ABB T6N800-TM800-40000-8000-F-F-3P

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-ポール, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems. Full Model Code Breakdown Section Marking Description Technical Note 1 T6 ...

  • 製品詳細

This is an ABB SACE Tmax T6N 800A MCCB equipped with a TMA800/4000-8000 adjustable thermomagnetic release, 3-ポール, fixed mount, front connection, with N-type breaking capacity (36kA@400V). It is used as a main switch in industrial main circuits, heavy-duty motor protection, and power distribution systems.

  1. Full Model Code Breakdown
SectionMarking説明Technical Note
1T6フレームサイズTmax T series MCCB, max frame current 800A, compact design (depth 103.5mm)
2N遮断容量クラスN‑type standard breaking capacity: 36kA@400V/415V, 25kA@500V, 20kA@600V
3800Frame rated currentMaximum rated current of the サーキットブレーカー frame: 800あ
4TM/TMARelease typeThermomagnetic Adjustable release – both overload (thermal) and short‑circuit (magnetic) protection are adjustable
5800定格電流 (で)Continuous operating current: 800あ
640000‑8000Instantaneous trip rangeI3 = 4000–8000A, adjustable short‑circuit instantaneous protection
7FMounting type修理済み (non‑withdrawable)
8F接続タイプFront connection
93P3‑pole circuit breaker for three‑phase systems
  1. 主要な技術的パラメータ
アイテム価値備考
Product typeSACE Tmax T6N 800A MCCBFactory code: 1SDA060214R1
定格絶縁電圧 (ウイ)1000VMaximum continuous voltage for insulation parts
定格インパルス耐電圧 (ウンプ)8kVCapability to withstand transient high voltage
定格動作電圧 (うえ)690VとMax operating voltage
頻度50/60HzFor standard mains systems
Trip characteristicAdjustable thermomagnetic過負荷 (逆時間), short‑circuit (瞬間的な)
Ultimate breaking capacity (ICU)36kA@400VN class
25kA@500V
20kA@600V
Service breaking capacity (ICS)100% ICUReusable after tripping
定格電流 (で)800あMaximum continuous current
Instantaneous trip range4000–8000AI3 = 5–10In, 調整可能な
寸法 (mm)高さ×幅×奥行き: 268×210×103.5Uniform depth for panel layout
重さ約. 9kg標準
保護等級IP30IEC 60529
  1. 代表的な用途
  2. 産業用配電

Main or sub-switch for 3-phase 800A circuits in factories, ワークショップ, データセンター.

  1. Large motor protection

Three-phase induction motors up to approx. 400kW (380V)

Critical motor circuits requiring adjustable overload and short-circuit protection

  1. 建物の電気

Main switchboards in commercial and high-rise buildings

Power circuits for HVAC, パンプス, and large equipment

  1. 再生可能エネルギー

Main switches in combiner boxes for PV and wind power systems

DC-side protection for energy storage (DC version required)

  1. Other heavy industries

Mining, ポート, 鉄道, and applications requiring high reliability and adjustable protection.

  1. 代替モデル

4.1 ABB Upgrades / Replacements

代替機種主な違い応用
T6S800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to S class (50kA@400V)Systems with higher short‑circuit current near transformers
T6L800 TMA800/4000‑8000 FF 3PBreaking capacity upgraded to L class (70kA@400V)Heavy industrial grids and large plants
T6N800 PR221DS‑LSI 800 FF 3PElectronic LSI release (Long / 短い / 瞬時)Complex systems requiring precise grading and selectivity
XT6N800 TMA800/4000‑8000 FF 3PNew‑generation Tmax XT, same dimensions, パフォーマンスの向上System upgrades and new installations

4.2 Cross-Brand Equivalents

ブランドモデル主要なマッチングパラメータ注意事項
シュナイダーNSX630N TM800D 3PIn=800A, Icu=36kA, thermomagneticNSX max frame 630A; 800A is special rating
シーメンス3VA6880‑6EL32‑0AA0In=800A, Icu=36kA, 3P, thermomagnetic3VA series, 同様のパフォーマンス
三菱NF800‑CW 3PIn=800A, Icu=35kA, thermomagnetic日本規格, suitable for Japanese equipment
デルタPM800H‑3PIn=800A, Icu=36kA, thermomagneticCost‑effective industrial MCCB
  1. 選択 & アプリケーションノート
  2. Breaking capacity matching

Ensure short-circuit current ≤ 36kA@400V; otherwise use T6S/T6L.

Icu is only 20kA at 600V – use with caution.

  1. Release settings

過負荷 (thermal): set to 1.0–1.1 × load rated current

瞬時 (magnetic): set to 5–10 × In to avoid nuisance tripping while maintaining selectivity.

  1. 取り付け & wiring

修理済み, front connection; allow depth ≥ 103.5mm.

Use copper busbar/cable rated for 800A; ≥240mm² copper recommended.

  1. メンテナンス & replacement

Regularly verify release settings.

Inspect contacts after short-circuit tripping; replace if needed.

For upgrades, prefer T6S/T6L or XT6N to keep dimensions compatible.

  1. 結論

ABB T6N800-TM800-40000-8000-F-F-3P is a high-performance 800A MCCB with compact size, adjustable thermomagnetic protection, and standard breaking capacity. It is ideal for high-current three-phase circuits in industrial automation. Selection should consider system short-circuit current, protection requirements, and installation space. For better accuracy and selectivity, use higher-breaking versions or electronic releases.

Schneider Replacement for ABB T6N800-TM800-40000-8000-F-F-3P

Key Summary: The ABB T6N800 is an MCCB; Schneider’s NSX series is the best match. If you require an MT air circuit breaker (ACB), suitable models are also available. Full solutions and technical comparisons below.

  1. Product Type Comparison
タイプABBSchneider Corresponding Series主な違い
MCCBT6N800NSX Seriesコンパクト, 36–150kA, for sub‑circuits
ACBNo equivalent in Tmax T6MT SeriesLarger, 50–200kA, for main incomers
  1. Schneider MT ACB Replacement

2.1 Recmmended Model: MT08N1 3P F MIC2.0+LR 800A

Model explanation:

MT08: Frame size 800A

N1: Breaking capacity 50kA@400V (higher than T6N 36kA)

3P: 3-ポール

F: Fixed mount

MIC2.0+LR: Thermomagnetic protection (Long + 瞬時)

800あ: 定格電流

Parameter matching:

アイテムABB T6N800Schneider MT08N1Match Level
定格電流 (で)800あ800あPerfect
取り付け修理済み修理済みPerfect
3P3PPerfect
遮断容量 (ICU)36kA@400V50kA@400VHigher
Release type熱磁気 (TMA)熱磁気 (LR)Functional match
Instantaneous range4000–8000A (5–10In)5–10In adjustablePerfect

注文番号: 63006 (MT08N1 3P F MIC2.0 800A)

2.2 代替案 (Higher Breaking)

MT08N2 3P F MIC2.0+LR 800A: 50kA@400V, wider current range

MT08H1 3P F MIC2.0+LR 800A: 65kA@400V for heavy short-circuit systems

  1. Better Schneider NSX MCCB Replacement

3.1 推奨モデル: NSX800F TMD 800 3P3D F

Model explanation:

NSX800: Frame 800A

F: 36kA@400V (identical to T6N)

TMD: Thermomagnetic release (distribution type)

800: 定格電流 800A

3P3D: 3-ポール

F: 修理済み, front connection

Parameter matching:

アイテムABB T6N800Schneider NSX800FMatch Level
タイプMCCBMCCBPerfect
800あ800あPerfect
ICU36kA@400V36kA@400VPerfect
取り付け修理済み修理済みPerfect
繋がりフロントフロントPerfect
3P3PPerfect
ReleaseTMATMDPerfect
瞬時5–10In5–10InPerfect

注文番号: C80F3TM800

3.2 Higher-Breaking Alternatives

NSX800N TMD 800 3P3D F: 50kA@400V, order No C80N3TM800

NSX800H TMD 800 3P3D F: 70kA@400V for heavy industry

  1. Replacement Selection Notes
  2. Product type choice

For direct replacement of an MCCB, choose NSX for identical form factor.

For upgrading to a main incomer, use MT ACB (note larger dimensions).

  1. Release settings

Long-delay (Ir): 1.0–1.1 × rated current

瞬時 (Ii): 5–10 × In (4000–8000A) to match original ABB behavior.

  1. 遮断容量

MT08N1, NSX800N/H exceed 36kA for improved safety.

NSX800F is sufficient if Isc ≤ 36kA.

  1. Mounting space

MT ACB depth ~300mm (much larger than T6N 103.5mm)

NSX matches T6 dimensions for easy retrofit.

  1. まとめ

Top Recommendation: Schneider NSX800F TMD 800 3P3D F (order No C80F3TM800).

Perfectly matches the ABB T6N800 in type, 現在, mounting, 遮断容量, and characteristics, with near-identical dimensions for easy replacement.

代替: If ACB is required, use MT08N1 3P F MIC2.0+LR 800A (order No 63006), which provides higher breaking capacity but requires more space.