Honeywell Searchpoint Optima Plus (2108N4000H) 잘못 & Warning Troubleshooting Table Reading methods: 수사슴 475/375 Communicator, SHC1 Handheld Interrogator, EDD Device Description File; W=Warning, F=Fault. Under fault condition, output defaults to 0mA (this HART version can be set to 1mA). Some faults are latched and require manual clearing or power cycle reset. Error Code Status English ...

  • 제품 세부정보

하니웰 Searchpoint Optima Plus (2108N4000H) 잘못 & Warning Troubleshooting Table

Reading methods: 수사슴 475/375 Communicator, SHC1 Handheld Interrogator, EDD Device Description File; W=Warning, F=Fault. Under fault condition, output defaults to 0mA (this HART version can be set to 1mA). Some faults are latched and require manual clearing or power cycle reset.

Error Code상태English Name오류 설명On-site Troubleshooting StepsLatched
0여 / 에프Temperature Limit ExceededOperating temperature near or out of -40~+65℃ range1. Measure ambient temperature of the detector아니요
2. Check direct sunlight or overheating from heat tracing
3. 환기 개선 & shading; relocate if over-temperature
4여 / 에프Bad 24V SupplySupply voltage outside 18~32VDC operating range1. Measure terminal voltage under load (not no-load power supply)아니요
2. 케이블 전압 강하를 확인하십시오., short circuit and wire gauge
3. Verify power capacity and restart the loop
5여 / 에프Bad 4-20mA LoopAnalogue output deviation >0.5엄마, cannot output correct signal1. Check polarity, shielding grounding and loop resistance✅ Latched
2. Avoid hot-plugging multimeter probes
3. Power cycle; if fault remains, output circuit is damaged
6여 / 에프Negative Gas ReadingNegative zero drift of gas reading1. Confirm clean atmosphere with no hydrocarbon gas아니요
2. Remove dust filter and clean optical window
3. Perform zero calibration; eliminate condensation and solvent interference
8여 / 에프Obscured Optics (Optical Contamination)렌즈 & gas chamber blocked by oil, dust or water vapour, optical path attenuation1. Remove weather shield and dust barrier아니요 (frequent warning)
2. Wipe optical window with lens paper and anhydrous ethanol
3. Dry and reset; check heating function if heavy condensation
11여 / 에프Low Lamp OutputInfrared lamp power degraded, end-of-life aging1. Clean optics first to rule out contamination아니요
2. If alarm persists after reset: replace optical module due to lamp failure
13에프Hardware FaultSelf-test failure of main board and drive circuit1. 다음 시간 동안 전원 끄기 5 minutes then re-power✅ Latched
2. 전원 공급 안정화
3. Recurring fault: return for repair or replace transmitter
16에프Poor Signal QualityNoisy, unstable infrared signal with low SNR1. Clean optical window and filter first✅ Latched
2. Check water ingress or frost inside gas chamber
3. Replace optical assembly if lamp aging or optical offset occurs
22여 / 에프Internal Firmware FailureFirmware checksum error, memory exception1. Full power cycle restart✅ Latched
2. Clear fault log via HART tool
3. Persistent error: re-flash firmware or replace main board

📌 Common General Faults (No independent Error ID in HART)

  1. HART Communication Failure

확인하다: 250Ω HART resistor must be installed on the loop; correct polarity; single-end shield grounding; no excessive non-HART devices on the bus; matching baud rate.

  1. Slow reading drift with no error code

확인하다: overdue calibration; clogged dust filter; continuous low-level hydrocarbon interference; heavy oil adsorption inside gas cell.

  1. No current output & no communication after power-on

확인하다: 물 유입 & terminal corrosion in M25 junction box; burnt circuit due to reverse polarity; 끊어진 내부 퓨즈.

🛠️ Operation Guidelines (for 2108N4000H)

  1. Clear Latched Faults: HART menu →【Fault/Warning】→Clear; or power off ≥30 seconds then restart. Hardware faults will reoccur immediately after reset; do not mask them permanently.
  2. Calibration Precondition: Clear all optical path & lamp warnings before zero/span calibration; calibration will drift severely with active optics contamination warning.
  3. Spare Parts Division: 오류 8,11,16 = optical module (램프 + detector + lens); Error5,13,22 = main board failure. Board-level repair is not recommended; replace the whole transmitter directly.
  4. SIL2 Reminder: F-class faults trigger SIL safety loop action. Do not run the detector with fault masked for long; rectify promptly.

(Searchpoint Optima Plus)

제품 위치: Point-type NDIR hydrocarbon combustible gas detector, HART protocol version

Manufactured by Honeywell Analytics UK. NDIR infrared principle, immune to catalytic bead poisoning. Ideal for offshore platforms, refineries, LNG and other harsh environments; SIL2 안전 무결성 수준.

✅ Model Coding Definition

2108: Searchpoint Optima Plus series

N: Hydrocarbon HC version (메탄, propane, gasoline etc., 당신의 모델)

4: Standard diffusion type with weather shield

000: Without remote gas cell & sampling path

시간: 수사슴 7 protocol superimposed on 4-20mA signal (suffix N = pure 4-20mA without HART, 예를 들어. 2108N4100N)

실: M25 (distinguished from 41xx series with 3/4″NPT 스레드)

표준 구성: 316L electropolished stainless steel housing, dust filter, nylon weatherproof cover, sunshade against rain splash.

📌 Key Technical Specifications

목매개변수
탐지 원리Non-Dispersive Infrared (NDIR)
측정 범위0~100%LEL; configurable for hundreds of hydrocarbons & solvents (메탄, propane, ethylene, gasoline, aromatics)
전원공급장치DC18~32V, nominal 24VDC; max power consumption <4.5W
신호 출력4-20엄마 + 하트7; Modbus RS485 multi-drop bus available with optional DX100(중) 기준 치수
Current Levels (Fault/Inhibit/Alarm)잘못: 0엄마 (HART version configurable to 1mA); Inhibit: default 2mA; 경고: default 3mA; Over-range: 20~21.5mA (default 21mA)
응답 시간 (Methane)T50<3s, T90<4s
작동 온도-40℃ ~ +65℃
유입 방지IP66 / IP67
하우징 재질316 스테인레스 스틸 (CF8M); 총 무게 약. 1.6kg
안전 인증ATEX, IECEx, FM, CSA; SIL2 (IEC61508)
정확성Baseline drift <±1%FSD (HC); <±2%FSD (ethylene)
Pressure Effect0.1% reading per mbar

✨ Infrared vs Catalytic Bead Advantages

  1. Resistant to catalytic poisons (silicone, lead, H₂S), longer service life and extended maintenance interval
  2. Fail-safe optical self-test; no silent failure risk
  3. Works normally in inert atmosphere (catalytic sensors require oxygen)
  4. Built-in temperature control heating; anti-condensation optical window; pre-warning for lens contamination
  5. Onboard event log; support HART communicator for commissioning, calibration and diagnostics

🧾 Typical Application Scenarios

Offshore oil & gas platforms, FPSO, oil tankers, refineries, LNG/LPG filling stations, gas regulator stations, gas turbine power plants, solvent coating & printing workshops, tank farms.

📎 Cross-model Reference (for replacement & selection)

2108N4000H: M25 thread, 수사슴, diffusion type with weather shield (your unit)

2108N4100N: 3/4″NPT, pure 4-20mA, 하트 없음

2108N4100H: 3/4″NPT, HART version

2108N5100H: Flow-through sampling type with HART, for pipeline sampling systems

⚠️ 중요 사항

  1. Infrared detector only responds to hydrocarbons; cannot detect non-hydrocarbon flammable gases such as H₂, 콜로라도, NH₃.
  2. Calibration gas must match target gas; response factor varies for different hydrocarbons.
  3. Cannot directly replace catalytic bead sensors without rechecking host logic and alarm thresholds.
  4. 소모품 예비 부품: optical module, dust filter and weather shield are regular wear items.

Honeywell Searchpoint Optima Plus (2108 시리즈) 전체 모델 목록

  1. 모델 코딩 규칙

2108N: Standard Hydrocarbon (HC) 버전 (메탄, propane, gasoline etc.)

2108비: Ethylene & solvent dedicated version (ethylene, aromatics, esters)

4번째 자리: 4 = Diffusion type; 5 = Flow-through sampling type (with gas cell)

Thread code: 0 = M25; 1 = 3/4″NPT

접미사: N = 4-20mA only; H = 4-20mA + HART7 protocol

접미사 10 = with Remote Gas Cell (RGC); 00 = without remote gas cell

  1. 2108N Hydrocarbon Standard Models (Main Series, including 2108N4000H)

2.1 M25 thread (0) | Diffusion (4) | No RGC (00)

  1. 2108N4000N: 4-20엄마, M25, diffusion, weather shield
  2. 2108N4000H: 4-20mA+HART, M25, diffusion (당신의 모델)
  3. 2108N4001N: Ethylene calibrated, M25, diffusion, 4-20엄마
  4. 2108N4001H: Ethylene calibrated, M25, diffusion, 수사슴
  5. 2108N4010N: HC + RGC remote test cell, M25, diffusion
  6. 2108N4010H: HC + RGC, M25, diffusion, 수사슴

2.2 3/4″NPT 스레드 (1) | Diffusion (4) | No RGC (00)

  1. 2108N4100N: 4-20엄마, NPT, diffusion
  2. 2108N4100H: 4-20mA+HART, NPT, diffusion
  3. 2108N4110N: With RGC, NPT, diffusion
  4. 2108N4110H: With RGC, NPT, diffusion + 수사슴

2.3 Flow-through sampling type (5) for sampling pipeline & pre-treatment systems

M25 thread (0)

  1. 2108N5000N: Flow gas cell, M25, 4-20엄마
  2. 2108N5000H: Flow gas cell, M25, 수사슴
  3. 2108N5010N: Flow type + RGC, M25
  4. 2108N5010H: Flow type + RGC, M25 + 수사슴

3/4″NPT 스레드 (1)

  1. 2108N5100N: Flow gas cell, NPT, 4-20엄마
  2. 2108N5100H: Flow gas cell, NPT, 수사슴
  3. 2108N5110N: Flow type + RGC, NPT, high concentration range (0~100%vol CH₄)
  4. 2108N5110H: Flow type + RGC, NPT + 수사슴

2.4 Special XTC Marine & Multi-certified Models (44/46/48 시리즈)

  1. 2108N4400N / 시간: Diffusion, marine certification, M25
  2. 2108N4600N / 시간: Diffusion, UL/FM certified, M25
  3. 2108N4601N / 시간: Ethylene calibrated, 46-type diffusion
  4. 2108N4800N / 시간: Optima Plus XTC version, M25 diffusion
  5. 2108N5400/5600/5800 N/H: Corresponding flow-through versions (44/46/48 sampling models)
  6. 2108B Ethylene & Solvent Dedicated Models (for Optima X/Z sampling systems)

Diffusion type (4)

  1. 2108B4001N / 시간: Ethylene calibrated, M25 diffusion
  2. 2108B4101N / 시간: Ethylene calibrated, NPT diffusion

Flow-through sampling type (5, only for sampling systems)

  1. 2108B5001N / 시간: Ethylene flow cell, M25
  2. 2108B5101N / 시간: Ethylene flow cell, NPT
  3. 2108B2001N / 시간: Optima X fast-response sampling model (special gas cell)
  4. 2108B2051N: DNV marine certified version
  5. Full Series Spare Part Order Codes
  6. Optical Module: 2108D3001 (Methane), 2108D3034 (Ethylene)
  7. Remote Gas Cell (RGC): 2108B0240
  8. Flow-through Gas Cell Assembly: 2108B0282
  9. Dust Filter + Weather Shield: 2108B2337
  10. 단말기 & Junction Box: 2108B2360
  11. Quick Selection Table (for replacement)
장착 유형실Without RGC (기준)With RGC (Remote Test)
Wall-mounted DiffusionM252108N4000N / 시간2108N4010N / 시간
Wall-mounted Diffusion3/4″NPT2108N4100N / 시간2108N4110N / 시간
Pipeline SamplingM252108N5000N / 시간2108N5010N / 시간
Pipeline Sampling3/4″NPT2108N5100N / 시간2108N5110N / 시간
  1. 보충 설명
  2. N = 4-20mA analogue only; H = HART enabled. Do not mix loop types; 250Ω resistor is mandatory for HART loops.
  3. 2108N only detects hydrocarbons; 2108B is dedicated for ethylene, esters and alcohols. Neither can detect H₂, CO or NH₃.
  4. All models meet SIL2, ATEX/IECEx/FM certification; IP67 ingress protection.

 