6ES7972-0BB12-0XA0 Siemens Bus Connector

전체 모델 & Official Description Order No.: 6ES7 972-0BB12-0XA0 SIMATIC DP, PROFIBUS Bus Connector, 최대 12 메가비트/초; 90° vertical cable outlet, with PG programming socket, integrated switchable isolated termination resistor, screw terminal wiring. Model Code Breakdown Code Segment Definition 6ES7 SIMATIC S7 automation system accessories 972 PROFIBUS RS485 bus connector series 0BB 90° outlet ...

  • 제품 세부정보

전체 모델 & Official Description

주문번호: 6ES7 972-0BB12-0XA0

SIMATIC DP, PROFIBUS Bus Connector, 최대 12 메가비트/초; 90° vertical cable outlet, with PG programming socket, integrated switchable isolated termination resistor, screw terminal wiring.

  1. 모델 코드 분석
코드 세그먼트정의
6ES7SIMATIC S7 automation system accessories
972PROFIBUS RS485 bus connector series
0BB90° outlet + with PG programming socket; 0BA = without PG socket
12나사식 터미널 (non-FastConnect stripping structure)
0XA0표준 일반 버전 (독일산)
  1. 핵심 전기 & 기계 사양
  2. Communication Standard: 프로피버스-DP / MPI (RS485)
  3. 최대 전송 속도: 12 메가비트/초
  4. Termination Resistor: Built-in 220Ω, ON/OFF toggle switch (with isolation)

Termination switch set to ON for the first and last station on the bus; OFF for all intermediate stations

  1. 배선 방법: 나사 터미널, conventional cable stripping, FastConnect cable is NOT supported
  2. 인터페이스: Rear 9-pin Sub-D male connector; independent front 9-pin PG female socket (online debugging without bus interruption)
  3. 케이블 콘센트: 90° vertical downward outlet, suitable for compact cabinet installation
  4. 전체 치수: 15.8 mm(여) × 64 mm(시간) × 35.6 mm(디)
  5. 보호 등급: IP20 (실내 캐비닛 설치 전용)
  6. 온도 범위: 운영 중: 0 ℃ ~ +60 ℃; 저장: -40 ℃ ~ +70 ℃
  7. 순중량: 대략. 60 g
  8. 배선 정의 (Standard PROFIBUS Purple Cable)

Terminal A: Green signal wire

Terminal B: Red signal wire

> ⚠️ Reversing A/B will directly trigger communication failure; secure the cable shield to the connector metal clamp with grounding at both cable ends.

  1. Cross Comparison of Similar Models (선택 참고)
주문 번호Outlet AnglePG Socket배선 유형
6ES7972-0BB12-0XA090°✅ Yes나사식 터미널 (이 모델)
6ES7972-0BA12-0XA090°❌ No나사식 터미널
6ES7972-0BB42-0XA035° angled outlet✅ Yes나사식 터미널
6ES7972-0BB52-0XA035° angled outlet✅ YesFastConnect quick stripping
  1. 적용 가능한 장치 & 시나리오

S7-300 / S7-400 CPU DP ports

ET200M, ET200S DP interface modules

PROFIBUS-DP inverters, 서보 드라이브, 악기, 인코더

S7-200 SMART RS485 (MPI/DP mode)

  1. Key Application Notes & Common Pitfalls
  2. FastConnect quick stripping technology is not supported. FC cables cannot be directly crimped; select 0BB52 / 0BA52 series if FC cables are used.
  3. Online monitoring via PG socket does not require bus disconnection, ideal for non-stop equipment debugging.
  4. Only enable termination resistors at the two ends of one PROFIBUS bus. Multiple active termination resistors cause unstable communication and packet loss.
  5. Avoid excessive tension on terminals during cable bending. Reliably crimp the shield; dual-end grounding is strongly recommended for long-distance communication.
  6. Wide-Temperature Special Version (For Harsh Environments)

6AG1972-0BB12-2XA0 (SIPLUS Version)

Derived from 6ES7972-0BB12-0XA0 with anti-corrosion coating. 작동 온도: -25℃ ~ +70℃, applicable to outdoor, 공조, metallurgy and high-humidity environments.

  1. 교체 정보

Direct form-fit replacement: Prioritize identical part number for no hardware modification.

If 35° angled outlet is required: Replace with 6ES7972-0BB42-0XA0.

새로운 프로젝트의 경우, prefer FastConnect version 6ES7972-0BB52-0XA0 for higher wiring efficiency.

Supplementary Document: PROFIBUS DP Topology, 배선사양 & 문제 해결 매트릭스

Compatible with 6ES7972-0BB12-0XA0 Bus Connector

  1. Standard PROFIBUS Bus Topology (Linear Topology; Star/Tree Topology Forbidden)

Mandatory Topology Rules

  1. Linear daisy-chain connection only; T-branches and star wiring are strictly prohibited. Branches cause signal reflection, communication jitter and packet loss.
  2. Set termination resistor to ON only on the first and last connectors of the whole bus; all intermediate stations must be set to OFF.
  3. Maximum two cables (안에 / 밖으로) per bus connector. Do not terminate multiple wires on one screw terminal.
  4. Detailed Wiring Specification for 6ES7972-0BB12-0XA0

2.1 터미널 정의

에이: Green wire

비: Red wire

> ⚠️ Red = B, Green = A. A and B must not be swapped.

2.2 Shield Handling

  1. Unfold the metal shielding braid of PROFIBUS purple cable; do not cut off the copper mesh.
  2. Lay shielding braid flat and clamp under the metal shield clip of the connector.
  3. Cabinet layout recommendation: Reliably ground the shield at both ends of the bus. Dual-end grounding is preferred for long-distance and high-interference sites; single-end grounding is adopted if potential difference exists between ground points.
  4. Never short shielding braid with signal wires A/B!

2.3 Termination Resistor Switch Operation

에: 220Ω termination resistor activated (for first & last station)

끄다: Termination resistor disconnected (all intermediate stations)

> Typical Fault: Multiple stations with termination resistor ON → Impedance mismatch, frequent communication errors.

2.4 PG Programming Socket Instructions

This model integrates a 9-pin female PG socket:

Programming cable can be plugged for online monitoring without cutting off the bus.

⚠️ PG socket is only for temporary debugging; do not permanently connect other slave devices.

  1. Step-by-Step Wiring Procedure
  2. Unscrew and open the connector housing;
  3. Strip outer cable sheath, remove 6~7mm insulation of red/green cores;
  4. Route red wire to terminal B, green wire to terminal A. Tighten screws with torque 0.4~0.6Nm (avoid thread slipping);
  5. Clamp shielding braid into metal shield clip;
  6. Verify no short circuit between A and B, no exposed conductors touching each other;
  7. Toggle termination resistor switch according to station position;
  8. Close housing, insert connector into module Sub-D port and lock fixing screws.
  9. PROFIBUS DP Communication Troubleshooting Matrix
결함 증상근본 원인Stepwise Remedial Actions
All stations offline; master reports DP fault (BF LED steady red)1. Termination resistors disabled at both ends1. Check two end connectors, set termination switch to ON
2. A/B reversed for the whole bus2. Verify A(녹색)/비(빨간색) wiring section by section
3. A/B short-circuit somewhere on bus3. 전원 끄기, use multimeter to check A-B short circuit
4. Broken bus cable4. Isolate cable segments to locate break point
Random drop-out of partial slaves, flashing BF LED, intermittent communication1. Termination resistor mistakenly enabled on intermediate stations1. Inspect termination switch on every connector
2. 쉴드 접지 불량 & 전자기 간섭2. Re-tighten shield crimp and grounding bar
3. Cracked/bent cable insulation3. Rewire to eliminate all branch lines
4. Branched (별) bus wiring4. Cross-check baud rate vs maximum cable length table
5. Baud rate too high, bus length exceeds limit
Devices near master run normally, remote slaves drop out frequently1. Bus length exceeds limit corresponding to selected baud rate1. Reduce communication baud rate
2. Ground loop interference caused by multi-point grounding2. Optimize shield grounding scheme
3. Low-quality non-standard PROFIBUS Type A cable3. Replace with certified PROFIBUS Type A cable
Communication fails after PG cable insertion; restored after unpluggingPG cable contains built-in termination resistor, conflicting resistance at bus terminalAvoid long-term PG connection on end-node connectors; use PG socket on intermediate stations for debugging
Communication works after commissioning, failure occurs after equipment vibrationLoose screw terminals, 와이어 접촉 불량; cable tension pulling connector단자 나사를 다시 조이세요; fix cables with cable ties to avoid mechanical load on connectors
  1. Baud Rate — Maximum Cable Length Table (PROFIBUS Type A Cable)
전송 속도최대 버스 길이
9.6 kbit/s1200 중
19.2 kbit/s1000 중
187.5 kbit/s400 중
500 kbit/s200 중
1.5 메가비트/초100 중
3 ~ 12 메가비트/초100 중
  1. Strict Forbidden Operations (Red Line Rules)
  2. ❌ Do not terminate more than two signal wires under one screw terminal
  3. ❌ Do not construct PROFIBUS bus with star topology or T-branches
  4. ❌ Do not activate termination resistor on multiple stations simultaneously
  5. ❌ Do not swap signal wire A and B
  6. ❌ Do not short shielding braid with A/B conductors
  7. ❌ Do not replace standard PROFIBUS Type A cable with ordinary 2-core cable
  8. ❌ Do not sharply bend cable near the connector outlet to prevent internal wire fracture
  9. Additional Selection Reminder

6ES7972-0BB12-0XA0 adopts screw terminal wiring and does NOT support FastConnect cables.

For new mass rollout projects, it is recommended to select:

6ES7972-0BB52-0XA0 (35° outlet + PG socket + FastConnect)