IFM AL1304 분산 I/O 모듈 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

IFM AL1304 분산 I/O 모듈 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

전기 같은/

IFM AL1304 분산 I/O 모듈

Basic Product Positioning Full Model Name: AL1304 DataLine IO-Link Master DL PN 4P IP67 Brand: IFM (독일) Core Profile: 4-port Class A IO-Link master with PROFINET bus + independent dual Ethernet ports for IoT JSON/MQTT. It is a field distributed I/O module with IP67 rating, allowing direct on-machine outdoor installation without control cabinets. 모델 코드 ...

  • 제품 세부정보

기본 제품 포지셔닝

Full Model Name: AL1304 DataLine IO-Link Master DL PN 4P IP67

상표: IFM (독일)

Core Profile: 4-port Class A IO-Link master with PROFINET bus + independent dual Ethernet ports for IoT JSON/MQTT. It is a field distributed I/O module with IP67 rating, allowing direct on-machine outdoor installation without control cabinets.

모델 코드 분석

알: DataLine series field IO-Link master

13: PROFINET bus version

04: 4-channel Class A IO-Link ports

No suffix marking = Standard industrial orange IP67 housing

  1. Core Hardware Port Layout (8 × M12 Connectors)

Port definitions from top to bottom:

  1. X1: PROFINET Ethernet Port (M12 D-coded, 100 Mbps) → Connect to PLC control network
  2. X2: Independent IoT Ethernet Port (M12 D-coded) → Isolated IT/cloud network for uploading sensor data via JSON/MQTT
  3. X3~X6: 4 × Class A IO-Link Ports (M12 5-pin A-coded)

Each port integrates 2DI + 1~하다, with a total of 8DI / 4DO for the unit

  1. X7: 전원 입력 (M12 A-coded, 24 VDC)
  2. X8: Ethernet Daisy-Chain Output (M12 D-coded) → For bus daisy-chain expansion
  3. 주요 전기 사양

3.1 전원공급장치

작동 전압: 18~30 V DC (기준 24 V industrial DC)

Max Total Power Consumption: ≤6 W

Power Connector: M12 A-coded, with reverse polarity and short-circuit protection

3.2 IO-Link Channels (4 × Class A)

IO-Link Version: V1.1, Conformance Class C; IRT를 지원합니다, MRP, CiR and S2 redundancy

Digital Inputs per Port: 2 에서 (PNP/NPN 호환)

High Level: 11~30 V DC; Low Level: 0~5 V DC

Digital Output per Port: 1 ~하다 (PNP)

Max Load per Channel: 300 엄마, with short-circuit/overload protection

채널당 최대 전류: 0.3 에이; total output current limiting for four channels

3.3 Communication Performance

PROFINET Control Network (X1/X8)

속도: 100베이스-TX, 100 Mbps

Supported Topologies: Line topology, MRP 링 중복

호환성: 지멘스 S7-1200, S7-1500, CPU 315, CPU 400 and other PROFINET controllers

Supporting File: GSDML file available for download with official manuals

Independent IoT Ethernet (X2, Hardware-Isolated Network)

Protocols: TCP/IP JSON, MQTT

속도: 10/100 Mbps 자동 협상

핵심 이점: Hardware isolation between control network and IT cloud network, preventing external network intrusion into PLC control systems. Raw sensor data is uploaded directly to MES/cloud platforms without occupying PLC cycle time.

3.4 환경 & 기계 사양

보호 등급: IP67 (waterproof and dustproof, direct mounting on machine bodies)

작동 온도: -25℃ ~ +60℃

보관 온도: -40℃ ~ +80℃

하우징 재질: Polyamide PA, vibration-resistant and oil-resistant

Vibration Standards: 안에 60068-2-6, 안에 60068-2-27

설치: 2 through holes for M4 screws; wall-mounted or machine-mounted

  1. 핵심 기능 하이라이트
  2. Dual Isolated Network Architecture

PROFINET is dedicated to PLC motion and logic control; the independent IoT port separately uploads diagnostic data such as temperature, counters and vibration without mutual interference, complying with factory network security standards.

  1. 4 IO-Link Channels with Integrated DI/DO

Each channel can directly connect IO-Link sensors (압력, flow, 광전, 인코더, temperature modules) while providing built-in digital inputs and outputs, eliminating the need for extra terminal blocks.

  1. Complete Advanced PROFINET Features

IRT real-time synchronization, MRP 링 중복, CiR online configuration modification, SNMP network diagnostics, suitable for high-speed production lines and robot workstations.

  1. Free Configuration Software moneo|configure free

Automatically scans all IO-Link devices, one-click import of IODD files, batch parameter downloading, online diagnostics and fault alarms.

  1. 종합진단

Real-time upload of port short-circuit, cable breakage, device loss, undervoltage and communication timeout signals to PLC; fault JSON logs are simultaneously pushed via the IoT port.

  1. 표준 포장 & 옵션 액세서리

Standard Delivery

1 × AL1304 Main Unit

Printed Quick Installation Manual

Separately Orderable Accessories

M12 D-coded PROFINET cables (똑바로 / angled)

M12 A-coded power cables

Port dust protection caps

Daisy-chain Ethernet cables

  1. Series Selection Comparison (AL13xx PROFINET Series)
모델IO-Link PortsIoT Port보호 등급일반적인 애플리케이션 시나리오
AL13044 × Class AIndependent Dual Ethernet PortsIP67Small workstations, standalone machines, applications with ≤4 sensors
AL13068 × Class AIndependent Dual Ethernet PortsIP67Multi-sensor stations, distributed data acquisition on production lines
AL13078 × Class AIndependent Dual Ethernet PortsIP69K음식 & pharmaceutical environments with high-pressure washdown
  1. Typical Application Industries

Automotive welding & 코팅 라인, machine tool centers

Packaging production lines, logistics sorting lines

사출 성형, 고무 & plastic equipment, small custom automation machines

Equipment cloud data upload, MES data acquisition projects

Complete Installation Manual for IFM AL1304 IO-Link Master

문서정보

모델: AL1304 (DL PN 4P IP67)

버전: Original Standard Installation & 운영 매뉴얼

애플리케이션: On-site wall/machine-mounted IO-Link master with isolated PROFINET + IoT dual networks

보호 등급: IP67, direct outdoor/machine mounting without control cabinets

Table of Contents

  1. Mandatory Safety Requirements
  2. Pre-Installation Inspection & 도구 목록
  3. 기계적 설치 사양 (치수, 고정, 토크, 접지)
  4. Port Definition & M12 Connector Wiring Specifications
  5. Step-by-Step Electrical Wiring Procedures
  6. 케이블링 & EMC Anti-Interference Specifications
  7. Pre-Power-On Inspection Checklist
  8. Power-On LED Indicator Status Guide
  9. Unit Disassembly Specifications
  10. Installation Prohibitions & Fault Prevention
  11. List of Original Optional Accessories

1 Mandatory Safety Requirements (Must Be Followed)

⚠️ Critical Hazard Warnings

  1. Cut off all 24 V power before any installation, wiring removal or disassembly. Hot plugging/unplugging of M12 connectors is strictly prohibited, as it will burn port driver chips.
  2. The power supply is SELV/PELV safety extra-low 24 VDC; connection to 220 VAC or 380 VAC mains power is forbidden.
  3. The metal mounting base must be reliably earthed to prevent electrostatic discharge and surge damage to Ethernet and IO-Link channels.
  4. For food/washdown applications, avoid direct high-pressure water spraying onto connector roots. Select AL1307 (IP69K) for long-term washdown exposure.
  5. Ambient Temperature Range: Operating -25℃ ~ +60℃; Installation temperature ≥0℃ to avoid seal hardening and water ingress at low temperatures.

2 Pre-Installation Inspection & 도구 목록

2.1 언박싱 검사

  1. Check the AL1304 unit for cracks, dents and deformed connectors; confirm FKM sealing rings are intact and undamaged.
  2. Standard contents: Main unit, printed quick installation manual. Cables and dust caps are not included and must be ordered separately.
  3. Verify model marking AL1304, 확인하다 4 Class A IO-Link channels and dual D-coded Ethernet ports.

2.2 필수 도구

토크 렌치 (0.5~3 N·m), M5 bolts, flat washers/spring washers

14 mm open-end wrench (for tightening M12 connectors)

멀티미터 (24 V continuity and short-circuit testing)

Cable ties, cable clamps, shielded industrial Ethernet cables

3 기계적 설치 사양

3.1 Overall Unit Dimensions

152 mm (시간) × 59.3 mm (여) × 38.4 mm (디)

3.2 장착 방법: 벽 / Machine Body Mount (No DIN Rail Clips)

  1. Two mounting through holes on the top and bottom rear of the unit; secure with 2 × M5 bolts + flat washers.
  2. Standard tightening torque: 1.8 N·m. Excessive torque is forbidden to avoid housing deformation and seal failure.
  3. Mounting Surface Requirements: Flat metal plate free of burrs and oil contamination. Max tilt angle ≤90°. Do not mount upside down with connectors facing upward (risk of water pooling ingress).
  4. 접지 요구 사항: The two M5 mounting bolts also serve as unit earthing terminals; the metal base shall connect to protective earth PE. For non-metallic mounting plates, run a separate earthing wire to the PE busbar.

3.3 Mounting Clearance Requirements

Reserve ≥30 mm vertical clearance above and below the unit for heat dissipation; ≥20 mm side clearance to prevent heat accumulation.

Keep a minimum distance of 150 mm from inverter and servo power cables to reduce electromagnetic interference.

4 Full Unit Port Definition (8 M12 Connectors from Top to Bottom)

Port No.커넥터 유형Coding기능 설명
X1M12 4-pin EthernetD-codedPROFINET control network (connect to PLC)
X2M12 4-pin EthernetD-codedIndependent isolated IoT network (MQTT/JSON cloud/MES upload)
X3/X4/X5/X6M12 5-pin IO-LinkA-coded4 Class A IO-Link channels, each with integrated 2DI+1DO
X7M12 5-pin PowerA-coded24 VDC power input
X8M12 4-pin EthernetD-codedPROFINET daisy-chain output

4.1 General M12 Connector Tightening Torque (Factory Standard)

Hand-tight basic torque: 0.6 N·m

Severe vibration/oil environments: 1.2~1.5 N·m (tightened with 14 mm wrench)

Do not power on if sealing rings are missing; IP67 protection will be lost.

5 Step-by-Step Electrical Wiring Procedures

5.1 X7 Power Port (M12 A 5-pin Standard IO-Link Pinout)

핀 정의 (viewed from plug front):

1: 갈색 +24 DC에서

2: Black DI1 (shared digital input for channels)

3: 파란색 0 V GND

4: White DI2 (shared digital input for channels)

5: Grey PNP DO output (최대 300 엄마)

Power supply range: 18~30 VDC, total power consumption ≤6 W. Power supply built-in reverse polarity, short-circuit and overcurrent protection.

5.2 IO-Link Ports X3~X6 (Independent 5-pin A-coded per Channel)

Each channel provides independent power supply, IO-Link communication and integrated DI/DO without external terminals:

Pin1: 24 V L+ sensor supply

Pin2: 에서 (PNP/NPN compatible input)

Pin3: 0 V L-

Pin4: IO-Link communication line (C/Q)

Pin5: PNP DO output, 300 mA per channel current limiting

5.3 D-coded 4-pin Industrial Ethernet Cables for X1/X2/X8

Pin1: TD+ Transmit +

Pin2: TDTransmit –

Pin3: RD+ Receive +

Pin4: RDReceive –

Shield layers shall be earthed at both ends to suppress motor interference. X2 IoT network and X1 control network are hardware-isolated with no intercommunication.

6 케이블링 & EMC Anti-Interference Specifications

  1. Separate power cables (servo, 인버터) and IO-Link/Ethernet cables into different cable trays with a minimum spacing of 150 mm. Use metal shielded trays for separation if routing together is unavoidable.
  2. Minimum bending radius of M12 cables ≥ 5 × cable outer diameter; sharp bending and squeezing at connector roots are prohibited.
  3. Cable Length Limits:

IO-Link cable: ≤20 m

PROFINET industrial Ethernet cable: ≤100 m (100 Mbps)

  1. All unused spare ports must be fitted with original dust and waterproof caps, otherwise IP rating will be invalidated.
  2. The shield of all shielded Ethernet cables shall be 360° crimped onto the metal connector shell with single-point earthing.

7 Mandatory Full Pre-Power-On Inspection Checklist

  1. 기계적 고정: Two M5 bolts tightened to 1.8 N·m; unit fixed without wobble.
  2. Earthing Test: Multimeter to verify continuity between mounting base and PE protective earth; earthing resistance <4 Ω.
  3. Cable Tightness: All M12 connectors tightened to 0.6~1.5 N·m with no looseness.
  4. Short-Circuit Test: Disconnect power supply, use multimeter to confirm no short-circuit between X7 Pin1 and Pin3, and no short-circuit to ground on Pin1/Pin3 of all IO-Link channels.
  5. Network Segregation: X1 connected to PLC control network, X2 to independent IT/MES network; connecting both ports to the same switch is forbidden.
  6. All spare ports fitted with dust caps.

8 Power-On LED Indicator Status Guide

Status LEDs integrated on the front panel for rapid fault diagnosis after power-up:

  1. PWR Power LED (Solid Green): 일반 전원 공급 장치; Off = No power / 단락; Flashing = Undervoltage <18 V
  2. NET1 (X1 PROFINET):

Solid On: Link established; 섬광: Data exchange; 끄다: Cable break / No connected device

  1. NET2 (X2 IoT Network):

Solid On: Stable IT network link; 섬광: MQTT/JSON data uploading

  1. CH1~CH4 Channel LEDs (X3~X6):

Solid Green: Normal IO-Link device communication

Flashing Red: Port short-circuit, cable breakage or device loss

끄다: No device connected to the channel

9 Unit Disassembly Specifications

  1. First cut off the 24 V main power supply and wait 30 seconds for discharge.
  2. Loosen all M12 connectors with a 14 mm wrench; do not pull cables forcibly.
  3. Loosen the two rear M5 mounting bolts and remove the unit.
  4. Install port dust caps immediately after disassembly to protect sealing rings.

10 Installation Prohibitions & Fault Prevention

❌ Forbidden: Mount unit upside down with connectors facing downward (water pooling into sockets)

❌ Forbidden: Tighten fixing bolts above 1.8 N·m; housing cracking and water leakage will occur

❌ Forbidden: Hot plug/unplug M12 connectors; communication chips will burn out

❌ Forbidden: Parallel close routing of power cables and IO cables, causing communication packet loss

❌ Forbidden: Connect X1 and X2 ports to the same switch, breaking network isolation security

❌ Forbidden: Long-term outdoor operation without dust caps; dust will cause port short-circuits

Common Installation Fault Prevention:

  1. Frequent communication disconnections: Check connector torque, shield earthing and separation distance from power cables
  2. Persistent port short-circuit alarms: Verify IO-Link sensor wiring and ensure load ≤300 mA
  3. PROFINET device not detected: Check GSDML file, IP address, device name and D-coded Ethernet cable
  4. Failed IoT data upload: X2 uses an independent network segment with no IP conflict with the PLC network

11 Original Optional Accessories (Ordered Separately)

  1. M12 D-coded straight/angled PROFINET Ethernet cables (2 중 / 5 중 / 10 중)
  2. M12 A-coded 5-pin power cables
  3. Standard 4/5-core IO-Link sensor cables
  4. 먼지 & waterproof port caps (single-channel / full set for unit)
  5. Stainless steel mounting brackets (for high-vibration equipment)

번역 노트

  1. Industrial automation professional terms adopt international standard industry expressions (IO-링크, 프로피넷, PNP/DI/DO, MRP, IRT, CiR, MQTT, JSON, 셀프/PELV, EMC, GSDML, IODD, DIN 레일, PE earth etc.)
  2. 토크, 온도, 길이, current units retain international metric symbols consistent with IFM official English datasheets
  3. M12 connector coding (A-coded / D-coded), pinout labels and protection class IP67/IP69K follow original factory standard terminology
  4. Tables, warning symbols, prohibited marks and document structure fully match the original Chinese text layout for direct use in overseas technical manuals

이전:

답장을 남겨주세요

메시지를 남겨주세요