전체 모델 이름: PSR-SPP24UC/ESA4/2X1/1X2
시리즈: PSRclassic 안전 릴레이, 피닉스컨택트 dual-channel safety monitoring module for emergency stop and safety gate monitoring
✅ Core Safety Ratings
ISO에서 13849: 카테고리 4 / PL 전자
IEC 61508 / 안에 62061: 실 3
Stop Category: 범주 0 멈추다
✅ Electrical Specifications
공급: 24 DC에서 (-15% ~ +10%), typical power consumption 1.68 여, typical current 70 엄마
산출: 2 safety normally open contacts + 1 signal feedback contact
접점등급: 250 V AC/DC, continuous current 6 에이 (AgSnO₂ gold-plated contacts)
Minimum switching load: 10 다섯, 100 밀리와트
기계적 수명: 대략. 10⁷ operations
응답 시간: 대략. 150 ms for automatic start; release time 20~45 ms
Recovery time: ≥1 s
✅ Wiring & 건설
배선 유형: Push-in pluggable terminals
와이어 단면: 0.2~1.5mm² (AWG24~16), 스트리핑 길이 8 mm
설치: DIN 레일 장착, yellow housing RAL1018, PA material
치수: W22.5 mm × H112 mm × D114.5 mm
보호 등급: IP20 (module body)
✅ Functions & 시작 모드
Dual-channel monitoring: 비상 정지 버튼, safety gate switches
Start mode: automatic start (ESA4 version, no external reset)
Built-in status LED indicators
Input circuit supports two-wire safety circuit detection for wire breakage and short-circuit faults
✅ 환경 조건
작동 온도: -20℃ ~ +55℃
Storage/transport temperature: -40℃ ~ +70℃
진동: 10~150Hz, 2 g; 충격 15 g
Maximum altitude: 2000 중
✅ 선택 & 대체 참조
Comparable models in the same series:
2963941: 수동 재설정 버전 (ESA2)
2963925: Single-channel simplified version
메모: ESA4 = automatic start; ESA2 = external reset required. Not directly interchangeable.
✅ 일반적인 애플리케이션
공작기계, 자동화된 생산 라인, 운반 장비, robot peripheral safety circuits, dual-channel emergency stop / safety gate monitoring, meets PL e and SIL3 safety requirements for machinery.
Troubleshooting Checklist for PSR-SPP-24UC/ESA4/2X1/1X2 (Order No.2963938) – Field Version
(나) 결함 현상 + LED 상태 + 문제 해결 단계
1) Power LED off after power-up (no module response)
가능한 원인: No supply voltage, 저전압, 역극성, 느슨한 단자, internal burnout
Troubleshooting steps:
- Measure voltage at A1/A2: must be 24 VDC (20.4~26.4 V), AC220V is strictly prohibited
- Check whether wires are securely clamped in push-in terminals, 스트리핑 길이 8 mm, no poor contact
- Confirm polarity is not reversed (A1=+24V, A2=0V)
- Power cycle; if LED still off → internal module failure, 직접 교체
2) Power LED on, but safety output contacts do not close (no main output)
Case A: Fault in input circuit (dual-channel emergency stop / 안전문)
- Confirm first: this model is ESA4 automatic start, no external reset terminal, reset button is not required
- Measure two input channels (S11/S12, S21/S22): both channels must conduct simultaneously
- Common faults:
Broken wire on one channel, poor contact of normally open contacts
Short circuit between two signal wires (short-circuit in two-wire circuit triggers fault lockout)
Oxidized or mechanically jammed contacts of safety gate switch
- 단락 테스트: temporarily short S11-S12 and S21-S22. If relay pulls in → external wiring / switch damaged; still no pull-in → module fault
Case B: Fault lockout triggered by circuit detection (internal latch)
현상: Input signal appears normal, but relay stays open, still inactive after power cycle
원인: Mismatched timing of two channels, 단락 / wire breakage stored in fault memory
Handling: Power off for ≥1 minute then re-power; remains locked → replace module
3) Relay pulls in and opens immediately after release (momentary action)
원인: Poor contact of input circuit, 느슨한 배선, contact bounce of button
문제 해결: Measure voltage drop section by section to eliminate loose terminals; use shielded cable to reduce interference
4) Output contacts close, but load does not operate
- 측정하다 13/14 그리고 23/24 two sets of safety NO contacts: conduction resistance should be <0.5 Ω
- 심각한 접촉 침식 (높은 저항) → contact failure, replace module
- Load-side short-circuit triggers safety disconnection, check external contactors and solenoid valves for short circuits
5) Random tripping and frequent false triggering (interference fault)
- Route power cables and safety signal cables separately, minimum distance ≥30 cm
- Add varistors on safety circuit to suppress surge voltage
- Confirm supply is an isolated DC power supply without ground noise
(II) Quick Self-Check Procedure (follow sequence)
- Measure power A1/A2: 24VDC normal ✅
- Measure two input channels: both conducting ✅
- 다음 시간 동안 전원 끄기 1 minute and re-power to clear fault lockout ✅
- Short input terminals to verify relay pull-in ✅
- Check continuity of output contacts ✅
- Eliminate open circuit, short circuit and interference on external wiring ✅
(III) 금지된 작업 (to avoid invalidating safety rating)
Do not modify ESA4 automatic start model for external reset, this will invalidate PL e / Cat.4 rating
Do not parallel the two input channels; dual channels must be wired independently
Do not connect freewheeling diodes across safety contacts (reduces contact service life)
- Full Model List of PSR-SPP-24UC Series (주문 번호. + 모델 + 시작 모드 + 연락처 구성)
(1) Dual-channel master modules for emergency stop / 안전문 (ESA series, 카테고리 4 / PL 전자 / SIL3)
- 2963938 | PSR-SPP-24UC/ESA4/2X1/1X2 | Automatic start (ESA4) | 2 safety NO + 1 feedback
- 2963941 | PSR-SPP-24UC/ESA2/2X1/1X2 | External manual reset (ESA2) | 2 safety NO + 1 feedback
- 2963954 | PSR-SPP-24UC/ESA2/4X1/1X2/B | 수동 재설정 | 4 safety NO + 1 feedback (B pluggable terminal version)
- 2963996 | PSR-SPP-24UC/ESAM4/8X1/1X2 | Automatic start | 8 안전 NO 접점 (high-output version)
(2) Single-channel simplified version (Cat.1~3 lower safety level)
- 2963925 | PSR-SPP-24UC/ESA4/1X1/1X2 | Single-channel automatic start
(3) Contact expansion modules (URM, used with master module for output expansion)
- 2964005 | PSR-SPP-24UC/URM4/5X1/2X2 | 5 아니요 + 1 NC expansion contacts
- 2981046 | PSR-SPP-24UC/URM4/5X1/2X2/B | B pluggable terminal version
(4) 모델 명명 규칙
PSR-SPP-24UC / ESA4 / 2X1 / 1X2
24UC: 24V AC/DC universal (this series only supports DC24V in practical use)
ESA4 = automatic start; ESA2 = external reset; ESAM = high-output multi-contact
2X1: 2 safety normally open contacts; 1X2: 1 feedback contact
III. Supplementary Interchange Notes
- 2963938 (ESA4 automatic) ≠ 2963941 (ESA2 manual reset). Wiring and PLC logic cannot be directly reused. Model replacement is mandatory to change reset mode.
- Suffix /B = separable pluggable terminals; no /B = fixed terminals. Electrical performance identical, 터미널 구조만 다름.
Working Principle of Phoenix Contact PSR Dual-Channel Safety Relay (2963938, PL 전자 / 카테고리 4 / SIL3)
Core summary: Two independent internal monitoring circuits check safety input signals continuously, while self-testing internal faults. It prevents safety loss caused by single-point failure. Once dangerous signal, wire breakage, short circuit or internal fault is detected, safety outputs are reliably de-energized.
A standard relay only has one coil and one contact set. Single-point failure may cause contact welding and loss of protection, which is the problem safety relays are designed to solve.
- Dual-Channel Input Principle (Core for E-Stop & Safety Gates)
For model 2963938: 채널 1 S11-S12, 채널 2 S21-S22. Two independent circuits connect to one dual-contact emergency stop or safety gate switch.
✅ Normal condition: Both channels conduct simultaneously → module confirms safe condition, safety outputs close
❌ Safety trigger (E-Stop pressed, safety gate opened): Both channels open at the same time → safety outputs cut off immediately
⚠️ Fault detection:
One channel open, one channel closed → identified as wire breakage or single contact failure → fault lockout, outputs open
Short circuit between the two channels → module detects short-circuit fault and latches off
Design goal: Avoid false safe status caused by broken wire or welded contact. This is the foundation of Cat.4: safety function remains available after a single fault.
구별: ESA4 (2963938 automatic start): outputs restore automatically once both channels return to conducting state; ESA2 requires an external reset button for confirmation.
- Internal Dual-Channel Self-Test & Cross Monitoring (Key Difference from Standard Relays)
A safety relay is not simply a pair of ordinary relays. It contains two independent drive circuits plus two safety contact banks monitoring each other:
- Contacts of the two internal relays are connected in series inside the safety output path (출력 13/14, 23/24)
- The module continuously compares the status of both internal relays:
If one internal relay contact welds closed, the other channel detects inconsistent status and locks the module, preventing output reclosure
Power-on self-test runs at startup to check coil and contact welding faults
👉 A standard relay with welded contacts keeps load powered. Safety relays detect this fault and lock out, preventing dangerous unintended startup.
- Feedback Contact (1X2, auxiliary contact for 2963938)
This auxiliary contact is not used for safety disconnection, only for status feedback to PLC or indicators:
It operates synchronously when safety outputs close
PLC uses it to judge safety circuit readiness and E-stop reset status
중요한: Do not use this auxiliary contact for safety stop! Safety shutdown must use the two main safety contacts.
- Fault Latch Logic
The module enters fault lockout when any of the following occurs:
Mismatched dual-channel signals
Short circuit or wire breakage on input wiring
Internal relay contact welding fault
Timing anomaly caused by electromagnetic interference
Once locked, outputs will not restore automatically even after external wiring is repaired (ESA4 also requires sufficient power-off time to reset; ESA2 needs reset button actuation).
Design philosophy: Faults must be visible to personnel instead of silent recovery, eliminating hidden hazards.
- 범주 0 멈추다 (이 모델 2963938 is Category 0)
Safety relay outputs directly cut off the coil circuit of contactors, which is Category 0 멈추다: immediate power removal, coast-to-stop
비교:
고양이.0: Direct power cut (이 모델)
카테고리 1: Controlled deceleration stop with delayed power removal (high-end safety controllers)
- Safety Rating Mapping
카테고리 4: 듀얼 채널 + self-test + fault lockout, single fault will not disable safety function; multiple faults are detected as much as possible
PL 전자: ISO13849, extremely low probability of dangerous failure, suitable for robots, 공작기계, presses and high-risk machinery
SIL3: IEC61508 functional safety, applied to high-risk process equipment
- Simple Analogy
Standard relay: Actuate when signal received, no self-check. Welded contact keeps load energized.
안전 릴레이:
Two eyes (dual input channels), two hands (two safety contact sets). The two eyes watch the two hands mutually.
If one eye loses signal or one hand sticks closed, it releases power immediately and locks itself to prevent dangerous startup.
일반적인 오해
- ❌ Two ordinary relays wired together do not equal a safety relay: standard relays lack cross-monitoring and short/open circuit detection, cannot achieve PL e
- ❌ Dual-channel does not mean simple parallel wiring: channels must be independent. Shorting S12 and S22 disables dual-channel fault detection