Technical Specifications & Application Guide This is a 2‑pole, タイプC, 25A miniature circuit breaker (MCB) from Schneider Electric’s Acti9 series, with order code A9F18225 and rated breaking capacity 6kA. It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems. Features include 3‑stage current limiting, quick make mechanism, ...

  • 製品詳細

Technical Specifications & Application Guide

This is a 2‑pole, タイプC, 25あ miniature circuit breaker (MCB) from Schneider Electric’s Acti9 series, with order code A9F18225 and rated breaking capacity 6kA.

It provides overload and short‑circuit protection for lighting, socket, and small motor circuits in AC distribution systems.

Features include 3‑stage current limiting, quick make mechanism, and protection degree IP40 (front) / IP20 (terminals).

It is compatible with iC65 series accessories for functional expansion.

  1. Model Breakdown
コード意味Description
SCHNEIDERブランドシュナイダーエレクトリック (France), global electrical equipment manufacturer
iC65NシリーズActi9 iC65 MCB, N‑type breaking capacity (6の)
2PNumber of poles2‑pole, breaks phase and neutral simultaneously, for 230V/400V systems
CTripping curveタイプC, instantaneous tripping at 5~10×In (5In~10In)
25あ定格電流25 amperes continuous at 30°C ambient
A9F18225Full order codeOfficial unique identifier
  1. Core Specifications
ItemSpecification注意事項
基本
タイプ小型サーキットブレーカー (MCB)Complies with IEC 60898-1 / GB 10963.1
Tripping typeThermal‑magneticOverload (thermal) + short‑circuit (magnetic) protection
遮断容量6のMax breaking current at rated voltage
定格動作電圧AC 230V/400VFor 2‑pole version
定格絶縁電圧500VMax withstand voltage of insulation
定格インパルス耐電圧6kVSurge voltage immunity
Rated frequency50/60HzGlobal grid compatible
Tripping characteristics
過負荷保護1.13で (no trip in 1h), 1.45で (trip within 1h)Meets IEC requirements
Short‑circuit protectionInstantaneous at 5In~10InタイプC, suitable for lighting, resistive loads, small motors
Physical & environmental
寸法 (W×H×D)18mm×86mm×62mmStandard modular, 2P = 2 modules (18mm/pole)
保護等級IP40 (front), IP20 (terminals)Solid object and moisture protection
動作温度-35°C ~ +70°CSuitable for harsh industrial environments
取り付け35mm DIN railStandard panel mounting
CertificationsCCC, CE, RoHSMeets Chinese and international safety & environmental standards
  1. Features
  2. Protection performance

3‑stage current limiting: Quickly limits peak current during short circuit, reduces thermal stress, protects equipment and cables.

Selective protection: Coordinates with upstream breakers for selective tripping, limits fault area.

Fault indication: Red window shows tripped status for quick diagnosis.

  1. Structural advantages

Dual‑lock clip: Secures firmly on DIN rail, prevents vibration loosening.

Quick make mechanism: Improves closing speed, reduces arcing, extends life.

モジュラー設計: Accepts auxiliary contacts, alarm contacts, shunt trip, undervoltage trip, 等.

  1. Safety design

Isolation function: Safe isolation distance in OFF position, meets electrical safety rules.

Anti‑misoperation: Handle design prevents accidental closing.

Flame‑retardant housing: V0 grade material improves cabinet safety.

  1. インストール & メンテナンス

Installation Rules

  1. 垂直に取り付ける (±15°) for proper tripping.
  2. Wiring: Copper 1.5~35mm², Aluminium 2.5~35mm², torque 1.2~4N·m (depends on cross‑section).
  3. Environment: Avoid damp, ほこりっぽい, corrosive or high‑vibration locations.
  4. Spacing: Maintain clearance for heat dissipation; follow installation manual.

Maintenance Guide

ItemIntervalCriterionSolution
Visual inspection毎月No damage, no overheating, tight connectionsClean, tighten loose terminals
Function testQuarterlyManual ON/OFF smooth, no stickingOperate 3–5 times, check mechanism
Trip testAnnuallyOverload & short‑circuit protection functionalTest with dedicated equipment or simulate overload
Accessory checkAnnuallyAuxiliary & alarm contacts workingCheck contact condition, replace damaged parts

トラブルシューティング

  1. Frequent tripping: Check overload → short circuit → high ambient temperature → aging.
  2. Cannot close: Check short circuit → handle position → trip reset → loose wiring.
  3. Overheating: Check terminal torque → overload → ventilation.
  4. アップグレード & Replacement

5.1 Same‑series Upgrades

iC65H-2P-C25A (A9F28225): H‑type, 10の, for higher short‑circuit current.

iC65L-2P-C25A (A9F38225): L‑type, 15の, for heavy industrial use.

iC65N-2P-C25A‑Vigi (A9V58225): With residual current protection (RCCB), prevents electric shock.

5.2 Functional Accessories

Accessory代表的なモデルFunction
Auxiliary contactA9A269241NO+1NC, remote status indication
Shunt tripA9X16224Remote tripping, 例えば, fire alarm
Undervoltage tripA9X16624Auto‑trip on low voltage
Alarm contactA9A27924Signal when breaker trips

5.3 Cross‑series Alternatives

シリーズReplacement互換性
Easy9EA9AN 2P C25ASame dimensions, 6の, economical
Acti9 CVSCVS100B 2P C25AMCCB, higher breaking capacity (10の), main circuit use
Merlin GerinC65N 2P C25AFully compatible with iC65
  1. Applications
  2. Commercial buildings: Offices, shops, hotels – lighting & socket circuits.
  3. 産業オートメーション: Control panels, small motors (≤5.5kW), VFD input protection.
  4. Residential: Home distribution – air conditioners, kitchen appliances.
  5. Public facilities: Schools, 病院, stadiums – electrical safety.
  6. Selection & Purchasing Tips
  7. Load matching: Type C for lighting, ソケット, small motors (≤5.5kW). Use Type B for pure resistive, Type D for large motors.
  8. 遮断容量: Choose N (6の), H (10の), L (15の) based on system short‑circuit current.
  9. 極: 2P for 230V single‑phase where phase + neutral must be disconnected.
  10. Accessories: Add aux, shunt, undervoltage for smart systems.
  11. Authenticity: Buy from authorized Schneider distributors.
  12. Quick Fault Guide
SymptomPossible CauseSolution
Trips immediately after closingShort circuit / 過負荷Locate short, reduce load or upsize breaker
Trips after running a whileOverload / high temperatureReduce load, 通気性を改善する, check cable size
Handle cannot be pushed to ONNot reset / wiring faultPull to OFF first, then ON; check circuit
Terminal overheatingLoose connectionRetorque after power off, check terminals
No operationThermal‑magnetic unit failedReplace MCB, check coordination

SCHNEIDER iC65N-2P-C25A

Cross‑Brand Replacement Guide

Core Summary: The iC65N-2P-C25A (A9F18225) can be directly replaced by equivalent MCBs from major international and domestic brands.

Key matching requirements:

2P, タイプC, 25あ, 6の, 35mm DIN rail mounting.

  1. International Brand Direct Replacements

ABB

ReplacementOrder CodeBreaking互換性
S202-C252CDS252001R02546のBest match, same dimensions, direct swap
S202M-C252CDS262001R025410のHigher breaking capacity
S202L-C252CDS242701R02544.5のEconomy option

シーメンス

ReplacementシリーズBreaking互換性
5SL6225-75SL6のDirect replacement, IEC 60898-1
5SY6225-75SY6のEconomy range
5SN6225-7CN5SN6のClassic, reliable

Eaton

ReplacementシリーズBreaking互換性
FAZ6-C25/2FAZ6のSame dimensions & mounting
PL9-C25/2PL96のHigh performance, fast limiting

Moeller

ReplacementシリーズBreaking互換性
FAZ6-C25/2FAZ6のSame dimensions & mounting
PL9-C25/2PL96のHigh performance, fast limiting
  1. Chinese Domestic Brands
ブランドReplacementBreaking互換性
CHINTNXB-63-2P C256のCost‑effective, direct fit
DELIXICDM3-63C25/2P6のSame dimensions
LiangxinNDM1-63C25/2P6のHigh quality domestic
TENGENTGM1-63C25/2P6の基本的な保護, economical
  1. Critical Parameter Matching
ItemOriginal (iC65N-2P-C25A)一致する必要がありますAdjustable注意事項
2P2PDisconnect phase + neutral
CurveタイプC (5~10In)タイプCFor lighting & small motors
Current25あ25あContinuous rating
Breaking6の≥6kACan be higher (10の)Ensure safe short‑circuit interruption
取り付け35mm DIN rail35mm DIN railStandard panel mount
Width18mm18mmH/D may varyFits standard spacing
VoltageAC 230V/400VAC 230V/400VUniversal AC system
  1. Replacement Notes & Best Practice

Before Replacement

System short‑circuit current ≤ breaking capacity of replacement.

35mm DIN rail, space, terminal size compatible.

Protection coordination with upstream/downstream devices.

Accessory mounting interface compatible.

Replacement has valid certifications (CCC, CE).

Procedure

  1. Power off and verify voltage absence.
  2. Remove wiring and old breaker.
  3. Clip replacement onto DIN rail.
  4. Torque terminals correctly.
  5. Test ON/OFF and tripping.
  6. Update labeling and drawings.

When NOT to replace

Original uses dedicated Schneider accessories (例えば, Vigi modules).

System short‑circuit current exceeds replacement rating.

Load inrush >10で (unsuitable for Type C).

Extreme environment outside replacement specs.

  1. Recommended Replacement Levels
レベルRecommended Models応用アドバンテージ
1stABB S202-C25Industry, commerceFull performance, global support
Siemens 5SL6225-7
2ndEaton FAZ6-C25/2Control panelsGood value, easy install
Moeller DIL M9-25 C/2
3rdCHINT NXB-63-2P C25Residential, economyLow cost, fast local supply
DELIXI CDM3-63C25/2P
  1. Common Issues & ソリューション
IssueCauseSolution
Frequent tripping after replacementWrong curve / 過負荷Confirm Type C, check load, upsize if needed
Will not fitWrong rail / 幅Use 35mm DIN rail, 18mm width model
Wiring difficultIncompatible terminalsUse suitable lugs or select compatible model
Insufficient breaking capacityReplacement < system short鈥慶ircuit currentUse higher version (例えば, ABB S202M-C25, 10の)

Cross‑brand replacement for SCHNEIDER iC65N-2P-C25A depends on parameter matching + mechanical compatibility + protection coordination.

Top international brands (ABB, シーメンス) give identical performance.

Domestic brands (CHINT, DELIXI) offer cost savings.

Always verify specifications and follow electrical safety standards.