위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

ABB Contactor A2X38.2-30-11-25 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

접촉기/

ABB Contactor A2X38.2-30-11-25

Model SegmentMeaning
A2XFormula series contactor with compact and cost-effective design
38Rated operating current of 38A (AC-3, 400다섯)
0.2Second-generation upgraded version (improved type)
303-pole main contacts, normally open configuration
11Auxiliary contact configuration: 1 평상시 열려 있음 + 1 평상시 닫혀 있음
13/25Coil voltage code: 13 = 380-400VAC, 25 = 220-240VAC
380V50/60HZRated coil voltage and frequency

  • 제품 세부정보

Basic Overview

ABB A2X38/A2X38.2 is a 3-pole AC contactor belonging to the ABB Formula series. A2X38 is an earlier model (discontinued), while A2X38.2 is its upgraded replacement (currently in production). It is mainly used for controlling three-phase squirrel-cage motors and other power loads, and is suitable for industrial automation and building electrical systems. Ordering Code: 2TFC200010R2511

  1. Model Code Explanation
Model SegmentMeaning
A2XFormula series contactor with compact and cost-effective design
38Rated operating current of 38A (AC-3, 400다섯)
0.2Second-generation upgraded version (improved type)
303-pole main contacts, normally open configuration
11Auxiliary contact configuration: 1 평상시 열려 있음 + 1 평상시 닫혀 있음
13/25Coil voltage code: 13 = 380-400VAC, 25 = 220-240VAC
380V50/60HZRated coil voltage and frequency

III. 핵심 기술 매개변수

  1. Electrical Parameters
매개변수 항목Remarks
Rated Operating Current (AC-3, 400다섯)38에이Controlled motor power: 18.5kW (50헤르츠) / 20hp (60헤르츠)
Rated Operating Current (AC-1, 400다섯)50에이Resistive load
정격 절연 전압 (Ui)690다섯IEC standard
정격 작동 전압 (Ue)400다섯 (AC-3), 690다섯 (AC-1)
Control Coil Voltage220-240VAC, 380-400VAC, 110VAC, 24VAC/DC, 등.Multiple options available
Coil Frequency50/60헤르츠Universal design, no adjustment required
Mechanical Service Life≥10 million operations
Electrical Service Life (AC-3)≥1 million operationsUnder rated load
  1. Physical Characteristics
매개변수 항목
Mounting MethodDIN rail mounting (35mm standard rail), slider design for one-hand disassembly
전체 치수 (mm)Approximately 85×105×55 (Width × Height × Depth)
무게Approximately 0.5kg
보호 등급IP20 (main body), IP00 for terminal blocks
주변 온도-25℃~+55℃ (operation), -40℃~+85℃ (storage)
오염도Degree 3
  1. Core Product Features
  2. Compact Design: Small size, 절약 30% of installation space, suitable for high-density distribution cabinets.
  3. High Efficiency and Reliability: Silver alloy contacts with arc resistance, low contact resistance and long service life.
  4. Easy Installation: Quick snap-on fixing, auxiliary contact modules can be directly clipped without tools.
  5. Safety Assurance: Flame-retardant engineering plastic housing complying with UL94 V0 standard, built-in surge suppression (일부 모델의 경우).
  6. Modular Expansion: Accessories such as auxiliary contacts (up to 4 units), mechanical interlocks, time-delay heads and surge suppressors can be added.
  7. 일반적인 애플리케이션 시나리오

Direct start and stop control of three-phase asynchronous motors (≤18.5kW/400V)

Electrical control of equipment such as fans, water pumps and compressors

Switch control of non-motor loads such as heating and lighting systems

Building electrical systems and industrial automation production lines

Replacement of old contactors for equipment upgrading and transformation

  1. Complete Model and Ordering Information
Complete Model코일 전압보조 연락처Ordering CodeStatus
A2X38-30-01 380V380VAC0 평상시 열려 있음 + 1 평상시 닫혀 있음10221469Discontinued
A2X38.2-30-11-13380-400VAC1 평상시 열려 있음 + 1 평상시 닫혀 있음10242059Currently in Production
A2X38.2-30-11-25220-240VAC1 평상시 열려 있음 + 1 평상시 닫혀 있음10242060Currently in Production
A2X38.2-30-00-13380-400VACNo auxiliary contacts10242058Currently in Production

Ⅶ. Installation and Wiring Specifications

설치 단계:

  1. Confirm that the installation environment meets the range of -25℃~+55℃, free from severe vibration and corrosive gases.
  2. Select a 35mm standard DIN rail and ensure the mounting surface is flat.
  3. Align the contactor’s snap with the rail, press down and slide to fix (one-hand operation).
  4. Cut off all power supplies before wiring, and use a multimeter to confirm no voltage exists.
  5. Main circuit wiring: L1/L2/L3 → input terminals, T1/T2/T3 → output terminals.
  6. Control circuit wiring: A1/A2 → coil power supply, 13/14 → normally open auxiliary contacts, 21/22 → normally closed auxiliary contacts.
  7. After wiring is completed, gently pull the wires to confirm they are connected firmly without loosening.

Terminal Block Specifications:

Main circuit: M6 bolts, suitable for copper core wires with cross-sectional area of 1.5-16mm²

Control circuit: M3.5 bolts, suitable for copper core wires with cross-sectional area of 0.5-2.5mm²

VIII. Replacement Models and Compatibility

Original ModelDirect Replacement ModelUpgraded Replacement SeriesRemarks
A2X38A2X38.2AF38 SeriesA2X38.2 is fully compatible with A2X38 in terms of installation dimensions and electrical performance
A2X38.2AF38-30-xx-xxAF SeriesAF series has advantages such as electronic coil (wide voltage range) and built-in surge suppression
AX38-30-xxAX SeriesEquivalent performance with slightly higher price
  1. Troubleshooting Guide
결함 현상가능한 원인솔루션
Contactor fails to pull inNo voltage/low voltage on coil; Coil burnout; Mechanical jammingCheck the control circuit; Measure coil resistance (approximately several hundred ohms under normal condition); Clean foreign objects and lubricate moving parts
Excessive noise after pull-inLow coil voltage; Oil stain/rust on iron core end face; Broken short-circuit ringAdjust control voltage to rated value; Clean iron core end face; Replace coil assembly
Contact overheating/ablationLoad overload; Poor contact of contacts; Loose wiringCheck load current; Polish contacts or replace them; Re-tighten terminal blocks
Auxiliary contact failureContact wear; Wiring errorReplace auxiliary contact module; Check wiring polarity
  1. Safety and Maintenance Precautions
  2. Power-off Operation: Cut off all power supplies before installation and maintenance, and hang theNo Switching Onsign.
  3. Regular Inspection: Conduct inspection every 6 months, including contact wear, terminal tightness and coil temperature.
  4. Contact Replacement: Replace the main contacts in time when the wear amount exceeds 1mm or the surface is severely ablated.
  5. 환경 요구 사항: Avoid use in humid and dusty environments; install a protective housing if necessary.
  6. Compatible Accessories: Only use auxiliary contacts, interlock devices and other accessories original or certified by ABB to ensure safety performance.

이전: