DVP28SV11T2
인주: 델타 PLC 시리즈 코드
28: 총 I/O 포인트 28 전철기 (16DI+12DO)
SV: High-performance main unit of SV series; SV2 denotes second-generation hardware (suffix T2 = SV2)
11: DC24V 전원 공급 장치
티: Transistor output NPN (sink type)
2: Second-generation SV2 hardware version, supporting left-side high-speed expansion port
핵심 하드웨어 사양
| 목 | 매개변수 |
| 전원공급장치 | DC24V, reverse‑polarity protection, maximum inrush current 2.2A |
| DI 디지털 입력 | 16‑point DC24V, source/sink compatible |
| 디지털 출력 DO | 12‑point NPN transistor output |
| 프로그램 용량 | 30K 단계 (SV2 second generation), data register 12K Word |
| High‑speed Counter | 8‑channel; X0/X1/X4/X5 max. 200kHz; remaining X terminals 10kHz |
| 펄스 출력 | Y0‑Y3 max. 200kHz (4‑axis independent pulse output); supports linear/circular interpolation |
| 의사소통 | COM1: Mini‑DIN8 RS232; COM2: RS485; Modbus RTU/ASCII master/slave |
| 확장 기능 | Right‑side for standard S‑series modules; dedicated left‑side high‑speed expansion port; maximum total I/O 512 전철기 |
| 설치 | DIN35 레일 장착; Dimensions W70 × H90 × D109.4 mm |
| 작동 온도 | 0‑55℃ |
소프트웨어
프로그래밍 소프트웨어: WPLSoft / ISP소프트, with COMMGR communication manager
Supported features: 4-레벨 비밀번호 보호, program backup, battery-free real-time clock, 16-channel external interrupt.
일반적인 응용 분야
서보 포지셔닝, XY manipulators, 라벨러, 포장 기계, 절단 장비, 섬유 기계, and other equipment requiring multi-axis pulse motion control.
Distinction of Models in the Same Series
DVP28SV11T: First-generation SV, 16K-step program, without left-side high-speed expansion port
DVP28SV11T2: SV2 second-generation, 30K-step program, with left-side high-speed expansion port
DVP28SV11R2: Relay-output version
DVP28SV11S2: PNP transistor-output version
Second-hand Inspection Checklist
- 전원 켜기 테스트: POWER indicator steady ON; check status of RUN/ERROR/BAT-LOW indicators; low-battery alarm.
- I/O test: Force ON/OFF to verify all input and output points.
- High-speed pulse test: Test Y0-Y3 pulse output up to 200kHz; verify high-speed counter reception on X0/X1.
- 통신 테스트: Program upload/download via RS232 and RS485; Modbus read-write test.
- Expansion port inspection: Check left-side and right-side expansion connectors for oxidation and intact pins.
Alternative References
델타 native alternatives: DVP28SV11S2 (PNP); DVP28SE211T (SE2 new generation, with Ethernet port)
국내 대안: Inovance H2U-1616MT-XP (200kHz pulse, 4-중심선)
Programming Software for Delta DVP28SV11T2 (SV2 Series)
This unit belongs to second-generation DVP-SV2 PLC; two official software packages are supported:
- ISP소프트 (새로운 프로젝트에 권장)
최신 버전: V3.24 and above
Mandatory companion: COMMGR communication manager, handles serial/USB communication connection
Supported IEC61131-3 languages: LD (래더 다이어그램), 성 (구조화된 텍스트), FBD (기능 블록 다이어그램), SFC (Sequential Function Chart); full SV2 motion instructions, interpolation, high-speed positioning; modular POU programming, simulation, 온라인 모니터링, 펌웨어 업그레이드.
OS: Win7/10/11 (64-조금)
- WPLSoft (Legacy software for existing project maintenance)
버전: V2.52, traditional Delta DVP programming software, mainly supports ladder diagram and instruction list, no Structured Text support
Suitable for reading backup programs from legacy equipment and simple logic; inferior to ISPSoft for complex motion-control functions.
⚠️ Note: DIADesigner does NOT support DVP28SV11T2. DIADesigner is for high-end SV3, AS/AH series PLCs.
Programming Cables
For the front-panel Mini-DIN8 RS232 port of DVP28SV11T2:
- Delta original USB-DVP programming cable (USB to Mini-DIN8)
- RS232-to-Mini-DIN8 cable is also acceptable; program download is available via COM2 RS485 as well.
Software Selection Guidance
서보 포지셔닝, 원형 보간, 복잡한 프로세스: ISP소프트 + COMMGR
Legacy equipment with WPLSoft-format project files: Maintain with WPLSoft.
Communication Protocols for Delta DVP28SV11T2 (SV2)
On-board hardware: COM1-RS232 (Mini-DIN8), COM2-RS485 terminal block. No native Ethernet or CANopen; fieldbus functions require left-side expansion modules.
Protocols Supported by On-board Serial Ports
- 모드버스 RTU / Modbus ASCII (가장 널리 사용됨)
Available on COM1(RS232) and COM2(RS485); supports both Master and Slave modes
Max baud rate 115200bps; configurable data bits, 둥가, 정지 비트
응용: Connect to HMI, 인버터, 서보, meters and third-party Modbus devices.
- Delta proprietary protocol (PLCLink)
Data exchange among multiple DVP-SV2/SA2/SS2 PLCs via RS485 networking.
- Program download protocol
COM1 RS232: ISPSoft/WPLSoft program upload/download, 온라인 모니터링
Program download and monitoring are also supported over COM2 RS485.
Factory default serial parameters: 9600, 7, 이자형, 1 (9600bps, 7-data-bit, even parity, 1 정지 비트)
Additional Fieldbus Protocols via Left-side High-speed Expansion Modules (Hardware add-on only, not built-in)
Use the dedicated left-side high-speed slot with corresponding communication modules:
DVPCOPM-SL: CANopen master module, CANopen DS301 compliant, for CANopen servo/drive connection
DVPNET-SL: 이더넷 모듈, supports Modbus-TCP (Master/Slave)
DVPDP-SL: Profibus-DP slave module
DVPDNM-SL: DeviceNet module
Port Function Summary
| 포트 | 하드웨어 | 기능 |
| COM1 | RS232 Mini‑DIN8 | Program download, Modbus RTU/ASCII Slave; cannot act as Modbus Master |
| COM2 | RS485 terminal block | Modbus Master/Slave, PLCLink, program download |
| Left‑side Expansion Port | Dedicated high‑speed slot | Optional CANopen, 이더넷, Profibus‑DP and other bus modules |
일반적인 함정
- DVP28SV11T2 has no built-in Ethernet or CAN interface. Expansion modules must be purchased separately.
- COM1(RS232) can only operate as Modbus Slave. Modbus Master function is exclusively for COM2(RS485).
- PLCLink works only between Delta DVP-series PLCs; incompatible with third-party hardware.
Complete Installation Guide for Delta DVP28SV11T2 (ISP소프트 + COMMGR)
ISPSoft is preferred for DVP28SV11T2(SV2). COMMGR is mandatory for communication; program download will fail without it.
Supported OS: Win10 / Win11 64-bit. Download installation packages from Delta Industrial Automation official website.
설치 전 준비
- Uninstall old versions of ISPSoft and COMMGR; mixed versions cause communication failures.
- Right-click installer → Run as administrator (critical for Win11; avoids installation errors and driver failure).
- Temporarily disable antivirus / Windows Defender to prevent component interception.
- Ensure .NET Framework4.5 is installed (included in modern Windows; download from Microsoft if missing).
Two Installation Procedures
Method A: COMMGR bundled inside ISPSoft installer (추천)
- Unzip ISPSoft archive and run Setup.exe.
- Select Chinese language, follow on-screen prompts; keep the [COMMGR] component checked, do not uncheck it.
- Customize install path; avoid Chinese-character directories on C drive (예를 들어. 디:\Delta\ISPSoft).
- Complete installation and reboot PC as prompted.
⚠️ If COMMGR was unchecked during setup, download and install COMMGR separately.
Method B: Separate installation
- Install COMMGR (Communication Manager) 첫 번째.
- Install ISPSoft programming software afterwards.
Post-installation Configuration (Program editing ≠ download capability; COMMGR channel setup is required)
- Close ISPSoft first, launch COMMGR from start menu (icon appears in system tray).
- Click [추가하다]
Driver name: English characters only, 예를 들어. DVP_SV2 (No Chinese characters or spaces)
Communication type:
Delta USB programming cable: Select USB
USB-to-RS232/485 adapter: Select Serial Port, confirm COM number in Windows Device Manager.
- Parameters matching PLC factory defaults: 9600, 7, 이자형, 1, 1번 역
- Confirm configuration, select this channel and click [시작]. Status START means channel is ready.
- Open ISPSoft, create new project, select model: DVP-SV2 → DVP28SV11T2
- 메뉴 [도구] → [통신 설정], select the pre-configured COMMGR channel to go online, upload or download programs.
Alternative Legacy Software WPLSoft (For maintenance-only)
Not recommended for new projects; lacks ST language and advanced motion interpolation instructions.
- Install WPLSoft V2.53, run as administrator.
- WPLSoft also relies on COMMGR; communication configuration follows identical steps above.
일반적인 문제 해결
- Gray online button: COMMGR is not running, channel status is not START.
- COM port not found: Install driver for USB-to-serial chip (CH340 / FT232); no yellow exclamation marks in Device Manager.
- Win11 installation errors: Always run as administrator, avoid Chinese-character install paths, disable security software temporarily.
- Communication errors: Double-check baud rate, parity setting and PLC station number. SV2 factory setting: 9600-7-E-1
Hint for New DVP28SV11T2 Project
ISPSoft New Project → Series DVP-SV2 → select DVP28SV11T2. The software automatically applies hardware parameters: 30K-step program capacity, 4-축 200kHz 펄스 출력.
접촉기,회로 차단기,태양광 인버터,전기 계량기,감지기,인코더,PLC























NH42-63-318x560.png)