 Siemens 3RT1064-6AP36 Contactor - コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池

接触器/

Siemens 3RT1064-6AP36 Contactor

3RT1064-6AP36 3RT: SIRIUS Electromagnetic Contactor Series 1: Classic imported SIRIUS 3RT1 Series (国内相当: 3RT5/3RT6) 0: 3-pole contactor for motor loads (3メイン接点なし) 64: Frame Size S10, AC-3 rated current 225 あ 6: Conventional electromagnetic operating mechanism (non-electronic coil) あ: Coil voltage code → AC/DC 220~240 V (ユニバーサルAC/DCコイル) P: Main circuit busbar ...

  • 製品詳細

3RT1064-6AP36

  1. 3RT: SIRIUS Electromagnetic Contactor シリーズ
  2. 1: Classic imported SIRIUS 3RT1 Series (国内相当: 3RT5/3RT6)
  3. 0: 3-pole contactor for motor loads (3メイン接点なし)
  4. 64: Frame Size S10, AC-3 rated current 225 あ
  5. 6: Conventional electromagnetic operating mechanism (non-electronic coil)
  6. あ: Coil voltage code → AC/DC 220~240 V (ユニバーサルAC/DCコイル)
  7. P: Main circuit busbar connection
  8. 36: Permanently built-in auxiliary contacts 2NO + 2ノースカロライナ州

詳しい説明: 3-pole power contactor, Frame S10, busbar terminals, 220~240 V AC/DC coil, 修理済み 2 通常開 + 2 通常閉補助接点.

  1. Main Electrical Specifications
アイテムパラメータ
主な接点構成3P Normally Open (3いいえ)
Rated operational current AC-3 / AC-3e @400 V225 あ
モーター定格出力 (3-段階, 400 V)110 kW
Rated operational current AC-4 @400 V195 あ
制御コイル電圧UC = 220~240 V AC/DC (Universal AC & 直流)
Coil operating range0.7~1.25 × rated voltage
標準補助接点2いいえ + 2ノースカロライナ州 (内蔵, non-removable)
フレームサイズS10
主回路接続Busbar connection (ボルト締め)
補助 & coil connectionネジ端子
定格絶縁電圧1000 V
汚染度3

Cable Connection Capacity

主回路: Stranded cable 70~240 mm²

補助回路: 0.5~4 mm²

  1. Outline & Installation Information

取付方法: Base plate screw mounting (DIN rail mounting NOT supported; large S10 frame can only be fixed to cabinet base plate)

Front protection class: IP00

Ambient operating temperature: -25℃~+60℃ (full-load operation at 60℃)

  1. 典型的なアプリケーションシナリオ

Direct-on-line starting of 3-phase induction motors, main contactor for star-delta starters, VFD bypass

エアコンプレッサー, ウォーターポンプ, ファン, 射出成形機, high-power production line drives

空調設備, power plant, 冶金, port crane power circuits

⚠️ Not recommended for long-term inching operation under AC-4 duty; select higher frame size for frequent start-stop applications.

  1. Alternative Selection Reference

1) Direct OEM replacement (Siemens original)

3RT1064-6AP36 (対象モデル, 220~240 V AC/DC coil)

Coil voltage variants:

3RT1064-6AP36 = 220~240 V AC/DC

3RT1064-6BP36 = 110~127 V AC/DC

2) Upgraded alternative

3RT1065-6AP36: Frame S10, AC-3 265 あ (Higher capacity, 同一取付寸法)

⚠️ Important distinction: 3RT12xx series are vacuum contactors with different construction; not directly interchangeable.

Domestic economical model: 3RT5064 (AC-only coil, different terminal structure; cannot directly replace imported busbar-type 3RT1064).

  1. Selection Pitfall Reminders
  2. Main circuit adopts busbar connection, not cable terminals; terminal adapter accessories are required if cable wiring is needed.
  3. S10 frame without DIN rail base, only base plate mounting available.
  4. ユニバーサルAC/DCコイル; compatible with both AC230 V control and DC220 V control circuits.
  5. Auxiliary contacts 2NO+2NC are permanently built-in, cannot be removed or reconfigured freely.
  6. Standard ordering designation with hyphen: 3RT1064-6AP36, do not omit the hyphen.
  7. Optional Compatible Accessories

3RU thermal overload relays (S10 frame rating)

サージキラー (RC network, varistor for coil protection)

Mechanical interlock kits (for forward/reversing contactor pairs)

Main circuit terminal adapters (cable-to-busbar transition)

Mounting Dimensions – Siemens 3RT1064-6AP36 (Frame S10)

Important Precondition: DIN rail mounting is not supported; only base plate bolt mounting

  1. Overall Outer Dimensions (幅×高さ×奥行き, mm)

Width W: 145 mm

Height H: 210 mm

Depth D: 202 mm (cabinet internal depth occupation)

  1. Base Plate Mounting Hole Dimensions (Critical for cabinet sheet metal processing)

4 fixing through holes, bolt specification: M8

  1. 水平方向の中心距離 (left-right): 124 mm
  2. 垂直中心距離 (up-down): 186 mm
  3. 取付穴径: Φ9 mm (for M8 bolts)

Bounding outline of mounting hole centers: 124 mm (W) × 186 mm (H)

  1. Wiring Clearance for Main Circuit Busbar

Main terminals exposed on top and bottom for busbar installation:

Phase spacing: 50 mm

Terminal bolt: M12

Recommended maximum busbar thickness ≤12 mm

  1. Minimum Cabinet Installation Clearance (Siemens official heat dissipation specification)

Top clearance above contactor: ≥10 mm

Bottom clearance below contactor: ≥10 mm

Left & right side clearance: ≥10 mm

Front clearance (towards arc shield): ≥20 mm

Insufficient clearance causes temperature rise and derated operation.

  1. 重さ

Net weight of unit: 約. 7.8 kg

  1. Supplementary Installation Notes
  2. 3RT1064-6AP36 = busbar connection version. Cable-terminated models of the same frame share identical overall dimensions, only terminal structure differs.
  3. 3RT1065 (265 あ) of the same series uses S10 frame; mounting dimensions are fully interchangeable, base plate hole layout can be reused.
  4. Minimum center-to-center distance between two side-by-side contactors with mechanical interlock for forward/reversing circuit: 150 mm.
  5. For continuous full-load operation above 40℃ ambient temperature, expand surrounding heat dissipation clearance to minimum 15 mm.

Service Life Parameters – Siemens 3RT1064-6AP36 (Frame S10)

  1. 機械的寿命 (Typical value from official datasheet)

機械的耐久性: 10,000,000 動作サイクル (10 百万回)

意味: No-load open/close cycles without main circuit load. Built-in standard mechanical auxiliary contacts (2NO+2NC) do not reduce mechanical life.

⚠️ Distinction:

If electronic auxiliary modules are fitted → mechanical endurance reduced to 5,000,000 サイクル.

Standard built-in 2NO+2NC mechanical auxiliary contacts of this model are not subject to this limitation.

  1. 電気的寿命 (主な連絡先, key reference for selection)

Duty condition: AC-3, 400 V, normal motor start-stop (breaking 6×Ie starting current)

Electrical endurance ≈ 200,000 サイクル (200,000 回)

AC-4 inching duty (ロックされたローター, frequent reversing): Electrical life drops significantly, typically limited to tens of thousands of cycles. Select higher-rated contactor or dedicated AC-4 contactor for frequent jogging applications.

  1. Key Supplementary Notes
  2. Mechanical life ≠ Electrical life

Mechanical endurance reflects durability of magnetic core, springs and transmission mechanism; electrical endurance is limited by contact arc erosion. In most operating conditions, electrical service life expires first.

  1. Environmental Influences

高温, ほこり, 湿度, coil voltage deviation and vibration will shorten both mechanical and electrical service life.

  1. Maximum Permissible Operating Frequency

標準任務: ≤1200 cycles/hour. Exceeding this frequency requires current derating, resulting in aggravated temperature rise and accelerated service life reduction.

  1. Interchangeability within Frame

All S10 frame contactors including 3RT1064 / 3RT1065 share uniform mechanical endurance of 10 百万サイクル, applicable for reference.