シュナイダー 3CT-H1-100-C 変流器

Schneider 3CT-H1-100-C 変流器の完全な仕様 (EOCR専用) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • 製品詳細

Full Specification of Schneider 3CT-H1-100-C 変流器 (EOCR専用)

  1. モデルコードの解釈
コードセグメント意味説明
3CT製品シリーズThree-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1仕様コードPrimary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100定格一次電流100あ (numerator of transformation ratio)
CMounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. コア技術パラメータ
パラメータのカテゴリ仕様述べる
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
精度クラスクラス 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10バージニア州Max permissible secondary loop impedance 200mΩ
周波数範囲50/60HzGeneral industrial frequency
定格絶縁電圧AC 600V最大連続動作電圧
耐電圧2kV (50Hz, 1分)Insulation test standard between windings and earth
Insulation Resistance≧100MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
全体の寸法W150×H71×D55mmコンパクトな構造, space-saving installation
取付タイプPanel mountingCompatible with standard 35mm DIN rail
材料Flame-retardant engineering plasticCompliant with UL94 V0 standard
重さ約. 0.58kgSingle unit weight
認証CE, ULConforms to international safety standards
注文番号3CT-H1-100-CExclusive official Schneider order code
  1. 全モデルリスト (EOCR 3CT Series)
モデルRatioAperture ShapeBore Size定格電流取付タイプ
3CT-HS-75-C/Z75/5あCircularφ22mm75あC=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5あCircularφ25mm100あC=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5あ四角30×30mm150あC=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5あ四角35×35mm200あC=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5あ四角45×45mm300あC=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5あ四角55×55mm400あC=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
ブランドモデルRatio正確さBurdenAperture互換性
シュナイダー

(SAMWHA)

3CT-H1-100-C100/5あクラス 110バージニア州φ25mmPerfect match for EOCR
シーメンス5SD7410-7100/5あクラス 110バージニア州φ25mmUniversal type, adaptation test required
ABBCT-AR/100100/5あクラス 115バージニア州φ25mmHigher burden capacity, EOCR compatible
チントBH-0.66/100100/5あクラス 110バージニア州φ25mmCost-effective domestic alternative
美味しいLMZ1-0.66/100100/5あクラス 110バージニア州φ25mm国内での交換, minor dimension difference

交換ノート

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. トラブルシューティング & メンテナンス
故障現象考えられる原因Inspection Stepsソリューション
No secondary output間違った配線, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
Insulation failureDampness, insulation aging, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

Safety Rules

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. 応用 & Cases

該当するシナリオ

EOCR motor protection system: 過電流, undercurrent and phase loss protection

Low-voltage power distribution: Current monitoring and protection for circuits below AC 600V

Motor control center: Compact layout saves cabinet space

Industrial production lines: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400Hz) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

典型的なケース

場合 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

場合 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, 節約 50% 設置スペース, simplifying wiring and improving operational reliability.

  1. 選択 & 設置ガイドライン

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

設置上の注意事項

Keep correct S1(I+) and S2(I-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

メンテナンススケジュール

アイテムサイクル標準
Visual inspection毎月No crack, looseness or overheating mark
Terminal tightening四半期ごとTorque range 2-3N·m
絶縁試験YearlyResistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 正確さ, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.