Full Specification of Schneider 3CT-H1-100-C 変流器 (EOCR専用)
- モデルコードの解釈
| コードセグメント | 意味 | 説明 |
| 3CT | 製品シリーズ | Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea |
| H1 | 仕様コード | Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm |
| 100 | 定格一次電流 | 100あ (numerator of transformation ratio) |
| C | Mounting/Terminal Type | Terminal block type; Z stands for direct lead wire type |
Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR
- コア技術パラメータ
| パラメータのカテゴリ | 仕様 | 述べる |
| Transformation Ratio | 100A/5A | Standard secondary current 5A, compatible with full EOCR series |
| 精度クラス | クラス 1 | Measuring tolerance ±1%, meets protection and metering requirements |
| Rated Burden | 10バージニア州 | Max permissible secondary loop impedance 200mΩ |
| 周波数範囲 | 50/60Hz | General industrial frequency |
| 定格絶縁電圧 | AC 600V | 最大連続動作電圧 |
| 耐電圧 | 2kV (50Hz, 1分) | Insulation test standard between windings and earth |
| Insulation Resistance | ≧100MΩ (DC 500V) | Measured by megohmmeter |
| Aperture Size | Circular φ25mm | Standard bore of H1 series |
| 全体の寸法 | W150×H71×D55mm | コンパクトな構造, space-saving installation |
| 取付タイプ | Panel mounting | Compatible with standard 35mm DIN rail |
| 材料 | Flame-retardant engineering plastic | Compliant with UL94 V0 standard |
| 重さ | 約. 0.58kg | Single unit weight |
| 認証 | CE, UL | Conforms to international safety standards |
| 注文番号 | 3CT-H1-100-C | Exclusive official Schneider order code |
- 全モデルリスト (EOCR 3CT Series)
| モデル | Ratio | Aperture Shape | Bore Size | 定格電流 | 取付タイプ |
| 3CT-HS-75-C/Z | 75/5あ | Circular | φ22mm | 75あ | C=Terminal block, Z=Lead wire |
| 3CT-H1-100-C/Z | 100/5あ | Circular | φ25mm | 100あ | C=Terminal block, Z=Lead wire |
| 3CT-HH-150-C/Z | 150/5あ | 四角 | 30×30mm | 150あ | C=Terminal block, Z=Lead wire |
| 3CT-H2-200-C/Z | 200/5あ | 四角 | 35×35mm | 200あ | C=Terminal block, Z=Lead wire |
| 3CT-H3-300-C/Z | 300/5あ | 四角 | 45×45mm | 300あ | C=Terminal block, Z=Lead wire |
| 3CT-H4-400-C/Z | 400/5あ | 四角 | 55×55mm | 400あ | C=Terminal block, Z=Lead wire |
- Cross-brand Alternative Comparison
| ブランド | モデル | Ratio | 正確さ | Burden | Aperture | 互換性 |
| シュナイダー (SAMWHA) | 3CT-H1-100-C | 100/5あ | クラス 1 | 10バージニア州 | φ25mm | Perfect match for EOCR |
| シーメンス | 5SD7410-7 | 100/5あ | クラス 1 | 10バージニア州 | φ25mm | Universal type, adaptation test required |
| ABB | CT-AR/100 | 100/5あ | クラス 1 | 15バージニア州 | φ25mm | Higher burden capacity, EOCR compatible |
| チント | BH-0.66/100 | 100/5あ | クラス 1 | 10バージニア州 | φ25mm | Cost-effective domestic alternative |
| 美味しい | LMZ1-0.66/100 | 100/5あ | クラス 1 | 10バージニア州 | φ25mm | 国内での交換, minor dimension difference |
交換ノート
- Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
- Aperture shall match cable outer diameter; H1 series fits cables below 25mm
- Calibrate transformation ratio and phase for alternative models
- トラブルシューティング & メンテナンス
| 故障現象 | 考えられる原因 | Inspection Steps | ソリューション |
| No secondary output | 間違った配線, winding open circuit, loose terminals | Check S1/S2 polarity; test secondary resistance; fasten terminals | Correct wiring polarity; replace faulty CT; reinforce terminals |
| Large measuring deviation | Overloaded circuit, mismatched ratio, core saturation | Calculate loop impedance; verify ratio; check overload current | Reduce circuit burden; replace matched model; upgrade CT specification |
| EOCR false tripping | Phase shift, harmonic interference, CT saturation | Test three-phase phase difference; check frequency converter interference; monitor surge current | Recalibrate phase; install harmonic filter; adopt high-saturation CT |
| Insulation failure | Dampness, insulation aging, mechanical damage | Measure insulation resistance; inspect shell cracks; test winding insulation | Dry or replace unit; renew CT; repair damaged parts |
Safety Rules
- Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
- Check load and wiring preferentially when deviation exceeds ±2%
- Replace CT immediately if insulation resistance below 10MΩ
- 応用 & Cases
該当するシナリオ
EOCR motor protection system: 過電流, undercurrent and phase loss protection
Low-voltage power distribution: Current monitoring and protection for circuits below AC 600V
Motor control center: Compact layout saves cabinet space
Industrial production lines: Heavy-duty equipment protection in steel, cement and automobile industry
UPS feeder in data center: Precise current monitoring
Inadmissible Scenarios
Long-term operating current over 120A causing core saturation
High frequency (>400Hz) or DC circuits with poor measuring accuracy
Outdoor installation without waterproof enclosure
Secondary circuit burden exceeding 10VA
典型的なケース
場合 1: Motor Protection in Automobile Workshop
3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.
場合 2: Crane Control Cabinet Renovation
Replace old split CT with combined 3CT-H1-100-C, 節約 50% 設置スペース, simplifying wiring and improving operational reliability.
- 選択 & 設置ガイドライン
Three-step Selection Method
- Calculate current: Multiply rated motor current by 1.1 overload factor
- Select aperture: Choose circular or square bore according to cable size
- Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring
設置上の注意事項
Keep correct S1(I+) and S2(I-) connection to prevent false operation
Strictly prohibit open secondary circuit during installation and maintenance
Total secondary loop impedance shall not exceed 200mΩ
Insulation resistance shall be no less than 100MΩ before commissioning
メンテナンススケジュール
| アイテム | サイクル | 標準 |
| Visual inspection | 毎月 | No crack, looseness or overheating mark |
| Terminal tightening | 四半期ごと | Torque range 2-3N·m |
| 絶縁試験 | Yearly | Resistance ≥100MΩ |
| Ratio calibration | Biennially | Tolerance ≤±1% |
Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 正確さ, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.