ABB 1SDA073674R1 MCCB 션트 릴리스

Basic Information Full Model: 1SDA073674R1 Brand: ABB Product Category: Tmax XT molded case circuit breaker accessory (MCCB accessory) Prefix 1SDA = Material code for ABB Tmax series MCCB accessories Material Description 1SDA073674R1: XT4 Shunt Release (소르), AC220-240V SOR = Shunt Release Applicable Circuit Breaker: ABB Tmax XT4 molded case circuit breaker Operating Voltage: AC 220…240 ...

  • 제품 세부정보

기본정보

전체 모델: 1SDA073674R1

상표: 씨줄

제품 카테고리: Tmax XT molded case circuit breaker accessory (MCCB accessory)

Prefix 1SDA = Material code for ABB Tmax series MCCB accessories

재료 설명

1SDA073674R1: XT4 션트 릴리스 (소르), AC220-240V

SOR = Shunt Release

Applicable Circuit Breaker: ABB Tmax XT4 molded case circuit breaker

작동 전압: AC 220…240 V

기능: Remote electric tripping. Apply rated voltage to the coil to open the circuit breaker; tripping only, closing not supported.

주요 매개변수

유형: Shunt Release Coil (소르)

적용 가능한 프레임: XT4

제어 전압: AC220~240V

암호: 1SDA073674R1

설치: Internal accessory installed inside the circuit breaker, 전면 커버 분해 필요

작동 특성: 단시간근무, 연속 통전 금지; 전원 공급 시 트리핑이 트리거됨

어울리는 & 선택 참고 사항

  1. XT4와만 호환 가능. 프레임 불일치로 인해 XT1/XT2/XT5/XT6에 직접 적용되지 않습니다..
  2. 동일한 시리즈의 다른 전압 변형에 대한 참조:

1SDA073673R1: SOR XT4 AC110-120V

1SDA073675R1: SOR XT4 DC24V

  1. 주문 알림: 션트 릴리스는 옵션 액세서리입니다.; 회로 차단기 본체는 별도로 주문해야 합니다..

응용 시나리오

개폐 장치의 원격 트리핑, 화재 연결 전원 차단, PLC 신호로 제어되는 MCCB 트리핑

건물 배전, 산업용 저전압 전원 캐비닛

문제 해결 포인트

트립 실패: 공급 전압 및 단자 배선을 확인하십시오., 코일 무결성 확인. 코일은 단시간 작동이므로 장기간 전원을 공급하면 소손됩니다..

거짓 트립: 배선에 유도 간섭 전압이 있는지 확인하세요..

HS 코드 참조

85369000 (전기 스위칭 장치용 액세서리, low-voltage releases)

대체 솔루션

원래 교체: Only the same part 1SDA073674R1. 국내 대안: XT4-compatible 220V shunt release with matching mounting dimensions. 하지만, mounting clips and terminal pins need verification; direct replacement for critical circuits is not recommended.

Application Scenarios of ABB 1SDA073674R1 (XT4 SOR AC220-240V Shunt Release)

핵심원리: External AC220~240V signal energizes the coil to remotely trip the XT4 molded case circuit breaker. Closing operation is not available.

  1. 화재 경보 연결 (Most Common Scenario)
  2. The fire alarm control panel outputs a 220V signal to the shunt release coil. When fire alarm is triggered, non-fire loads (ordinary lighting, power sockets, 공기 조절, non-fire fan circuits) are disconnected.
  3. 적용 대상: Power distribution rooms, 바닥 배전함, low-voltage cabinets in shopping malls/hotels/office buildings.

요구 사항: The fire signal shall be a short pulse. SOR 코일 소손을 방지하기 위해 지속적인 통전은 금지됩니다..

  1. 산업 플랜트의 PLC/DCS 원격 트리핑
  2. 공장 전원 캐비닛 및 생산 라인 분배 캐비닛, PLC로 구동되는 AC220V 릴레이 접점은 션트 릴리스에 전원을 공급합니다..
  3. 시나리오: 장비 비상 정지 인터록, 프로세스 장애 인터록 전원 차단, 호스트 SCADA를 통한 원격 비상 종료.
  4. 대표적인 산업: 조립 라인, 포장 기계, 공기 압축기, 펌프 및 팬 전원 공급 회로.
  5. 보안 / 출입 통제 연계 전원 차단

컴퓨터실 및 중요 창고용: 출입 통제 경보 또는 침입 감지 시 해당 지역의 전원 차단을 실행합니다..

약한 전류실 및 소규모 컴퓨터실의 배전 보호.

  1. 배전계통 보호 인터록
  2. 호스트 모니터링 시스템 (SCADA) 비정상적인 상황이 감지되면 원격으로 회로를 개방합니다..
  3. 버스바 보호는 다운스트림 MCCB 트리핑을 인터록합니다. (complete switchgear projects).

메모: Only for emergency tripping. Circuit breaker manual handle operation is preferred for routine switching; frequent operation via shunt release is not recommended.

  1. Other Application Cases
  2. 지능형 전력 분배 & smart buildings: Linkage with smart meters / power monitoring devices to remotely trip upon overload or leakage alarm.
  3. Low-voltage MCC cabinets for ships, wastewater treatment and HVAC power circuits.

❌ Inapplicable Scenarios

  1. Cannot perform remote closing. SOR only provides tripping function.
  2. Not suitable for frequent switching operations (short-time duty coil; repeated operations accelerate coil damage).
  3. Must not be used in continuously energized control circuits.
  4. Only fits ABB XT4 frame molded case circuit breakers; XT1/XT2/XT5/XT6 are not compatible.

On-site Implementation Guidelines

  1. Recommended signal type: Pulse signal (0.2~1s) 영구적인 에너지 공급을 피하기 위해.
  2. 제어 루프를 위한 중간 릴레이 격리 추가; 화재 제어 캐비닛에서 직접적으로 무거운 코일 전류 출력을 피하십시오. / PLC.
  3. 회로 차단기 보조 접점을 배선 루프에 연결합니다.. 코일 보호를 위해 트립 후 코일 전원 공급 장치가 자동으로 차단됩니다..

션트 릴리스의 작동 원리 (소르, 션트 릴리스)

핵심 요약

션트 릴리스는 본질적으로 단시간 임무 전자석입니다., 회로 차단기용 옵션 액세서리. 외부에서 정격전압 인가 → 전자석이 끌어당김 → 기계적 메커니즘이 차단기 내부 트립 메커니즘을 밀어냄 → 차단기가 트립되어 개방됨.

트리핑만 수행합니다., 닫히지 않음. 코일은 단시간 사용이며 지속적인 통전은 허용되지 않습니다..

자세한 원리 분석

  1. 대기 상태

코일에 전원이 공급되지 않습니다.. The internal spring holds the armature at the released position. The armature does not contact the trip link, and the circuit breaker can be closed normally with the main circuit powered on.

  1. Trip Signal Received (Energization)

The external control circuit supplies rated voltage (AC220~240V for this ABB 1SDA073674R1). The coil generates electromagnetic force to overcome spring tension and pull the armature in.

The armature strikes or pushes the trip lever (free trip mechanism) inside the circuit breaker.

  1. Circuit Breaker Tripping & 열기

Once the free trip mechanism is activated, it no longer locks the main contacts of the circuit breaker. Driven by the internal stored-energy spring of the breaker, the main contacts separate rapidly and cut off the main power supply.

  1. Power Must Be Cut After Action

✅ 추천: Pulse signal (0.2~1s).

넘어진 후, series the circuit breaker auxiliary contact in the shunt coil loop. The coil power supply is cut immediately after breaker opening.

Continuous power supply to the coil will cause overheating and rapid burnout.

Simple Distinction from Other Releases (쉽게 혼동됨)

션트 릴리스 (소르): Trips when externally energized. Used for remote manual control such as fire linkage and PLC emergency stop; no action when de-energized.

과전류 / Thermal Release: Automatically trips on excessive main circuit current, 외부 전원 공급 장치가 필요하지 않습니다..

저전압 해제 (UVR): Trips automatically upon low voltage or power loss. Closing is only possible when power is available.

Supplementary Notes for ABB XT4 1SDA073674R1

Excitation at AC220~240V;

Installed internally within XT4 molded case circuit breaker;

Action only triggers mechanical tripping, no automatic reclosing. Manual on-site reset is required after tripping.

Common Faults of Shunt Release (소르) (Compatible with ABB XT4 1SDA073674R1)

잘못 1: Circuit breaker fails to trip upon receiving trip signal (Failure to Trip, Most Common On-site Fault)

현상: Fire/PLC sends signal; AC220~240V is measured at coil terminals, but the breaker does not trip.

원인

  1. 부적절한 설치: SOR accessory is not fully clipped and locked. Insufficient armature stroke fails to actuate the trip lever (common issue during XT4 accessory fitting).
  2. Damaged coil: 코일 개방 회로 (infinite resistance measured by multimeter) or inter-turn short circuit (obviously low resistance). Continuous energization is the primary cause of coil burnout.
  3. 기계적 발작: Dust accumulation or corrosion on armature, jammed spring; foreign matter on internal trip lever leads to insufficient thrust when armature pulls in.
  4. Insufficient voltage: Voltage drop due to long wiring distance or small wire gauge; insufficient power supply capacity to drive the coil (코일은 단시간 임펄스 부하입니다.).
  5. 일치하지 않는 프레임/모델: XT1/XT2 액세서리를 XT4에 장착, 또는 잘못된 전압 (예를 들어. AC220V에 연결된 DC24V 코일).

문제 해결

전원 끄기, 액세서리를 제거하세요. 코일에 단시간 정격전압을 별도로 인가하여 전기자가 강하게 당겨지는지 확인. 확인을 위해 액세서리를 회로 차단기에 다시 설치하고 잠급니다..

잘못 2: 통전 후 코일 화상

원인

  1. 영구 통전: 직렬로 상시 폐쇄 보조 접점 없음. 코일은 트립 후에도 전원이 계속 공급되며 몇 초에서 수십 초 내에 과열됩니다. (SOR은 단기 근무입니다., 지속적인 통전은 엄격히 금지됩니다).
  2. 과전압: 제어 회로의 서지, 전압 초과 1.1 배 정격 가치.
  3. 배선 오류: 220V 전원 공급 장치에 연결된 저전압 코일.
  4. 짧은 간격으로 반복 트리거링: 열 방출 없이 연속적으로 여러 번 작동.

잘못 3: 외부 신호 없이 회로 차단기가 예기치 않게 작동함 (거짓 트립)

원인

  1. 잔여 / 유도전압: 제어 케이블은 고전력 케이블과 병렬로 연결됩니다., 수십 볼트를 유도하고 민감한 코일을 트리거할 수도 있음.
  2. 제어 회로의 누출, 라인 습기로 인해 누설 전압 발생.
  3. 기계적 여유 공간이 너무 작음, 진동으로 인해 우발적인 넘어짐이 발생함.
  4. 중요한 구별: 과부하/단락/누전 보호로 인한 트리핑을 먼저 배제합니다.. 주 회로 보호 오류와 SOR 오류를 혼동하지 마십시오..

잘못 4: 코일 작동의 청각적 클릭, 그런데 차단기가 안 떨어지네요

현상: 에이 “딸깍 하는 소리” 전원을 공급하면 소리가 들립니다., 뼈대 움직임, 하지만 스위치는 계속 닫혀 있어요.

원인

  1. 과도한 설치 간격. 전기자 스트로크가 차단기 프리 트립 메커니즘을 트리거하기에 충분한 추력을 제공하기에 충분하지 않습니다..
  2. 마모되거나 변형된 트립 스트라이커.
  3. 차단기 본체의 프리 트립 메커니즘 압수 (SOR 코일 결함이 아님, MCCB 기계적 고장).

잘못 5: 간헐적인 트립, 가끔 실패

원인

  1. 단자가 느슨하고 접촉 불량; 진동으로 인해 회로가 분리됨.
  2. 불안정한 장력으로 인한 전기자 스프링의 피로; 먼지가 때때로 뼈대를 막습니다..
  3. 불안정한 출력 전압으로 이어지는 제어 회로의 산화된 릴레이 접점.
  4. 배선의 전압 강하 변동; 전압이 작동 임계값에 도달할 수도 있고 도달하지 않을 수도 있습니다..

권장되는 단계별 현장 유지보수 문제 해결

  1. 전원 끄기, 멀티미터로 코일 저항 측정: 개방 회로를 확인하세요. / 단락, 동일한 모델의 좋은 예비 코일과 저항 값을 비교하십시오..
  2. 차단기를 닫아두세요, SOR 단자에 직접 단시간 정격 전압을 인가합니다. (0.5초 이내) 결함이 코일 자체에 있는지 외부 회로에 있는지 확인하기 위해.
  3. 액세서리가 완전히 장착되고 잠겨 있는지 확인하십시오..
  4. 영구 코일 통전을 방지하기 위해 회로 차단기의 상시 폐쇄 보조 접점이 직렬로 배선되어 있는지 확인하십시오..
  5. 제어케이블의 전압강하 및 구동능력 점검.

중요한 유지 관리 참고 사항 (ABB XT4 SOR의 경우)

션트 코일은 펄스 전원 공급 장치만 허용합니다. (1초 이하).

지속적인 통전 테스트는 금지되어 있습니다., 1SDA073674R1을 즉시 태울 수 있음.

빈번한 기능 테스트는 권장되지 않습니다.; 기계적 타격은 서비스 수명이 제한되어 있습니다..

습하고 먼지가 많은 환경의 캐비닛에 대해 연간 샘플링 기능 검사를 권장합니다..

ABB XT4의 설치 절차 (1SDA073674R1) 션트 릴리스 SOR

⚠️ 안전 전제조건: 회로 차단기의 주 회로는 전원을 차단하고 자격을 갖춘 전기 기술자가 작동하지 않는지 확인해야 합니다.. The SOR is fitted into the right accessory compartment of XT4 circuit breaker (auxiliary contacts are normally fitted on the left).

단계 1: 준비

  1. Verify materials: XT4 circuit breaker body + 1SDA073674R1 (AC220-240V SOR). Confirm frame and voltage rating; do not use XT1/XT2/XT5 accessories.
  2. Place the circuit breaker handle at closed position. (Must install when closed! Installation in tripped position may cause jamming and inability to close.)
  3. Unscrew 2 fixing screws on the front panel of the circuit breaker and remove the front cover.

단계 2: Fit the Shunt Release

  1. Align with the right accessory cavity of the circuit breaker, hold the SOR clip, push the SOR into the slot and press firmly until a “딸깍 하는 소리” 잠그는 소리가 들린다.
  2. 육안검사: SOR surface is flush with the internal base of the breaker without tilting or looseness. 전기자 스트라이커는 회로 차단기의 내부 트립 레버와 정렬됩니다..

❗ 임계점: 장착되지 않은 SOR은 전기자 스트로크가 부족하고 전원 공급 시 트립이 발생하지 않음. 정렬이 잘못되면 차단기를 닫을 수 없게 될 수 있습니다..

단계 3: 케이블 라우팅

  1. 두 개의 제어선이 SOR과 함께 제공됩니다.. 차단기의 예비 배선 구멍을 통해 밖으로 인도하십시오.. 절연 손상을 방지하기 위해 전선을 짜지 마십시오..
  2. 보조 접점도 장착된 경우 (자동 코일 전원 차단 및 상태 피드백용), 왼쪽 슬롯에 보조 접점 장착.

단계 4: 전면 커버 재장착

  1. 내부에 이물질이 없는지, 움직이는 메커니즘에 전선이 끼어 있는지 확인하세요..
  2. 전면 커버를 다시 장착하고 두 개의 패널 나사를 대각선으로 조입니다..

단계 5: 기계적 사전 점검 (전원 없음)

  1. 수동으로 차단기를 여러 번 닫았다가 열었습니다.. 끼임 없이 원활하게 닫히고 열리는지 확인.

If the breaker trips immediately after closing: The SOR mechanically presses the trip mechanism. Disassemble and reposition.

단계 6: Electrical Test (Short-time Energization Only!)

  1. Wiring of control circuit: Connect the two SOR control wires to AC220~240V control power supply. Normally closed auxiliary contact of circuit breaker is strongly recommended in series to cut coil power after tripping and prevent burnout.
  2. 회로 차단기를 닫습니다., apply momentary pulse power (0.2~1s) and verify reliable tripping.

Continuous energization test is prohibited! Short-time duty coil can be damaged within seconds.

  1. 넘어진 후, reset and close the breaker. Repeat 1~2 times to confirm stable operation.

✅ Installation Acceptance Criteria

  1. Smooth manual closing and opening without jamming or spontaneous tripping.
  2. Reliable SOR operation under pulse power supply.
  3. Wires not squeezed; front cover fully assembled.
  4. 자동 전원 차단을 위한 보조 접점을 갖춘 제어 회로.

❌ 일반적인 설치 실수 (빈번한 현장 오류)

  1. 차단기 트립시 부속품 설치 → 메커니즘 예압, 문 닫은 후 바로 여행.
  2. SOR이 완전히 안착되지 않고 슬롯에 떠 있음 → 전기자 스트로크 부족, 전원 공급 시 트립되지 않음.
  3. 움직이는 기구에 전선이 끼임 → 기구 고착 및 절연체 마모.
  4. 직렬로 상시 폐쇄 보조 접점 없음, 영구 통전 → 코일 소손.
  5. 왼쪽 및 오른쪽 슬롯이 반전됨 (왼쪽에 SOR 장착) → 트립 메커니즘을 실행할 수 없음.

매칭 배선에 대한 간략한 설명

SOR의 두 와이어: 외부 제어 신호에 연결 (사격 통제 장치의 AC220V 릴레이 출력 / PLC). 루프에 있는 회로 차단기의 상시 폐쇄 보조 접점을 직렬로 연결합니다.. 차단기가 닫혔을 때, 보조 접점은 신호 입력을 허용하기 위해 닫힌 상태로 유지됩니다.. 한 번 넘어지면, 상시 폐쇄 접점이 열리고 SOR 코일의 전원 공급이 즉시 차단됩니다..