1.Basic Model Information
주문번호: 2744429
전체 모델: PSM-ME-RS485/RS485-P
제품 유형: RS485 Isolated Repeater (Bus Signal Amplifier / Segment Isolator)
기원: 독일
설치: Standard DIN 35 mm rail mounting
Housing Dimensions: 여 22.5 mm × H 99 mm × D 114.5 mm, IP20 보호
하우징 재질: Flame-retardant PA6.6, Green RAL6021
- 핵심 기능
- 3-way Galvanic Isolation: Power Side ↔ Segment A Bus ↔ Segment B Bus, completely eliminating ground loop interference, surge and common-mode noise.
- Bus Segmentation & Capacity Expansion: 맥스. 32 nodes per single RS485 segment; each segment supports independent 32 nodes after repeater connection. 최대 9 units cascaded at low baud rates.
- Extended Transmission Distance: 기준 1200 중 (twisted pair; lower baud rate corresponds to longer transmission distance).
- Compatible Bus Protocols: 모드버스 RTU, 프로피버스-DP, general 2-wire RS485 half-duplex bus.
- Automatic Direction Control: No external RTS/CTS required; hardware auto transmit/receive switching.
- 전기 사양
3.1 전원공급장치
정격전압: 24 V AC/DC ±20%
일반적인 전력 소비: 90 mA @ 24 VDC, 최대. 100 엄마
Isolation Withstand Voltage: ≥2.5 kV AC between power supply and buses, and between two bus segments.
3.2 통신 인터페이스 (Dual 2-wire RS485 Half-duplex)
Baud Rate Range: Full coverage from 4.8 kbps로 1500 kbps
4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 187.5 / 375 / 500 / 1500 kbps
Frame Format: Switchable 10-bit / 11-조금, NRZ UART encoding
Signal Delay: Bit delay < 200 ns, signal distortion < 1.5%
Termination Resistor: 내장 220 오 + 390 Ω switchable via DIP switch
터미널 블록: Screw pluggable terminals, cable cross-section 0.2~2.5 mm² (AWG24~14)
3.3 환경 매개변수
작동 온도: -40 ℃ ~ +70 ℃ (Wide-temperature industrial grade)
저장 / 운송 온도: -40 ℃ ~ +85 ℃
습기: 10%~95% 비응결, 최대. 고도 5000 중
진동 / 충격 저항: 5 g vibration, 25 g shock, compliant with IEC industrial standards.
- 인증 & 승인
General Certifications: CE, UL, cUL, RoHS 규제, EAC, DNV GL Marine Approval
Explosion Protection: ATEX II 3G Ex ec IIC T4 Gc (Suitable for hazardous areas)
EMC: Full set of EN61000 anti-interference standards (ESD, 급등하다, RF radiation)
- 일반적인 애플리케이션 시나리오
- Multi-instrument Modbus networking in factories; segmented isolation when node quantity exceeds 32.
- Long-distance cross-workshop PROFIBUS-DP wiring to eliminate ground potential difference.
- Mixed high/low voltage control cabinets; isolate RS485 bus from inverter interference.
- Signal extension for field bus in chemical & oil/gas hazardous areas.
- 빌딩 자동화, long-distance remote PLC RS485 acquisition sub-stations.
- 대체 모델 참조
Cost-effective non-explosion-proof variant of same series: PSM-ME-RS485/RS485 (without ATEX, different order number)
Fiber-optic isolated version: PSM-ME-RS485/FO, alternative for long-distance heavy electromagnetic interference scenarios.
- Key Operation Guidelines
- Termination resistors must be enabled via DIP switches at both physical ends of each bus segment respectively.
- Use shielded twisted pair for bus wiring; single-point grounding for shield layer.
- Maximum cascade limit: 최대 9 units at 4.8~93.75 kbps; reduce cascade quantity for high baud rates.
- Three independent isolation channels allow connection to devices with different ground potentials to avoid communication dropouts.
Official Installation Manual for 피닉스 연락하다 2744429 (PSM-ME-RS485/RS485-P)
Basic Document Information
주문번호: 2744429
Full Model Name: PSM-ME-RS485/RS485-P
제품 유형: 3-way Isolated RS485 Repeater (with ATEX explosion-proof certification)
Mounting Standard: 당신의 것 60715 TH35 표준 레일
보호 등급: IP20 (Indoor cabinet use only)
Applicable Environment: -40 ℃ ~ +70 ℃, 비응축, free of dust and water accumulation.
- 설치 전 준비
1.1 도구 목록
Flat-blade screwdriver (2.5 mm), 토크 드라이버, rail end stop (E/NS35 N, 주문 번호. 0800886), shielded twisted pair cable, 멀티미터.
1.2 Cable Specifications
전원 단자: 0.2~2.5 mm² solid / stranded copper wires
RS485 Bus: Dedicated shielded twisted pair (0.5~0.75 mm² recommended)
Terminal Tightening Torque: 0.5~0.6 N·m (5~7 lb-in)
1.3 Installation Environment Prohibitions
- Do not mount directly under inverters, contactors or high-power transformers (blocked heat dissipation air duct + 전자기 간섭).
- Reserve ≥25 mm ventilation gap above and below the module.
- Keep away from 380 V power cables; separate trunking for power and signal cables.
- Strictly comply with ATEX II 3G Ex ec IIC T4 Gc zoning regulations for hazardous area installations.
- DIN Rail Mechanical Installation Procedures
2.1 Mount Module onto DIN Rail
- Fix clean, rust-free standard TH35 DIN rail on cabinet backplate.
- Hook the upper latches of the module onto the top edge of the rail.
- Press the bottom of the module forward until a click sound indicates full locking.
- Install rail end stops on both sides of the module to prevent sliding during operation.
2.2 Module Removal Steps
- Pry down the bottom locking tab of the module with a flat-blade screwdriver.
- Gently pull the lower part of the module outward.
- Lift upward to disengage the upper latches from the rail for removal.
2.3 Mechanical Installation Notes
Do not strike or force plug/unplug the module to prevent damage to internal isolation circuits.
Install shock-absorbing mounting brackets for cabinet rails in high-vibration equipment (stamping, 채광).
Only horizontal transverse mounting is permitted; vertical upside-down installation is forbidden.
3.2 Standard Wiring Rules (2-wire Half-duplex Modbus / 프로피버스)
- Strictly match bus polarity one-to-one: A1 connects to device A of upstream equipment, B1 connects to device B of upstream equipment; A2 connects to substation A of downstream equipment, B2 connects to substation B of downstream equipment.
- Shield layer of shielded twisted pair: Single-point grounding at both physical ends of the bus. Unify G1/G2 terminals of intermediate repeaters to FE terminal for central single-point grounding. Strictly prohibit double-ended grounding which forms ground loops.
- 전원 배선: L+ and Lcannot be reversed. Built-in reverse polarity protection exists, yet long-term reverse connection will shorten service life.
- Do not short-circuit A/B terminals or mix power and bus terminals; short circuits will burn isolation circuits.
3.3 Mandatory Wiring Requirements for Hazardous Areas
- Use explosion-proof shielded cables with cable glands complying with Ex ec standard.
- Reliably connect FE earth bar to protective earth of explosion-proof cabinet; ground resistance < 4 오.
- No mid-bus tapping; termination resistors can only be installed at the two physical ends of the bus.
- DIP Switch Configuration Operation
4.1 DIP Switch Location
Pry open the plastic side cover of the module; two groups of DIP switches are inside:
- S1: Termination resistor for Segment A bus (220 오 + 390 Ω voltage divider matched to 120 Ω bus)
- S2: Termination resistor for Segment B bus
4.2 DIP Switch Application Rules
에: Enable built-in termination resistor; 끄다: Disable termination resistor.
Only set the DIP switch to ON for devices/repeaters at the physical extreme ends of the bus; set all intermediate nodes to OFF.
일반적인 시나리오:
- PLC at the start of Segment A bus, this repeater at Segment A end → S1=ON
- Last instrument at the end of Segment B bus → S2=ON
- Repeater only used as intermediate segment divider with other terminals at both ends of two bus segments → S1 and S2 both OFF
4.3 Transmission Rate Adaptation Note
This model features hardware auto-adaptation from 4.8 kbps로 1500 kbps; no baud rate DIP switch required. Hardware auto transmit/receive switching without RTS control signal.
- 전원 켜기 시운전 단계
- After wiring completion, measure voltage between L+/Lwith multimeter: 19.2~28.8 V (24 V ±20%), 단락 없음.
- Power on without load; steady green power indicator light means normal operation. If off, inspect power supply circuit.
- Bus communication test:
Flashing DATA indicator during data transmission indicates normal signal forwarding.
No flashing: Check reversed A/B polarity, mismatched termination resistor setting or broken bus cable.
- Communication packet loss troubleshooting: Inspect shield grounding, separation of power & signal cables and termination resistor configuration.
- Electrical Isolation Safety Instructions (핵심)
The module adopts three independent isolation channels: Power ↔ Bus A ↔ Bus B, with isolation withstand voltage of 2.5 kV AC.
- Supports connection of two bus segments with different ground potentials to eliminate ground potential difference interference.
- Isolates bus segments connected to inverters and high-power motors, preventing surge breakdown of PLC communication ports.
- Provides physical isolation between hazardous area bus and control room bus to meet Ex safety clearance requirements.
- Installation Acceptance Criteria
- 기계: Module fixed without looseness, latches fully engaged, rail end stops installed properly.
- 배선: All terminals tightened to 0.5~0.6 N·m, no bare copper exposed, no insulation trapped under terminals.
- 접지: FE terminal reliably connected to cabinet protective earth, single-point shield grounding without ground loops.
- DIP Switch: Termination resistors only enabled at bus two ends, all intermediate nodes disabled.
- Power-on: Steady power indicator light, normal flashing of communication indicator during data transmit/receive.
- 환경: Unobstructed ventilation above and below module, kept away from strong electromagnetic interference sources.
- Installation Fault Troubleshooting Matrix
| 결함 현상 | Root Installation Cause | Rectification Action |
| 전원 표시등 꺼짐 | Reversed L+/L-, insufficient supply voltage, 느슨한 단자 | 역방향 전원 극성, 전압을 측정하다, retighten terminals |
| Complete communication failure | Reversed A/B polarity, broken bus cable, all termination resistors enabled | Swap A/B wiring, conduct cable continuity test, enable resistors only at bus two ends |
| Frequent packet loss at high baud rates | Double-ended shield grounding, mixed power & signal trunking, missing termination resistors | Single-point shield grounding, separate cable routing, set DIP switches to ON at bus two ends |
| Unstable communication in hazardous areas | Excessive ground resistance, non-ex-certified cables | Rebuild earth bar, replace with Ex-certified shielded cables |
| Severe module overheating | No upper/lower ventilation gap, adjacent high-power power supplies | 예약하다 25 mm gap top and bottom, relocate away from heat-generating components |
- 규정 준수 & 유지 보수 요구 사항
- 인증: CE, UL, ATEX, DNV GL, RoHS 규제; retain certification documents for hazardous area projects.
- 정기 유지 관리 (모든 6 개월):
Inspect terminal torque to prevent loosening caused by thermal expansion & contraction.
Clean dust on module surface to guarantee ventilation.
Re-test ground resistance and confirm intact shield grounding.
- Modification Prohibitions: Do not remove isolation circuits, short isolation terminals or replace with non-original terminal accessories.
Cross-brand Model Comparison Table for Phoenix Contact 2744429 (PSM-ME-RS485/RS485-P)
Core Features of Reference Product (Replacement Matching Criteria)
- 3-way isolation: Power ↔ Bus A ↔ Bus B, 2.5 kV AC isolation rating
- 2-wire RS485 half-duplex, auto TX/RX switching, compatible with Modbus / 프로피버스
- DIN35 rail mounting, wide temperature range -40~+70 ℃, built-in switchable termination resistors
- Wide-range 24 V AC/DC 전원 공급 장치, narrow 22.5 mm housing width
- Factory-certified ATEX II3G explosion protection (Key distinguishing factor)
- Direct Replacements from Top European Industrial Automation Brands (Preferred for Standardized Projects)
1.1 바이드뮐러 (Explosion-proof Isolated Repeater with Same Positioning)
| OEM Model | 매칭율 | 핵심 차이점 | 적용 가능한 시나리오 |
| 7760054321 | 95% | 3-way isolation, ATEX explosion-proof, 24 V AC/DC, 22.5 mm 하우징; max baud rate limited to 500 kbps (1500 kbps for Phoenix Contact) | Chemical hazardous areas, general Modbus/PROFIBUS; fully interchangeable for low-speed buses |
| 7760054322 (비방폭형) | 90% | No ATEX certification; all other electrical parameters identical | Indoor standard control cabinets without hazardous area requirements |
1.2 지멘스
| OEM Model | 매칭율 | 핵심 차이점 | 적용 가능한 시나리오 |
| 6ES7972-0AA02-0XA0 PROFIBUS Repeater | 70% | PROFIBUS-only, prone to Modbus packet loss; 2-way isolation without independent 3-way isolation; no ATEX | Dedicated to pure DP bus; direct replacement not recommended for Modbus |
| 6ES7972-0CB20-0XA0 (Universal Isolated Repeater) | 82% | 3-way isolation, 1.5 Mbps; no explosion protection, wider 45 mm 하우징 | Siemens complete cabinet systems, non-hazardous zones |
1.3 슈나이더 일렉트릭
| OEM Model | 매칭율 | 핵심 차이점 | 적용 가능한 시나리오 |
| TSXCSU01 | 80% | 2-way isolation without independent 3-way isolation; no ATEX; 최대 500 kbps | Supporting legacy Modbus PLCs, low-interference environments |
| XPSM-RS485-ISO | 88% | 3-way isolation, auto TX/RX; no explosion protection, 27 mm 하우징 | General building automation, water treatment non-hazardous projects |
1.4 씨줄
| OEM Model | 매칭율 | 핵심 차이점 | 적용 가능한 시나리오 |
| RS485-REP-ISO | 85% | 3-way isolation, 1.5 Mbps; no explosion protection, 35 mm wide housing | Standard control cabinets matched with ABB DCS |
- Cost-effective Alternatives from Domestic Industrial Communication Brands (Cost-down Projects)
2.1 어드밴텍
| 모델 | 매칭율 | 차이점 | |
| ADAM-4510S (Isolated Version) | 83% | 2-way isolation without independent 3-way isolation; no ATEX; rail-mounted | General factory Modbus data acquisition, non-hazardous zones without severe ground loops |
2.2 뜸쑥
| 모델 | 매칭율 | 차이점 | |
| TCC-80I | 86% | 3-way isolation, 1.5 Mbps; no ATEX; 30 mm housing width | 자동화된 생산 라인, remote sub-stations, non-hazardous areas |
2.3 Mornsun (DIN Rail Isolated Repeater)
| 모델 | 매칭율 | 차이점 | |
| UR485-REP | 80% | 3-way isolation, 2.5 kV withstand voltage; no explosion protection, 저렴한 비용 | Low-voltage complete sets, small equipment matching |
- Internal Phoenix Contact Replacements (OEM Spare Parts, Zero Rewiring)
- 2744416 PSM-ME-RS485/RS485 (No P Suffix)
매칭율: 99%
차이점: No ATEX explosion-proof certification; 터미널, 딥 스위치, dimensions and electrical performance fully identical
교체 제안: Direct swap in non-hazardous zones without wiring modification
- PSI-REP-RS485W2 (주문 번호. 2313096)
매칭율: 85%
차이점: 4-way isolation, wider housing, 향상된 서지 보호, 더 높은 가격; suitable for heavy-interference high-power workshops
- Replacement Selection Grading Recommendations
등급 1: Fully Seamless Replacement (Priority for Hazardous Area Projects)
바이드뮐러 7760054321
3-way isolation + ATEX explosion-proof, narrow 22.5 mm 하우징, consistent terminal logic; universal wiring, installation and DIP switch rules, only slightly lower max baud rate for high-speed buses.
등급 2: OEM Equivalent for Non-hazardous Zones (Optimal Cost)
피닉스컨택트 2744416 (Same brand non-explosion-proof variant)
Identical cabinet cutout size, terminal layout and termination resistor DIP switch; plug-and-play replacement without program modification.
등급 3: Compatible Replacement for Siemens Complete Cabinet Projects
6ES7972-0CB20-0XA0
Supports dual DP & Modbus protocols, 3-way isolation; only wider housing requires reserved cabinet space.
등급 4: Low-cost General Industrial Replacement (위험하지 않음, Low Interference)
Moxa TCC-80I / Advantech ADAM-4510S
Not recommended for hazardous areas, inverter-dense workshops or sites with large cross-equipment ground potential differences.
- Replacement Risk Warnings (Key Differentiators)
- ATEX Explosion Protection: Only Phoenix Contact 2744429 and Weidmüller 7760054321 carry explosion-proof certification; all other models cannot be deployed in Ex zones, causing compliance failure if substituted.
- Independent 3-way Isolation: Siemens 6ES7972-0AA02 and Advantech ADAM-4510 only provide 2-way isolation, prone to communication dropouts when crossing large ground potential differences.
- 최대 전송 속도: Weidmüller explosion-proof model capped at 500 kbps vs. 원래의 1500 kbps; caution for high-speed Profinet / high-speed Modbus applications.
- 하우징 폭: 지멘스, ABB and Moxa units mostly 30~45 mm wide; rail layout adjustment required for original 22.5 mm narrow installation slots.