モデル: LUA1C20 (often miswritten as LUCA1C20)
シリーズ: テシスユー / TeSys Ultra motor starter signalling 補助接点ブロック
タイプ: Plug-in snap-on 補助 signalling contact, mounted on LUB power base, paired with LUCA/LUCB control units
接点構成: 2いいえ (1NO for OF running status + 1NO for SD fault trip signal)
端子: ネジクランプ端子
Terminal numbers: 17-18 (OF running status); 97-98 (SD fault trip)
電気仕様
定格絶縁電圧Ui: 250V (IEC/UL/CSA)
Conventional free air thermal current Ith: 2.5あ
信頼性の高い最小スイッチング容量: 17V / 5ミリアンペア (ideal for PLC digital inputs)
準拠基準: IEC 60947-5-1, CE, UL, CCC, グリーンプレミアム (RoHS/REACH compliant)
正味重量: 0.03 kg
Model Coding Explanation
LUA: Auxiliary contact accessory series for TeSys U
1: Single module unit
C: Signalling contact (OF+SD start/trip interlock)
20: 2 通常開 (2いいえ)
比較: LUA1C11 = 1NO+1NC (OF+SD)
Compatible Components
Power base: LUB12, LUB32, 等.
Control unit: ルカ / LUCB / LUCC / LUCD (標準 / advanced protection units)
取り付け: Plug directly into the dedicated slot on the power base, プラグアンドプレイ
応用
Remote collection of motor running feedback (の) and overload/short-circuit trip alarm (SD) by PLC; widely used for motor status monitoring in DCS and control cabinets.
相互参照 & 同等モデル
LUA1C20: 2いいえ (OF NO + SD NO)
LUA1C11: 1NO+1NC (OF NO + SD NC)
シュナイダー does not publish separate service life data for the LUA1C module. It is mechanically coupled with the LUB power base and shares the same actuation mechanism.
- 機械的寿命 (LUB power base, contact actuation limit)
15 100万操作 (15 Mcycles) — this is the official mechanical endurance rating of the TeSys U power base. The LUA1C20 contact actuates synchronously with every motor start-stop cycle, which defines the contact’s mechanical lifetime limit.
最大動作周波数: 3600 1時間あたりのサイクル数 (60 1分あたりのサイクル数); prolonged operation above this frequency is not recommended.
- 電気的寿命 (Key note: this is a low-level signalling contact, not a power contact)
This is a low-current signalling contact (Ith=2.5A, minimum switching capacity 17V/5mA). Most applications connect to PLC digital inputs (24VDC, 5~20mA).
Under low-signal conditions (24VDC, ≤10mA, non-inductive load), electrical service life approaches the mechanical life (nearly 15 百万サイクル).
When switching AC250V near 2.5A resistive loads, electrical life drops sharply to several hundred thousand cycles (no separate AC-load electrical life published in the datasheet).
- Difference Between OF and SD Contacts
の (running feedback, 端子 17-18): Actuates on every start-stop cycle; this high-frequency contact is the lifetime bottleneck.
SD (fault trip, 端子 97-98): Only actuates on protection tripping; it remains stationary during normal operation, so wear is negligible and failure due to frequent cycling almost never occurs.
- 保証期間
Contractual factory warranty: 18 months from production date (this is not the operational service life, only the manufacturer’s liability term).
Field Service Life Estimation
Typical fan & pump applications (dozens of start-stop cycles daily): 5~10 years of service is common.
Frequent-cycling process equipment (multiple cycles per minute): The 15-million-cycle limit will be reached quickly; regular contact resistance testing is recommended.
Typical failure symptom: Intermittent PLC signal loss and rising contact resistance (most common with low-level DC signals).
Supplementary Reminders
The LUA1C is a pluggable accessory. When contacts wear out, only the module needs replacement; the entire LUB base does not have to be changed.
Do not use this contact to drive contactor coils or other inductive loads directly; electric arcs will burn the contacts rapidly.
Installation Instruction for LUA1C20 (TeSys U Signalling Auxiliary Contact Module)
タイプ: Snap-on plug-and-play design, installed into the dedicated accessory slot on the LUB power base (next to the control unit). No screws required.
Compatible bases: LUB12, LUB32 and other TeSys U non-reversible power bases.
- 取付位置
On the front face of the LUB base, the side accessory slot (Slot B) next to the LUCA/LUCB control unit. Only one LUA1C signalling module can be fitted per base.
区別: LUA1C is dedicated OF+SD status signalling contact. Do not mix its slot with LUFN auxiliary contacts or LUFDH11 modules.
- Standard Installation Steps (Can be fitted live; power-off operation is recommended for safety)
- 準備: Align the module latches with the base slide rail, with the terminal side facing outwards (端子 17-18 & 97-98 facing the operator for easy wiring).
- Alignment: Insert the rear guide ribs into the internal slide rail and push horizontally.
- Locking: Push firmly until an audible click confirms both plastic latches are fully engaged.
- 検証: Pull the module outward gently; if it cannot be pulled free, locking is complete. The terminal face should sit flush without tilting or warping.
- 配線: Use screw terminals. の: 17-18; SD: 97-98, wired to PLC DI circuits.
- 削除手順 (No need to disconnect main circuit or control unit when replacing the module)
- Locate the two release latches (small tabs) on both sides of the module.
- Press both latches inward simultaneously with fingernails or a small flat screwdriver.
- Pull the module straight out horizontally.
- Critical Installation Constraints & 注意事項
- インストール手順: The module can be fitted either before or after the base is wired with main and secondary circuits, with no impact on existing wiring.
- Reversed mounting is impossible: Forcing the module into the slot backwards will break the guide ribs and latches.
- 機械的インターロック: The internal actuator only meshes with the base’s operating mechanism when fully inserted. Poor engagement causes loss of OF/SD signal synchronisation and intermittent feedback.
- 端子: ネジクランプ式 (not spring terminals). Use 0.5~1.0 mm² flexible wires for 24VDC PLC signal circuits.
- Environmental protection: No extra cover is provided for the fitted module; terminals remain exposed. Take dustproof measures in dusty cabinet environments.
- Common Faults Caused by Improper Installation
No OF feedback after motor closure: Module not fully seated; actuator not meshed mechanically.
No SD signal after tripping: Module tilted; only one side latch engaged.
Signal drops when lightly touched: Broken latches; the LUA1C module must be replaced.
- LUA1C Series (Primary Signalling Contact Modules | Front Slot B on TeSys U Base)
1) Current Production Models (Standard Ordering Items)
| モデル | 接点構成 | 端子の定義 | 応用 |
| LUA1C11 | 1NO+1NC | の(17-18 いいえ); SD(95-96 ノースカロライナ州) | Running NO + fault trip NC, widely used for PLC signal collection |
| LUA1C20 (LUCA1C20) | 2いいえ | の(17-18 いいえ); SD(97-98 いいえ) | Dual normally open signals for running and fault trip |
2) Discontinued Legacy Models with Replacement Options
| Obsolete Model | 新しい交換品 | Discontinuation Date |
| LUA1C110 | LUA1C11 | Jan-12 |
| LUA1C200 | LUA1C20 | Apr-21 |
モデルのコーディング規則
LUA1CXX
LUA: TeSys U auxiliary signalling contact series
1: Single module unit
C: OF+SD start/trip linked signalling contact
11 = 1NO+1NC; 20 = 2NO
- Full List of Other Auxiliary Contacts in the Same TeSys U Series
- ルフン (Front Main Slot, Power-Grade Auxiliary Contacts, 5A Rated)
LUFN11: 1NO+1NC
LUFN20: 2いいえ
LUFN02: 2ノースカロライナ州
- LUA8E (Side-Mounted Auxiliary Contacts)
LUA8E20: 2NO side-mounted auxiliary contact
- Dedicated Status Contacts (旅行 / Ready Position)
LUFDH11: Trip status auxiliary contact (SD)
LUFDA01: Ready-position contact
LUFDA10: Door interlock contact
- Other Matching Accessories
LUFV2: Voltage monitoring module
LUFW10: Winding over-temperature protection module
LU9C1: Blank slot dust cover
Ⅲ. Slot Allocation (Avoid Wrong Installation)
- LUA1C11 / LUA1C20: Front Slot B (beside control unit), OF+SD mechanically linked; only one module allowed per base.
- ルフン: Front Slot A, power-type auxiliary contacts.
- LUA8E: Side slot on the power base for expanded contact capacity.
- Universal Electrical Parameters for All LUA1C Models
定格絶縁電圧Ui: 250AC/DCV
従来熱電流 Ith: 2.5あ (low-level signalling only)
Minimum reliable signal level: 17V / 5ミリアンペア (PLC DI compatible)
機械的寿命: Coupled with LUB base, 15 100万操作.
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ