엘에스 (MEC) Thermal Overload Relay GTH-22/3

Legacy MEC series, 22AF 프레임, 3-요소 (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. 교체 모델: MT-32/3H ✅ Core Specifications Trip class: 클래스 10A (표준 모터 보호) 보조 접점: 1a1b (1아니요 + 1NC) 보호 기능: 초과 적재, 잠긴 로터, 3-phase phase-loss protection (advantage of 3-element design) 건설: bimetallic ...

  • 제품 세부정보

Legacy MEC series, 22AF 프레임, 3-요소 (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. 교체 모델: MT-32/3H

✅ 핵심사양

여행 클래스: 클래스 10A (표준 모터 보호)

보조 접점: 1a1b (1아니요 + 1NC)

보호 기능: 초과 적재, 잠긴 로터, 3-phase phase-loss protection (advantage of 3-element design)

건설: 바이메탈 스트립, 온도 보상, 트립 프리 메커니즘

정격절연전압 Ui: 690다섯

재설정 모드: 수동 재설정 (with TEST button)

독립 장착: Optional bracket AZ-22H

📋 Full Current Range List for GTH-22/3

모델 코드전류 범위 설정
GTH-22/3 0.160.1~0.16A
GTH-22/3 0.210.16~0.25A
GTH-22/3 0.330.25~0.4A
GTH-22/3 0.50.4~0.63A
GTH-22/3 0.80.63~1A
GTH-22/3 1.31~1.6A
GTH-22/3 2.11.6~2.5A
GTH-22/3 3.32.5~4A
GTH-22/3 54~6A
GTH-22/3 6.55~8A
GTH-22/3 7.56~9A
GTH-22/3 8.57~10A
GTH-22/3 119~13A
GTH-22/3 1512~18A
GTH-22/3 1916~22A

🔁 Replacement Information

Factory upgraded replacement: MT-32/3H (identical current ratings, direct replacement for GTH-22/3)

구별: GTH-22/2 is 2-element, without phase-loss protection, do not interchange

📌 Wiring Notes

주회로: 1/2/3 안에, 4/5/6 밖으로, connected in series between contactor outlet and motor

보조 접점: 95-96 (NC, wired into contactor coil circuit); 97-98 (아니요, for fault alarm)

현재 설정: Align dial pointer with motor full-load current (FLA)

  1. 터미널 정의 & Standard Start-Stop Wiring for GTH-22/3

터미널 표시:

주회로: 1, 3, 5 (incoming); 2, 4, 6 (outgoing), wired in series after contactor T1/T2/T3 and before motor

보조 접점:

95-96: NC 평상시 닫힘 (must be wired in contactor coil circuit; opens on overload to stop motor)

97-98: NO 상시 열림 (for alarm lamp / PLC fault input)

Front panel buttons: 시험 (simulated trip), 다시 놓기 (다시 놓기); GTH-22/3 is factory set to manual reset only, no auto-reset selector (different from some domestic thermal relays)

Standard Start-Stop Wiring Sequence (380V Motor)

  1. Circuit breaker → Contactor KM main contacts L1/L2/L3
  2. KM output T1/T2/T3 → GTH-22/3 terminals【1, 3, 5]
  3. GTH-22/3 terminals【2, 4, 6】→ Motor 3-phase terminals
  4. 제어 회로: Power supply → Stop button NC → 95 → 96 → Start button NO → KM coil A1/A2; KM auxiliary NO for latching
  5. 경보 회로: 97-98 in series with alarm lamp / 중간 릴레이, powered from control supply

플러그인 설치: Snap directly onto the bottom of GMC-9/12/18/22 contactors. DIN rail independent mounting requires bracket AZ-22H.

✅ Offline Test Method (전원 끄기)

Use multimeter continuity mode:

상태: 95-96 conducts; 97-98 열려 있는

테스트 버튼을 누르세요: 95-96 열립니다, 97-98 닫는다; release TEST, RESET button must be pressed to restore

  1. 문제 해결 표 (GTH-22/3 3-element phase-loss protected type)

예방법: GTH-22/3 is Class 10A. It protects against overload, locked rotor and phase loss ONLY. It cannot provide short-circuit protection. Short-circuit protection shall be implemented by fuse or circuit breaker.

징후근본 원인점검 & 치료
모터 과부하 / 잠긴 로터, thermal relay does not trip or protect1. Setting current too high2. Heating element burnt or internal solder joint open3. 메커니즘이 막혔습니다., bimetallic strip deformed4. Wrong frame size (current range oversized)1. Align setting dial with motor nameplate rated current (FLA; +5%~10% allowed for frequent start)2. Measure continuity of main circuit phases 1-2, 3-4, 5-6 멀티미터 포함; replace if open3. Activate TEST button to verify contact switching; replace if TEST fails4. Confirm model is GTH-22/3 (3-element with phase-loss protection), not GTH-22/2
Motor runs at normal load, nuisance tripping, trips immediately on startup1. Setting current too low2. Loose terminal connection, 과열 (terminal heat triggers premature bimetallic action)3. High cabinet ambient temperature, mounted too close to hot contactor4. Long motor starting time (높은 관성 부하)5. 3-phase supply phase loss (GTH-22/3 trips on phase loss)1. Recheck motor rated current and adjust setting upwards2. 전원 끄기, retighten all main circuit screws; inspect conductors for oxidation or discoloration3. Keep clear of heat sources, 환기를 개선하다; increase setting by 5% if ambient >40℃4. For long-start loads, consider Class20 thermal relay5. Measure 3-phase supply voltage, check for missing phase or broken cable
넘어진 후, RESET button cannot reset the relay1. Internal trip mechanism jammed or damaged2. Bimetallic strip not cooled down (2~5 min cooling required; hot state prevents reset)3. Auxiliary contacts welded together1. Wait for cooling then retry reset; replace if still unable to reset after cooling2. 측정하다 95-96 연속성; replace if remains open after reset
Control circuit dead, contactor cannot pull in1. Thermal relay tripped, 95-96 open2. Loose or broken wiring on 95/963. Auxiliary contacts eroded and high resistance1. Reset relay first, then test continuity of 95-962. Re-terminate control wiring; replace relay if contacts are heavily burnt
Random tripping after running for a period, restarts after cooling1. Hidden motor overload, bearing seizure, excessive load2. 소형 케이블, high voltage drop, terminal overheating3. Unbalanced 3-phase current1. Measure 3-phase running current with clamp meter, compare against setting value2. Inspect motor bearings, impeller and gearbox for binding3. If current imbalance >10%, investigate supply voltage and motor winding

III. Special Notes for GTH-22/3

  1. 3-요소 (/3) ≠ 2-element (/2):GTH-22/3 has phase-loss protection; GTH-22/2 does not, cannot substitute
  2. Phase-loss protection principle: If one phase is lost, the other two phases draw elevated current, the two corresponding heating elements heat and bend the bimetallic strips to trigger trip. It is thermal accumulation, not instantaneous voltage detection.
  3. Conductor sizing: Main circuit conductors must be sized for rated current; thin wiring causes false tripping from self-heating.
  4. Avoid frequent TEST operation, which accelerates internal mechanism wear.
  5. Replacement model MT-32/3H shares identical terminal assignment and wiring logic, 직접 교환.
  6. Quick On-site Troubleshooting Sequence
  7. Isolate power → Visual inspection: 화상 자국, burnt odor, overheated terminals
  8. Multimeter test: main circuit phase continuity, auxiliary contact normal state
  9. Activate TEST to confirm trip action and reset function
  10. 전원 켜기, clamp meter test 3-phase running current, cross-check setting
  11. Measure 3-phase voltage, check phase loss and imbalance
  12. Rule out motor and mechanical load faults before confirming thermal relay failure

Overload Protection Principle of Bimetallic Thermal 과부하 릴레이 (GTH-22/3 type)

핵심원리: Current thermal effect + bimetallic strip thermal deformation, simulating motor thermal characteristics for delayed overload protection. It cannot provide instantaneous short-circuit protection.

  1. 핵심 구성요소: 바이메탈 스트립

Two metal strips with different thermal expansion coefficients are clad together:

Active layer: higher expansion rate

Passive layer: lower expansion rate

At ambient temperature: 평평한, mechanism latched, 95-96 NC contact closed.

  1. Action Sequence on Overload
  2. Motor current flows through heating element, higher current generates more heat;
  3. Heat transfers to bimetallic strip;
  4. Differential expansion causes the strip to bend toward the low-expansion side;
  5. Sustained overcurrent accumulates bending displacement until trip threshold is reached;
  6. Mechanical latch releases: 95-96 NC 접점 열림, cutting contactor coil supply and stopping motor; 97-98 NO contact closes for fault signal.

특징: 반한시 특성

Larger overload current → faster heating and shorter trip time. Mild overload requires long duration to trip, matching motor allowable short-time overload. For Class10A: trips within 4~10s at 10× setting current.

  1. Additional Phase-loss Protection Principle of GTH-22/3 (3-요소)

Basic 2-element relays only monitor two phases.

GTH-22/3 has independent heating elements and bimetallic strips for all three phases:

When one supply phase is lost, the remaining two phases carry excess current, both heating elements bend and trigger accelerated trip.

Phase-loss protection is still thermal accumulation, not instantaneous voltage detection.

  1. Built-in Temperature Compensation (GTH series)

Internal compensation bimetallic strip offsets ambient temperature influence, preventing false tripping in hot cabinet or cold environment when current is normal.

  1. Reset Principle

넘어진 후, the bimetallic strip must cool and spring back to original shape.

GTH-22/3 is manual reset: after full cooling, press RESET to re-latch the mechanism and restore contact status.

  1. 주요 제한 사항 (Field Critical)

✅ Protected conditions: sustained overload, 잠긴 로터, 위상 손실, continuous excess current

Not protected: 단락 (short-circuit current is too high; the relay will burn before the strip bends. Short-circuit protection via breaker/fuse)

Not protected: 순간 돌입 전류 (starting current is bypassed by inverse time delay)

엘에스 (Legacy GTH + New MT Series) Thermal Relay ↔ Contactor Compatibility Chart

메모: Direct plug-in fit. Independent DIN rail mounting requires bracket (AZ / UZ series). /3 = 3-element with phase-loss protection; /2 = 2-element without phase-loss protection.

  1. Legacy GTH Series (including GTH-22/3)
Thermal Relay ModelDirect Plug-in Contactor비고
GTH-22/2, GTH-22/3GMC-9, GMC-12, GMC-18, GMC-22Max setting 22A; bracket AZ-22H for standalone mounting
GTH-40/2, GTH-40/3GMC-32, GMC-40Max setting 34A
GTH-85/2, GTH-85/3GMC-50, GMC-65, GMC-75, GMC-85Max setting 74A
GTH-100/2, GTH-100/3GMC-100, GMC-125Max setting 107A
GTH-150/2, GTH-150/3GMC-150Max setting 130A
GTH-220/2, GTH-220/3GMC-180, GMC-220Max setting 200A
GTH-400/2, GTH-400/3GMC-300, GMC-400Max setting 320A
  1. New MT Series (GTH Replacement, 메타솔)
Thermal Relay Model호환 가능한 접촉기Replaces LegacyStandalone Bracket
MT-32/3HMC-9b, MC-12b, MC-18b, MC-22b, MC-32a, MC-40aGTH-22/3, GTH-40/3UZ-32
MT-63/3HMC-50a, MC-65aGTH-85UZ-63
MT-95/3HMC-75a, MC-85a, MC-100aGTH-100UZ-95
MT-125/3HMC-125aGTH-150UZ-125
MT-200/3HMC-150a, MC-185a, MC-220aGTH-220UZ-200

III. Common Pitfalls for GTH-22/3

  1. GTH-22/3 only plugs into GMC-9/12/18/22, cannot directly fit GMC32 and above contactors.
  2. Current rating = adjustable range, not contactor rating. Contactor rated current must be ≥ motor rated current.
  3. 업그레이드 경로: GTH-22/3 → MT-32/3H. Same terminal definition and contact logic, but new contactors are MC series instead of old GMC.
  4. Bracket incompatibility: AZ-22H for old GTH; UZ-32 for new MT-32, cannot interchange.
  5. 빠른 선택 규칙

Motor rated current ≤22A: Old scheme GMC-9~~22 + GTH-22/3; New scheme MC-9b~~22b + MT-32/3H

Setting Current Adjustment Procedure for LS GTH-22/3 Thermal Relay

  1. Setting Principle

Setting Current = Motor Nameplate Full-Load Current (FLA)

Continuous-duty standard motor: set exactly to nameplate FLA

팬 / pump general loads: set to nameplate value

빈번한 시작, heavy-start or long acceleration loads: +5% ~ +10% of FLA, do not exceed 1.1×

Intermittent short-cycle motor: can reduce slightly, minimum ≥0.9× FLA

메모: The dial scale of GTH-22/3 is adjustable range, not fixed value. The value aligned by the pointer is the setpoint.

  1. 조정 단계 (GTH-22/3)
  2. Power off for safety (always power off before adjustment to avoid live terminal exposure)
  3. Open the front protective cover
  4. Rotate the central adjustment dial with indicator pointer
  5. Align pointer to target setting current
  6. Refit cover
  7. 전원 켜기, test run, verify 3-phase current with clamp meter

예:

Motor nameplate FLA = 5.2A → Select GTH-22/3 5 (4~6A range), align pointer to 5.2.

III. On-site Verification (비판적인)

조정 후, run motor at full load and measure 3-phase current with clamp meter:

Measured stable current ≈ setting value: 정상

Continuous running current far below setting: protection is loose, overload may not trip

Frequent tripping near rated current: check setting, 모터 과부하, hot terminals or high ambient temperature

  1. 일반적인 오해
  2. Set by contactor rated current: wrong, always reference motor nameplate
  3. Turn dial to maximum end: removes effective overload protection
  4. Increase setting heavily to accommodate starting inrush: inverse time characteristic is designed to withstand starting surge, no large over-set required
  5. Adjust setting to fix 3-phase imbalance: imbalance must be traced to supply, cable or motor winding, not thermal relay setting
  6. Temperature Compensation Impact

GTH has built-in temperature compensation. If cabinet ambient temperature is persistently above 40℃, relay trips easier at same current; 에이 5% upward setting is acceptable. If ambient <0℃, setting can be reduced slightly.

  1. Supplementary Notes for GTH-22/3

TEST button only simulates trip, it does not change the current setting value

Adjustment only changes overload trip threshold, phase-loss protection function remains active