(部品番号: 59659)
The ACE850FO is a fiber-optic multi-protocol communication interface module dedicated to Sepam series protective relays. It is compatible with Sepam 40/60/80 series protection IEDs, equipped with dual 100BASE-FX fiber Ethernet ports for substation bay-level networking. It supports RSTP ring topology and is suitable for switchgear cabinets with severe electromagnetic interference.
Comparison within the same series: ACE850TP is the RJ45 copper version; ACE850FO is the fiber SC version.
状態: Marked End-of-Life (EOL). Last order date: 2026-12-31; サポート & maintenance until 2030-12-31.
モデルの定義
ACE850: Sepam communication interface family
FO = Fiber Optic, fiber optic variant
材料 / 部品番号: 59659
主要な技術仕様
- Fiber Port Specifications
スピード: 100BASE-FX
Fiber type: Multi-mode fiber
Wavelength: 1300 nm
コネクタ: SC
Dual fiber ports: S-LAN (Supervision Network) and E-LAN (Engineering Network); ring topology supported
- Supported Protocol Stack
IEC 61850 MMS / GOOSE
Modbus TCP
RSTP (IEEE802.1d 2004 Rapid Spanning Tree, リング冗長性)
SNMP, FTP, HTTP, SNTP, ARP
- Compatible Host IEDs: Sepam 40 / Sepam 60 / Sepam 80 (including Sepam80 NPP)
- 電源: Powered from the Sepam unit itself; no separate power required
- Default Login Credentials
ユーザー: Admin
Password: ACE850
Port Definition
S-LAN: Supervision network, connects to SCADA backend, carries IEC61850 and Modbus TCP traffic
E-LAN: Engineering maintenance port, used for SFT2841 software local/remote commissioning and parameter download
Both ports share identical hardware; functions are differentiated by software. Star and fiber ring network topologies are supported.
典型的なアプリケーションシナリオ
Fiber networking of Sepam protection relays in medium-voltage switchgear for EMI immunity
IEC61850 digital protection at substation bay level
Dual-network redundancy and fast self-healing fiber ring for IEDs
Migration & 交換ガイドライン
ACE850FO is discontinued. New projects are not recommended for procurement; spare parts are limited to existing stock. New design options:
- Upgrade to new-generation Sepam protection relays with built-in IEC61850 fiber ports, eliminating external ACE850 modules
- Retrofit for existing Sepam40/80: evaluate full IED replacement or third-party optical-electrical converters (GOOSE latency must be validated)
Troubleshooting Checklist
- Optical link: Inspect SC connector endface cleanliness, verify multi-mode fiber matching and optical power. 100BASE-FX does not work with single-mode fiber.
- Ring network: RSTP configuration. Avoid multiple root bridges within one ring; guard against GOOSE storm.
- コミュニケーション: Distinguish S-LAN and E-LAN. E-LAN is for SFT2841 commissioning only; do not permanently connect to SCADA supervision network.
- Login: Password reset requires factory reset, which erases all network configuration.
Supporting Software
SFT2841: Configuration and commissioning software for Sepam protection relays. Connect to the E-LAN port of ACE850 for parameter download and oscillography retrieval.
Full Model List for シュナイダー Sepam 40 / 60 / 80 Series Protection IEDs (Compatible with ACE850FO)
Prefix definition:
S: フィーダ / incoming line protection
T: 変圧器の保護
M: モーター保護
G: 発電機の保護
B: Busbar protection
C: Capacitor protection
All models use the same hardware platform; protection functions are determined by embedded application firmware. Communication extension via ACE850TP (銅) / ACE850FO (fiber SC). Whole series EOL discontinued.
Sepam 40 シリーズ (経済的, basic distribution protection, 13 models)
S40: フィーダー保護 (basic overcurrent & 地絡)
S41: Directional feeder protection
S42: Dual-source / busbar ATS, parallel incoming line protection
S50: Voltage protection (PT cabinet, busbar voltage monitoring)
S51: 電圧 + 過電流保護
S52: 着信 + バスバー, automatic transfer
S53: Directional residual earth fault protection
S54: Sensitive earth fault protection
T40: Distribution transformer protection (中くらい & 小型変圧器)
T42: トランス + automatic transfer
T50: Transformer voltage monitoring protection
T52: トランス + incoming interlock
M41: Medium-voltage motor protection
G40: Small generator protection
位置決め: Basic medium-voltage switchgear, limited I/O, low sampling rate for fault recording, suitable for simple distribution networks.
Sepam 60 シリーズ (強化された, complex distribution applications, 8 models)
S60: フィーダー保護
S62: Parallel incoming line / busbar ATS
M61: Medium-voltage motor protection (heavy-duty motors)
T60: 変圧器の保護
T62: トランス + incoming interlock
G60: 発電機の保護
G62: Generator paralleling protection
C60: コンデンサバンク保護
位置決め: More I/O and stronger logic than Sepam40; supports advanced custom logic. Three HMI panel options available.
Sepam 80 シリーズ (ハイエンド, プログラム可能な, 16 models, most commonly paired with ACE850FO)
S80: Basic feeder protection
S81: Directional overcurrent feeder protection
S82: Parallel incoming line / busbar ATS
S84: Incoming protection with directional residual and islanding detection
T81: 変圧器の保護
T82: トランス + automatic transfer
T87: Main transformer protection with Buchholz and temperature monitoring
M81: Medium-voltage motor protection
M87: High-power motor with temperature and bearing monitoring
M88: Motor-transformer unit protection
G82: 発電機の保護
G87: Full generator protection (loss of excitation, 逆電力, 等)
G88: Generator paralleling protection
B80: Basic busbar protection
B83: Busbar differential protection
C86: コンデンサバンク保護 (multi-section capacitor, アンバランス保護)
位置決め: Top-tier Sepam family. Supports Logipam custom programmable logic, 36 samples per cycle fault recording, abundant I/O resources. Widely used in digital substations for GOOSE over ACE850FO.
Cross-Series Comparison for Selection
| アイテム | Sepam40 | Sepam60 | Sepam80 |
| Programmable Logic | Limited | 中くらい | Full Logipam programming |
| 障害記録 | 12 サンプル/サイクル | 12 サンプル/サイクル | 12/36 samples optional |
| I/O容量 | 低い | 中くらい | 高い |
| ACE850FO Compatible | ✅ | ✅ | ✅ |
| 一般的な使用方法 | Simple feeder, small transformer | Complex distribution, モーター | Main transformer, バスバー, ジェネレータ, digital bays |
補足情報
- Unified commissioning software: SFT2841. Connect PC to ACE850FO E-LAN for parameter download and fault record retrieval.
- ハードウェア: Native RS485 on IED; IEC61850 / GOOSE over fiber requires external ACE850FO (59659).
- EOL Status: Sepam 40/60/80 IEDs and ACE850FO are discontinued. New projects recommended to adopt Easergy P3 / P5 series.
Application Scenarios of Sepam 40 / 60 / 80 Protection IEDs (シリーズ別, 業界 & Bay Type, ACE850FO Fiber Digital Retrofit)
電圧範囲: 3kV~35kV medium-voltage distribution network, industrial and municipal user substations, excluding 110kV/220kV transmission grid. All series EOL, widely deployed in legacy retrofit projects; new projects use Easergy P3/P5 as replacement.
Sepam 40 Series|Economical, basic distribution protection
位置決め: 基本的な保護, limited I/O, 単純なロジック. For bays with simple protection requirements and budget constraints.
Typical Bay Applications
- General feeder outgoing (S40/S41): Plant / park simple outgoing protection, overcurrent and residual earth fault
- PT voltage cabinet (S50): Busbar voltage monitoring, 過電圧/不足電圧, frequency supervision
- Small distribution transformer (T40): 10kV/0.4kV distribution transformer protection, simple instantaneous overcurrent, overload and earth fault
- Busbar tie / dual-source basic ATS (S42/T42): Simple automatic transfer for single busbar sectionalized scheme with basic logic
- 中くらい & small MV motors (M41): Ordinary fans and pump motor protection
- Small diesel generator (G40): Standalone emergency generator protection
Target Industries
複合商業施設, 病院, small manufacturing plants, distribution kiosks, simple wastewater treatment plants
Normally deployed with RS485 Modbus; ACE850FO is added for IEC61850/GOOSE fiber networking.
Sepam 60 Series|Enhanced, complex distribution, medium logic requirements
位置決め: More I/O points, stronger interlock logic, multi-condition interlock supported, better recording performance than Sepam40.
Typical Bay Applications
- フィーダ & incoming protection (S60/S62): Directional protection, busbar ATS, dual-source interlock, main incoming cabinets in industrial plants
- Medium-voltage motors (M61): Heavy-duty pumps, 破砕機, compressors with RTD temperature monitoring
- 配電変圧器 (T60/T62): Distribution transformers with temperature interlock and trip blocking
- Capacitor banks (C60): Reactive power compensation capacitor protection, unbalance and overvoltage protection
- Paralleling small generators (G60/G62): Protection for multiple small generators in parallel operation
Target Industries
Pharmaceutical plants, paper mills, medium-sized waterworks, 10kV substations for data centers, rail auxiliary substations
ACE850FO is commonly used in digital retrofit to build fiber ring networks for fast GOOSE interlock.
Sepam 80 Series|High-end programmable, Logipam, complex primary equipment protection (Most common ACE850FO pairing)
位置決め: Top product line. Supports custom Logipam programming, high sampling fault recording, bus differential, full generator protection. Preferred for digital substation retrofit.
Typical Bay Applications
- 着信 / critical feeder (S80/S81/S82/S84): Directional residual, islanding detection, breaker failure, complex ATS logic
- Power transformers (T81/T82/T87): Main distribution transformers, interfacing Buchholz, 油温, pressure relief non-electrical signals
- High-power MV motors (M81/M87/M88): 鋼鉄 & mining heavy-duty motors, bearing temperature monitoring, stall and rotor protection
- Generators (G82/G87/G88): Diesel & biogas generators, loss of excitation, 逆電力, overexcitation, underfrequency, multi-unit paralleling
- Busbar protection (B80/B83): Busbar differential protection for fast fault clearing on sectionalized single busbar
- Large capacitor banks (C86): Multi-section capacitor banks with segmented unbalance protection
Target Industries
石油化学, coal chemical, 冶金 & 鋼鉄, 採掘, large data centers, power plant auxiliary power, 空港, ポート, large pumping stations. Widely used in legacy digital retrofit projects (fiber ring + IEC61850 GOOSE interlock) with ACE850FO.
Cross-Series Industry Summary
業界: 石油化学, 冶金 & 鋼鉄, 採掘, 紙, 製薬, セメント, heavy manufacturing auxiliary power
インフラストラクチャー: 空港, ポート, 鉄道輸送, tunnels, municipal water & wastewater plants
Building power distribution: Large commercial complexes, tertiary hospitals, 10kV user substations for data centers
エネルギー: On-site power plants, diesel generator stations, distributed energy grid-connection bays
クイックセレクションガイド
- Basic overcurrent & earth fault only, no complex interlock → Sepam40
- ATS, モーター温度監視, コンデンサ保護, medium complexity interlock → Sepam60
- Bus differential, transformer non-electrical protection, high-power motor, generator paralleling, custom logic, IEC61850/GOOSE fiber ring → Sepam80 + ACE850FO
Engineering Notes
- Core value of ACE850FO: GOOSE cross-cabinet interlock for Sepam80 ring deployment, replacing hardwired secondary wiring with superior EMI performance in switchgear environments
- 制限: IEDs are EOL discontinued. Not allowed for new projects; only for legacy substation retrofit and spare replacement
- コミュニケーション: Native Modbus RTU on IED; IEC61850, GOOSE and RSTP fiber ring require external ACE850FO / ACE850TP
Sepam 60 Series Full Model List (Schneider EOL Protection IEDs, compatible with ACE850FO fiber module)
Prefix definition:
S = Feeder / incoming protection
T = Transformer protection
M = Motor protection
G = Generator protection
C = Capacitor protection
Sepam60 shares unified hardware platform; protection functions are implemented by embedded firmware. Native RS485 Modbus RTU; IEC61850, GOOSE and fiber ring require ACE850FO (59659) or ACE850TP copper module.
Model Details & コア機能
- S60|Feeder / Incoming Protection
General incoming and feeder cabinets, phase overcurrent, residual earth fault, 電圧 & frequency monitoring, basic logic interlock; suitable for plant outgoing and single busbar incoming bays.
- S62|Directional Incoming / Busbar, Automatic Transfer
Directional overcurrent and directional residual earth fault protection. Supports busbar ATS, dual-source interlock and loop incoming discrimination. Widely used for single busbar sectionalized incoming and bus tie cabinets; the most popular model in Sepam60.
- T60|Distribution Transformer Protection
10kV distribution transformer protection, instantaneous overcurrent, 過負荷, residual current and oil temperature monitoring for conventional plant distribution transformers.
- T62|Transformer + Incoming Interlock / ATS
Transformer protection plus source automatic transfer logic. Able to interface transformer non-electrical signals (温度, プレッシャー). Designed for critical distribution transformers.
- M61|Medium-Voltage Motor Protection
Medium-voltage heavy-duty motors (パンプス, ファン, 破砕機). ストール, 過負荷, unbalance and earth fault protection. までサポート 16 RTD inputs for stator / bearing temperature measurement. The only motor model in Sepam60.
- G60|Standalone Generator Protection
Protection for standalone diesel generators. 過電流, 過電圧/不足電圧, underfrequency and overload for independent emergency generator sets.
- G62|Generator Paralleling Protection
Generator grid paralleling protection with reverse power, out-of-step and synchronisation-related logic for multi-generator parallel operation.
- C60|Capacitor Bank Protection
Medium-voltage reactive compensation capacitor cabinet protection, 過電流, 過電圧, residual and unbalance protection for single-section capacitor banks.
Common Hardware Specifications of Sepam60
アナログ入力: 4 current inputs, 3 voltage inputs
デジタル I/O: 28 から, 16 する
温度測定: マックス. 16 RTD channels
論理: Built-in logic equation editor (注記: Sepam60 does not support full Logipam ladder programming available on Sepam80)
障害記録: 12 samples per cycle
HMI: 3 optional panels (基本的な / 標準 / large display)
Commissioning software: SFT2841
Engineering Selection Tips
- EOL status: Sepam60 IED discontinued. New projects recommended Easergy P3. ACE850FO can be fitted for GOOSE fiber networking in legacy retrofit.
- Compare with Sepam40: Higher I/O capacity, more RTD channels and stronger custom logic.
- Compare with Sepam80: No advanced Logipam programming, no bus differential and no high sampling oscillography.
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ




















NH42-63-318x560.png)