Danfoss ICAD Actuator 027H9075

⚠️Important Note: Part number 027H9075 corresponds to ICAD 600A (NOT ICAD 1200A). ICAD 1200A part-number: 027H9077, rated current 2.0 A. 027H9075: ICAD 600A, 24 VDC, rated 1.2 A, compatible with ICM20-32 027H9077: ICAD 1200A, 24 VDC, rated 2.0 A, compatible with ICM40-150 Model Code Breakdown Part‑number Model Power Supply Rated Current Compatible Valve Body 027H9075 ICAD 600A 24 VDC 1.2 A ICM‑20/25/32 027H9077 ICAD 1200A 24 VDC 2.0 A ICM‑40…ICM‑150 ICAD ...

  • 제품 세부정보

⚠️Important Note: Part number 027H9075 corresponds to ICAD 600A (NOT ICAD 1200A).

ICAD 1200A part-number: 027H9077, rated current 2.0 A.

027H9075: ICAD 600A, 24 VDC, rated 1.2 A, compatible with ICM20-32

027H9077: ICAD 1200A, 24 VDC, rated 2.0 A, compatible with ICM40-150

  1. 모델 코드 분석
Part‑number모델전원공급장치정격전류Compatible Valve Body
027H9075ICAD 600A24 VDC1.2 에이ICM‑20/25/32
027H9077ICAD 1200A24 VDC2.0 에이ICM‑40…ICM‑150

ICAD = Stepper-motor actuator for ICM motor-operated valves; Version A: built-in encoder + local LCD MMI keypad.

  1. 핵심 전기 매개변수 (ICAD-1200A 027H9077, 24 V 2.0 A)
사양
전원공급장치24 VDC isolated power supply; tolerance +10% /‑15% (21‑26.4 Vdc)
Max Current Consumption2.0 에이
Optional Fail‑Safe Power Supply24 VDC UPS / battery, 2.0 에이
Analogue Input0/4‑20 mA (200 Ω); 0/2‑10 V (10 kΩ)
Analogue Output0/4‑20 mA, 최대. load 250 Ω
디지털 입력Passive dry‑contact ON/OFF control
디지털 출력3‑channel NPN open‑collector outputs (valve fully‑open, fully‑closed, 경보); external 5‑24 VDC required
유입 방지IP67
주변 온도‑30 ℃~+50 ℃; 응축 / icing conditions prohibited
무게Approx. 1.9 kg
인터페이스2 × M12 circular connectors: 4‑pin power, 8‑pin signal
  1. 작동 원리

The ICAD uses a high-speed stepper motor with magnetic-coupling gear-free transmission to drive the ICM motor-operated valve. A built-in position encoder provides closed-loop valve-position feedback.

Supported functions:

  1. Continuous modulating via 4-20 mA / 2-10 V analogue signal.
  2. Digital dry-contact full-open / full-closed switching.
  3. Local LCD keypad for parameter setup, position indication and fault-code reading.

Magnetic-coupling design: No rigid mechanical connection between actuator and valve body; eliminates refrigerant-leakage risk.

  1. Pin Assignment: M12-8-pin Signal Connector
Wire Colour기능
1하얀색24 V DC Positive
2갈색24 V DC Negative
3검은색Alarm Output NPN‑
4갈색Full‑Open Output NPN‑
5빨간색Full‑Closed Output NPN‑
6주황색Signal GND
7노란색4‑20 mA Input (+)
8녹색2‑10 V Input / IN 디지털 입력 (+)

4-pin M12 power connector: Main 24 VDC supply; optional connection for fail-safe UPS power.

  1. Compatible Valve List

ICAD 600A (027H9075): ICM-20, ICM-25, ICM-32

ICAD 1200A (027H9077): ICM-40, 50, 65, 80, 100, 125, 150; also suitable for CVE pilot valves.

  1. 일반적인 애플리케이션 시나리오

Industrial refrigeration, ammonia refrigeration, CO₂ transcritical refrigeration units

Liquid-line electronic expansion regulation

Suction-pressure / temperature regulation

Hot-gas bypass & hot-gas defrost control

Large cold-storage plants, refrigeration compressor stations, food-processing freezing lines

Selection Pitfalls & 위험 경고

  1. Do not mix-up part-numbers: 027H9075 = 600A (1.2 에이); 027H9077 = 1200A (2.0 에이). Mechanical mounting interfaces are identical, but output torque differs drastically. Never drive large-size valves with ICAD-600A; this triggers A1 valve-mismatch alarm.
  2. Use isolated 24 VDC power supply only; 24 VAC is strictly forbidden. Calculate cable voltage drop; terminal voltage must not drop below 21 Vdc.
  3. Outputs are NPN transistors; external power supply is mandatory. Do NOT connect relay coils directly to actuator outputs.
  4. 작동 범위: -30 ℃ ~ +50 ℃. IP67 rating provides dustand splash-proof protection; permanent submersion is prohibited.
  5. Parameter i26 must be set to match the actual ICM valve type, otherwise alarm A1 will activate.
  6. Summary of Fault Codes
Alarm Code설명Troubleshooting Guidance
A1Valve type not configuredSelect correct ICM model in parameter i26
A2Travel error / 기계적 방해Check for valve jamming; verify magnetic‑coupling engagement
A3Supply‑voltage out‑of‑rangeCheck 24 V power supply and cable voltage drop
A4Fail‑safe supply faultUPS / backup‑battery power supply abnormality
  1. 교체 정보

ICAD600A / 1200A are mature active-range products, not obsolete. Legacy ICAD600 / 900 / 1200 can be directly replaced by A-series units; mechanical interfaces are fully compatible. Simply re-configure valve-type parameter i26 after swap-out.

Domestic alternative note: No drop-in magnetically-coupled replacement actuator available. Full valve-body + actuator assembly replacement is required for third-party retrofits.

Commissioning Procedure for 댄포스 ICAD 1200A (027H9077)

Applicable models: ICAD-600A / ICAD-1200A (A-series with LCD panel); 24 VDC supply; for ICM motor-operated valves.

⚠️027H9075 is ICAD-600A with reduced torque. Do NOT use it for ICM40 or larger valves.

Prerequisites: Valve mechanically fitted, magnetic-coupling correctly engaged, piping pressure-test completed. All wiring performed with power removed; M12 connectors fully tightened.

  1. Pre-power-on Wiring Check (필수적인)
  2. Confirm isolated 24 VDC power supply; 24 VAC forbidden. Power-supply rating ≥ 2.5 A.
  3. Secure M12-4-pin power and M12-8-pin signal connectors. Cables undamaged; cable shield single-ended earthed.
  4. NPN output circuit: External 24 V must be supplied from PLC side. Never connect relay coils directly to actuator outputs.
  5. Analogue-signal circuit: Total loop impedance for 4-20 mA input ≤ 200 Ω. 2-10 V input impedance ≥ 10 kΩ.
  6. Verify valve stem free from mechanical obstruction. Magnetic-coupling ring correctly fitted, no disengagement.
  7. Power-up & Initial Self-test
  8. Apply 24 VDC supply; LCD illuminates and actuator performs automatic self-test.
  9. If alarm codes appear after self-test: record alarm code first, do not reset immediately.
  10. ⚠️First-time power-on: No valve selected, alarm A1 is normal expected behaviour.
  11. Basic Parameter Setup via LCD Keypad
  12. Enter menu: Press and hold OK key for 3 seconds.
  13. Locate parameter i26 Valve type

ICAD-1200A (ICM40-150): Select actual valve size (ICM-40 /50 /65 /80 /100 /125 /150).

ICAD-600A (027H9075): Only ICM-20-25-32 permitted.

  1. Save setting. Actuator executes full-stroke auto-calibration.

Behaviour: Actuator travels automatically to full-closed position, then full-open. Do not cut power or apply external force during calibration.

  1. When calibration completes, alarm A1 clears. If A1 persists: double-check i26 setting; inspect magnetic-coupling for slipping.

Frequently-used Parameter Table

매개변수 번호.매개변수 이름설명Recommended Setting
i03 Control signalControl source0 = Local manual; 1 = 4‑20 mA; 2 = 2‑10 V; 3 = Digital DI switchMatch control‑system hardware
i04 Min signalMinimum control signal4 mA → 0 % position; 2 V → 0 % positionFactory default
i05 Max signalMaximum control signal20 mA → 100 % position; 10 V → 100 % positionFactory default
i26밸브 종류Must match physical ICM valve sizeSelect actual valve size on‑site
i40 Fail‑safe modeFail‑safe behaviour0 = No fail‑safe; 1 = Fail‑safe close; 2 = Fail‑safe openSet according to process requirements
i50 Output functionAnalogue output assignment0 = Valve‑position feedbackDefault 0
  1. Functional Tests

4.1 Local Manual Mode Test

  1. Set i03 = `0 Local manual`.
  2. Use up/down keys to adjust valve position from 0 %-100 %.
  3. Compare LCD indicated position with actual valve movement.

No valve movement: Check magnetic-coupling, 기계적 방해, i26 misconfiguration.

  1. Drive valve to 0 % (full-closed) and 100 % (full-open); confirm mechanical end-stops are reached.

4.2 External Analogue-signal Control Test (PLC / DCS)

  1. Set i03 to `1 (4-20 엄마)` or `2 (2-10 다섯)` as appropriate.
  2. Send minimum signal (4 mA / 2 V) from PLC; confirm valve moves to 0 % full-closed.
  3. Send maximum signal (20 mA / 10 V); confirm valve moves to 100 % full-open.
  4. Send intermediate 50 % reference; verify position tracking. Read analogue feedback output for cross-validation.

4.3 Digital-output Verification (NPN outputs)

Monitor three NPN outputs via PLC:

Full-open output: Conducts at 100 % valve position.

Full-closed output: Conducts at 0 % valve position.

Alarm output: Conducts when actuator fault is active.

NPN logic: Conducted = pin short-circuited to GND; non-conducted = high-impedance state.

  1. Alarm Acknowledgement
  2. Transient alarms: Navigate to `Acknowledge alarm` menu item, press OK to confirm.
  3. Persistent alarms: Alarm recurs immediately after reset. Resolve root-cause fault before acknowledgement; avoid repeated blind resetting.
  4. Post-commissioning Final Steps
  5. Restore i03 to the control-source required by the plant-control system.
  6. Exit parameter menu to return to main position-display screen.
  7. Retighten M12 connectors; implement cable-strain-relief protection.
  8. Document commissioning data: i26 valve setting, i40 fail-safe mode for project records.
  9. On-site Troubleshooting Summary
결함 증상문제 해결 단계
A1 Valve‑type not selected1. Verify i26 valve‑type setting; 2. Inspect magnetic‑coupling disengagement; 3. Confirm actuator‑valve mechanical mating
A2 Travel‑error mechanical fault1. Valve blocked by foreign objects; 2. Magnetic‑coupling slip; 3. Media icing; 4. Internal valve‑cartridge damage
A3 Power‑supply alarm1. Measure terminal voltage under load; voltage ≥ 21 V mandatory; 2. Inspect cable voltage drop / insufficient conductor cross‑section
Valve ignores control reference1. Wrong i03 source selection; 2. Broken signal wiring; 3. Faulty transmitter output; 4. Missing signal‑circuit common‑GND
Local manual works, external signal no responseConfirm i03 is NOT set to local manual; check wiring; verify signal‑loop impedance requirements
  1. Commissioning Hard-Rules (Forbidden Operations)
  2. ❌ Hot-plug M12 connectors: Risk of IO-board electrostatic burnout.
  3. ❌ Operate actuator without configuring i26 valve-type: Magnetic-coupling damage risk.
  4. ❌ Use ICAD-600A (027H9075) for ICM40-and-larger valves: Insufficient torque causes recurring A2 and magnetic-coupling destruction.
  5. ❌ Power-loss during auto-calibration: Loss of stroke-calibration data.
  6. ❌ 24 VAC power supply: Permanent actuator power-supply-circuit destruction.

일반적인 결함 & Troubleshooting for Danfoss ICAD-600A / ICAD-1200A (A-series LCD-type)

Applicable part-numbers: 027H9075 ICAD600A, 027H9077 ICAD1200A; 24 VDC supply, for ICM modulating valves.

Split into LCD-displayed alarm codes and non-alarming functional anomalies.

  1. Panel Alarm Codes (LCD Axx display)
Alarm Code오류 설명Root‑causes진단 & 교정 조치
A1 No valve selectedValve‑type not configured / detection failure1. i26 not set on first commissioning1. Enter parameter i26, select matching ICM valve size, run auto‑calibration
2. Magnetic‑coupling disengagement / poor mechanical mating2. Power‑off; check magnetic‑coupling ring seating; fasten actuator‑valve assembly
3. Improper mounting3. Alarm clears after calibration; recurring A1 indicates worn / slipping magnetic‑coupling
A2 Travel errorStroke over‑travel, 기계적 방해, torque deficiency1. Spool jamming, fouling, media icing1. Power‑off; manually verify free valve‑stem movement; remove ice / fouling
2. Magnetic‑coupling slip / fracture2. Inspect magnetic‑coupling for wear; replace coupling kit if required
3. ICAD‑600A driving oversized ICM40+ valves3. Torque matching rule: ICAD‑600A only for ICM20‑32; ICM40‑150 require ICAD‑1200A
4. External force applied during calibration4. Re‑select i26 and perform full‑stroke calibration; no external force allowed during calibration
A3 Supply voltageSupply voltage out‑of‑specification1. Power‑supply output outside 21‑26.4 VDC1. Measure M12 terminal voltage under load; must remain ≥ 21 VDC
2. Long‑cable / thin‑conductor voltage‑drop under load2. Increase cable cross‑section; shorten cable run; power‑supply rating ≥ 2.5 A
3. Insufficient power‑supply rating3. Use isolated DC power supply; ban 24 VAC
A4 Fail‑safe supplyFail‑safe UPS / backup‑supply abnormality1. i40 fail‑safe mode enabled but no backup‑supply connected1. Fail‑safe not required: set i40 = 0 to disable fail‑safe function
2. Backup‑supply wiring error, degraded battery2. When using fail‑safe: check backup‑24 V wiring and battery health
A5 Internal faultActuator internal PCB / motor hardware failureSurge‑voltage damage, ESD / static‑electricity damage1. Power‑cycle attempt; persistent alarm = hardware failure; replace complete actuator
A6 Signal input errorExternal reference signal out‑of‑valid range1. 4‑20 mA < 3 mA or > 22 mA1. Measure PLC output signal to confirm valid range
2. 2‑10 V < 1 V or > 11 V2. Check wiring and common‑GND; locate open‑circuit faults; verify i03 matches actual signal type
3. Broken wiring, faulty signal source
  1. Functional Abnormalities Without Active Alarms

Fault 1: Local manual works; external PLC reference has zero response

-징후: Valve responds 0-100 % from keypad; no reaction to 4-20 mA / 2-10 V remote signal, 알람 없음.

-Root-causes:

  1. `i03 Control signal` set to 0 (local manual), remote reference blocked.
  2. Signal-type parameter mismatch (hardware 4-20 mA but i03 set for 2-10 V).
  3. Missing common-GND between signal source and actuator; floating signal.
  4. Broken signal cable, faulty PLC analogue channel.

-교정 조치:

  1. Set i03 to correct source: 1 = 4-20 mA; 2 = 2-10 V.
  2. Connect signal negative to actuator signal-GND (pin 6).
  3. Measure signal directly at actuator-side terminals with multimeter to isolate PLC-side versus actuator-side faults.

Fault 2: Reversed valve-position tracking; 4 mA = full-open, 20 mA = full-closed

-Root-cause: Reversed signal-span configuration.

-교정 조치: Swap numerical values of i04 minimum-signal and i05 maximum-signal; alternatively invert output scaling inside PLC program.

Fault 3: Chattering / hunting; valve moves intermittently, position oscillates

-Root-causes:

  1. High internal valve-spool friction, fouling / scaling.
  2. Voltage sag under load from undersized power-supply / 배선.
  3. Electrical-noise interference; unshielded cables routed alongside power cables.

-교정 조치:

  1. Evaluate valve-body service; perform overhaul if fouled.
  2. Maintain terminal voltage ≥ 21 VDC under load; upgrade power-cable cross-section.
  3. Use shielded cable with single-end shield-earthing; separate signal wiring from power-cable routes.

Fault 4: No feedback from NPN digital outputs (full-open / full-closed / 경보)

-징후: LCD indicates full-open status but PLC receives no feedback signal.

-작동 원리: ICAD NPN open-collector outputs draw no voltage themselves; they only provide a switch-to-GND path.

-Root-causes:

  1. No external 24 V supply fed into PLC DI-input circuit.
  2. Mis-wiring; relay coil connected directly to output terminal.
  3. Incorrect output-threshold parameter settings.

-교정 조치:

  1. Supply external 24 V to PLC DI-channel; output pin pulls low to GND when active.
  2. Never drive relay coils directly; install intermediate relay.

Fault 5: No LCD illumination; actuator completely dead on power-up

-Root-causes:

  1. Zero 24 VDC supply; reversed power-supply polarity.
  2. Crimp-failure / bent pins inside M12 power connector.
  3. Surge-damage to internal power-supply circuit.

-교정 조치:

  1. Measure voltage and polarity at M12 power-connector terminals.
  2. Inspect connector pins for retraction / 손상.
  3. Correct supply voltage present yet no display: internal hardware failure, replace actuator.
  4. Frequent Human-induced Field Faults (선택 / 설치 / Commissioning-related)
  5. ICAD-600A (027H9075) driving ICM40-or-larger valves

Insufficient torque triggers repeated A2 travel-fault alarms and rapid magnetic-coupling wear. Must upgrade to ICAD-1200A (027H9077).

  1. Running unit without i26 valve-type configuration and auto-calibration

Incorrect stroke-data leads to incomplete valve-closure / incomplete opening; magnetic-coupling damage risk.

  1. Hot-swapping M12 circular connectors

ESD-stress may destroy IO-board electronics, triggering A5 internal-fault alarm.

  1. 24 VAC mains supply applied

Permanent destruction of actuator power-supply circuit, total unit loss.

  1. Power-interruption during auto-calibration

Calibration-stroke data lost; persistent A2 alarms; full recalibration required.

  1. Standardised General Troubleshooting Workflow
  2. Record LCD alarm-code; document operating conditions (온도, 중간, valve-position).
  3. 전원 끄기; inspect mechanical assembly: actuator mounting, magnetic-coupling, valve-spool jamming.
  4. Power-on; measure M12-terminal supply-voltage under load; confirm 21-26.4 VDC.
  5. Cross-check key parameters: i26 valve-type, i03 control-source, i40 fail-safe setting.
  6. Execute complete automatic valve-stroke calibration.
  7. Isolate fault-location by testing local manual mode:

✅ Local manual works: Fault lies in PLC, cabling or external control-system.

❌ Fault persists in local manual: Defect in actuator hardware, valve-body mechanics or magnetic-coupling.

Spare-part note: Magnetic-coupling ring is a consumable component and can be ordered separately; full-actuator replacement is not always required.