RS485 PROFIBUS 9-pin Sub-D bus plug, 90° vertical outlet, with PG programming port, built-in disconnectable terminating resistor. Suitable for DP/MPI stations such as S7-300/400 and ET200M, 인버터.
✅ Key Specifications
Communication rate: 최대 12 메가비트/초
케이블 콘센트: 90° (vertical downward)
구성: PG 프로그래밍 소켓 포함 (programming cable can be plugged in online without disconnecting the bus)
종단저항: built-in with toggle switch (켜기/끄기, 외딴)
치수: 15.8 × 64 × 35.6 mm (폭 × 높이 × 깊이)
Bus standard: 프로피버스 DP / MPI (MPI network compatible)
상품상태: PM300 active product, made in Germany, RoHS 준수
특징: pure hardware connector, no configuration required in TIA Portal / STEP7, 플러그 앤 플레이
📌 Model Comparison for Selection
| 주문 번호. | Outlet Angle | PG Port |
| 6ES7972-0BB12-0XA0 | 90° vertical | ✅ With PG port (이 모델) |
| 6ES7972-0BA12-0XA0 | 90° vertical | ❌ Without PG port |
| 6ES7972-0BB42-0XA0 | 35° angled outlet | ✅ With PG port |
| 6ES7972-0BA42-0XA0 | 35° angled outlet | ❌ Without PG port |
접미사 12 = updated optimized version; older 11 series is gradually phased out
🛠️ Typical Application
- MPI/DP interface of S7-300 CPU, IM153 interface module, ET200M slave stations
- 인버터 (MM440, G120 old DP board), DP instruments, remote I/O
- Field commissioning: reserved PG port for PLC online monitoring, program upload and download without interrupting the bus network
- Start and end nodes of the bus: switch to ON to enable terminating resistor; switch to OFF for intermediate stations
⚠️ 설치 & Troubleshooting Notes
- 배선: A/B lines must be connected correspondingly, A to A, B에서 B로. Communication fails directly if reversed. 지멘스 DP bus cable 6XV1830-0EH10 is recommended.
- Terminating resistor rule: Only the first and last connectors on the entire DP bus shall activate terminating resistors; all intermediate stations must turn them off, otherwise packet loss and intermittent communication failure occur.
- Clarification: It is only a physical connector, not a protocol converter. MPI cannot be directly converted to Modbus RTU.
- 국내 대안: Compatible DP plugs (90° with PG) are available on the market. 을 위한 12 Mbit/s high-speed and heavy interference environments, original parts are preferred.
🌡️ Special Wide-temperature Version
SIPLUS anti-corrosion wide-temperature model: 6AG1972-0BB12-2XA0, -25~+70℃ with anti-corrosion coating, suitable for outdoor and corrosive environments.
Application Scenarios of 6ES7972-0BB12-0XA0 (90° Outlet DP Bus Connector with PG Programming Port)
Core advantage: Built-in PG debug port, programming adapter can be connected for online monitoring and downloading without removing the bus cable. Preferred for stations requiring frequent commissioning. 프로피버스 DP 지원 / MPI up to 12 Mbps, 90° vertical outlet saves cabinet space for compact wiring.
- Compatible Hardware Stations
- S7-300 PLC (CPU315-2DP, 313-2DP etc., onboard DP/MPI port) – most widely used
- S7-400 PLC, CP443-5 DP communication module
- S7-200 (with DP expansion EM277)
- ET200 series remote I/O: ET200M, ET200S, ET200B, ET200L (IM153-1/2/4 interface module)
- Siemens DP inverters: MM440, MM420, legacy G120 DP option board, 6SE70 DC drives
- Third-party PROFIBUS DP slaves: DP instruments, weighing modules, valve islands, 인코더, 온도 컨트롤러, DP servo drives of other brands
- Network Function Scenarios
- DP bus master station (highly recommended for this model)
Located at the PLC master station, used for frequent commissioning, upload/download and online diagnosis. USB-MPI/DP adapter can be plugged into the PG port without breaking the bus, this is its mainstream application.
- Start and end terminating nodes of DP bus
Terminating resistor toggled ON for connectors at both ends of the bus. If the master station sits at the end, the PG-equipped version is preferred.
- MPI network communication
MPI communication between S7-300 and legacy HMI such as MP277 / TP170. This connector can be fitted on CPU or HMI side to reserve a debug port.
- Compact wiring inside control cabinet
90° downward cable routing along cabinet base plate. Compared with 35° angled outlet, it fits densely arranged backplanes with limited cabinet space.
For intermediate stations with rare maintenance, select 6ES7972-0BA12-0XA0 without PG port to reduce cost.
III. 산업 응용
공작기계: CNC 선반, 머시닝 센터, gantry machines (legacy 840D/810D PROFIBUS networks)
포장, textile and printing production lines
수처리, 공조, 공기조화장치, 펌프장
고무 & plastic extruders, 사출 성형 기계
크레인, 운반 시스템, 자동화 창고
발전소, 야금, petrochemical retrofitting & maintenance of legacy DP systems
- Not Suitable Scenarios (Pitfall Reminder)
- Not a protocol converter, DP/MPI cannot be directly converted to Modbus RTU
- Not applicable for PROFINET (PN Ethernet)
- 집 밖의, corrosive and ultra-wide temperature (below -25℃) 환경: use SIPLUS version 6AG1972-0BB12-2XA0
- FastConnect stripping cable: this model does not support FC quick terminals; dedicated FC models are required
PROFIBUS DP Wiring Specification + Terminating Resistor Setting + Communication Troubleshooting Checklist
For 6ES7972-0BB12-0XA0 / 6ES7972-0BA12-0XA0 standard Sub-D DP connectors
권장 케이블: 6XV1830-0EH10 standard purple DP cable (shielded twisted pair with copper conductor)
- 배선사양
- Bus Topology Rule (DP only permits bus topology; star and tree topology forbidden)
✅ Valid: All stations connected in series on one main cable with two terminators at both ends
❌ 금지: Short branches, T-taps, star junction boxes (causes unstable communication)
If branches are mandatory, DP repeater (6ES7972-0AA01-0XA0) must be used
- 전송 속도 & Max Cable Length (single segment without repeater)
| 전송 속도 | Max Cable Length |
| 9.6 킬로비트/초 | 1200 중 |
| 19.2 킬로비트/초 | 1000 중 |
| 187.5 킬로비트/초 | 500 중 |
| 500 킬로비트/초 | 200 중 |
| 1.5 메가비트/초 | 100 중 |
| 3 메가비트/초 / 6 메가비트/초 / 12 메가비트/초 | 100 중 |
연발총: Each repeater extends one segment and isolates signals; 최고 9 repeaters cascaded
- 차폐 & 접지 (root cause of most faults)
- The outer metal shield of DP cable shall be crimped to the metal shell of the connector. Do not strip a separate wire from shield for PE connection.
- Metal shell of all DP connectors connected to cabinet PE protective earth (equipotential bonding)
- Power cables (인버터, motor power lines) and DP signal cables shall be routed separately, minimum spacing ≥20 cm. Cross at 90° if unavoidable.
- Line reactors and filters shall be installed for variable frequency motors and high-power contactor circuits to suppress interference.
- Avoid multi-point earthing of shield and cross-cabinet wiring with large potential difference, which creates ground loop and intermittent communication dropouts.
- 핀 정의 (9-pin Sub-D, DP standard)
핀 3: B line (녹색)
핀 8: A line (빨간색)
✅ Mnemonic: Red=A, Green=B. A to A, B에서 B로, consistent across the whole bus. A/B crossover causes communication failure.
A and B are differential signals inside the connector. Reversed wiring leads to no slave station found without short-circuit alarm.
- 콘센트 & 설치
90° models (0BB12/0BA12): suitable for horizontally arranged backplanes inside cabinet, cable routed downward
35° angled outlet (0BB42/0BA42): suitable for cables entering from cabinet side
Avoid sharp bending of DP cable; bending radius ≥ 8 × cable diameter
Do not bundle DP cables together with servo power cables in the same trunking
- Terminating Resistor Setting (비판적인)
Side toggle switch on connector: ON = terminating resistor activated; OFF = deactivated
✅ Standard rule:
Only the very first and last stations on one DP bus shall toggle ON; all intermediate stations must stay OFF!
Master station at bus end: master connector ON, last slave connector ON, others OFF
Master station located in the middle of bus: master connector OFF, connectors at two remote ends ON
Common mistakes:
① No terminator activated at both ends → signal reflection, packet loss, intermittent failure, worse at high speed
② Multiple nodes with terminator ON → excessive bus load, unstable communication and slave failure alarms
③ Only one end terminator ON → signal reflection, sporadic faults
메모: The PG port on 6ES7972-0BB12-0XA0 does not carry built-in terminator. The PG adapter itself has no terminating resistor, it is only for commissioning.
III. DP Communication Troubleshooting Checklist (follow sequence for high efficiency)
단계 1: Visual Hardware Inspection (우선 사항)
- Check A/B wiring for reverse connection, loose contact, stray copper wire short circuit
- Verify terminating resistor switches, confirm only two ends are ON
- Check DP cable for damage, compression, heat exposure from power equipment
- Confirm shield is reliably crimped and connector shell is well earthed
- Check Sub-D connector is fully locked and not loose
단계 2: PLC Diagnosis (STEP7 / TIA 포털)
- Online check CPU diagnostic buffer:
잘못: Station failure: usually cable issue, terminator setting, interference or slave power loss
잘못: Frame error, checksum error, 동기화 오류: mostly loose A/B contact, interference or baud rate mismatch
- 하드웨어 구성: baud rate of master and all slaves must be identical, cannot mix 1.5M and 500K
- No duplicate DP addresses. DP address range: 0~126. Master is usually address 2; duplicate addresses are forbidden.
단계 3: Segmentation Isolation Method (for hard-to-locate intermittent faults)
- Split the bus into two segments and test separately to locate faulty section
- Remove slaves one by one starting from the last station to find the faulty node
- Suspected interference: replace with short DP cable temporarily and keep away from inverters and contactors
- Suspected connector failure: replace DP plug directly (many faults come from aged spring contacts inside)
단계 4: Frequent Pit Summary
- Ordinary 2-core shielded cable substituted for Siemens dedicated DP cable → impedance mismatch, unstable communication at high speed
- Large ground potential difference, ground loop formed by shield earthing → slow intermittent dropout
- Excessive bus length with baud rate set too high, exceeding length limit
- Unstable 24V supply and large voltage drop for old EM277, IM153 modules
- Ungrounded inverters and servos inject high-frequency interference into DP bus
- Pulling PG adapter during commissioning loosens bus connector and causes poor contact
단계 5: 보조 도구
DP bus tester: measure terminal impedance. When both ends are enabled, bus impedance is approximately 110 오. Readings other than 110 Ω at intermediate nodes are normal.
Online diagnosis table: observe cyclic loss and recovery of slaves. Periodic dropout is mostly interference or terminator problem.
- Quick Commissioning Tips (for 0BB12 with PG port)
- USB-DP adapter plugged into PG port during commissioning, no removal of original DP bus required, no impact on the whole network
- Prefer 0BB12 if master station is at the end for convenient maintenance later
- Select 0BA12 (without PG) for intermediate stations with minimal maintenance to save cost
- Fault Quick Reference Table
| 징후 | 가능한 원인 |
| All slaves cannot be detected | A/B reversed on master connector, terminators disabled at both ends, master DP port damaged |
| One slave drops randomly, others normal | Loose connector of this station, unstable power supply of this slave, faulty slave module |
| Communication drops after running, recovers after cooling | Inverter interference, heat-affected cable, thermal contact degradation of connector |
| Works at 9.6K baud rate, frequent dropout at 1.5M | Overlength cable, impedance mismatch, wrong terminator setting, heavy interference |
- 6ES7972 Full Series PROFIBUS Bus Connectors (DP/MPI Plugs)
모델 코딩 규칙
접두사: 6ES7972 (standard DP connector); 6AG1972 (SIPLUS wide-temperature anti-corrosion version)
5번째 문자: B = with PG programming port; A = without PG programming port
6th~7th digits: outlet angle & 배선 유형
12: 90° vertical outlet, 나사식 터미널 (표준형)
42: 35° angled outlet, 나사식 터미널
52: 90° vertical outlet, FastConnect quick stripping type
60/61: 35° angled outlet, FastConnect quick plug
접미사: 0XA0 (standard industrial grade)
- Standard Industrial Versions (6ES7972, IP20, 0~+60℃)
1) 90° Vertical Outlet (downward routing in cabinet, flagship model)
Screw Wiring (not compatible with FC cable)
- 6ES7972-0BB12-0XA0|90°, with PG port (이 모델, preferred for master station)
- 6ES7972-0BA12-0XA0|90°, without PG port (cost-effective for intermediate slaves)
FastConnect Quick Plug (no stripping required for FC purple cable)
- 6ES7972-0BB52-0XA0|90°, with PG port, FC quick plug
- 6ES7972-0BA52-0XA0|90°, without PG port, FC quick plug
2) 35° Angled Outlet (cable entering from cabinet side)
Screw Wiring
- 6ES7972-0BB42-0XA0|35°, with PG port
- 6ES7972-0BA42-0XA0|35°, without PG port
FastConnect Quick Plug
- 6ES7972-0BB60-0XA0|35°, with PG port, FC quick plug
- 6ES7972-0BA60-0XA0|35°, without PG port, FC quick plug
3) 180° Straight Outlet (축방향 출구, for OLM fiber module)
- 6ES7972-0BB00-0XA0|straight outlet, with PG
- 6ES7972-0BA00-0XA0|straight outlet, without PG
4) Matching Active Terminating Resistor (for bus end)
- 6ES7972-0DA00-0AA0|active terminator, improves signal for high-speed long-distance communication
III. SIPLUS Wide-temperature Anti-corrosion Series (6AG1972, harsh & 야외 환경)
온도 범위: -40℃ ~ +70℃, anti-corrosion coating, for HVAC, metallurgy and outdoor equipment
- 6AG1972-0BB70-7XA0 (90° with PG, equivalent to 0BB12)
- 6AG1972-0BA70-7XA0 (90° without PG, equivalent to 0BA12)
- 선정 참고표
| Routing Type | 배선 유형 | With PG Port (Master Station) | Without PG Port (Intermediate Slave) |
| 90° downward (common cabinet layout) | 나사식 터미널 | 6ES7972-0BB12-0XA0 | 6ES7972-0BA12-0XA0 |
| 90° downward | FC quick plug | 6ES7972-0BB52-0XA0 | 6ES7972-0BA52-0XA0 |
| 35° side entry | 나사식 터미널 | 6ES7972-0BB42-0XA0 | 6ES7972-0BA42-0XA0 |
| 35° side entry | FC quick plug | 6ES7972-0BB60-0XA0 | 6ES7972-0BA60-0XA0 |
- Related Accessories
- PROFIBUS standard cable: 6XV1830-0EH10 (purple DP cable)
- DP repeater: 6ES7972-0AA01-0XA0 (extend segment, isolate interference)
- OLM fiber link module: convert electrical DP to optical fiber for long-distance and heavy interference applications
Master station & frequent commissioning → BB (with PG); intermediate stations with rare maintenance → BA (without PG)
Ordinary wiring & standard DP cable → 12/42 (screw type); FC fast cable used → 52/60 (FC quick plug)
Backplane downward routing in cabinet → 90° (12/52); side cable entry → 35° (42/60)
접촉기,회로 차단기,감지기,인코더,PLC,변환기



















NH42-63-318x560.png)