hold lock; door releases automatically upon power failure. Suitable for safety guard doors, safety chambers.
| モデル | タイプ | 出力 | Cable Style |
| GS-51N5 | Locking Standard | NPN | 5m bare cable |
| GS-51N10 | Locking Standard | NPN | 10m bare cable |
| GS-51P5 | Locking Standard | PNP | 5m bare cable |
| GS-51P10 | Locking Standard | PNP | 10m bare cable |
| GS-51PC | Locking Standard | PNP | M12コネクタ |
| GS-53PC | Locking High-function | PNP | M12コネクタ |
- Solenoid Lock GS-70 Series (Power-to-lock: Lock only when energized)
Unlocked when power off; coil must be energized to engage lock. Suitable for robot safety doors.
| モデル | タイプ | 出力 | Cable Style |
| GS-71N5 | Locking Standard | NPN | 5m bare cable |
| GS-71N10 | Locking Standard | NPN | 10m bare cable |
| GS-71P5 | Locking Standard | PNP | 5m bare cable |
| GS-71P10 | Locking Standard | PNP | 10m bare cable |
| GS-71PC | Locking Standard | PNP | M12コネクタ |
| GS-73PC | Locking High-function | PNP | M12コネクタ |
- Matching Actuators (Magnetic head, mandatory for GS main unit)
| モデル | 名前 |
| GS-A10 | Standard Actuator |
| GS-A20 | Long Sensing Distance Actuator |
- 取付金具 & 付属品
GS-B01, GS-B11, GS-B21, GS-B31, GS-B41, GS-B33, GS-B43
- Other Accessories
GS-T01: Test Tool
✅ Quick Selection Guide
- Only door detection, no locking → GS-10 series (GS-11N5/GS-11P5)
- Lock required, auto unlock on power loss → GS-50 series
- Lock required, lock only when powered → GS-70 series
- High-function models (GS-13/53/73): support EDM external diagnostic, 手動リセット; GS11/51/71 standard versions do not support EDM.
述べる: GS models with SO suffix (GS-10PCSO / GS-11PCSO / GS-51PCSO / GS-71PCSO) are special custom versions, rarely used in general projects.