슈나이더 3CT-H1-100-C 전류 변압기

Schneider 3CT-H1-100-C 변류기의 전체 사양 (EOCR 전용) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • 제품 세부정보

Full Specification of Schneider 3CT-H1-100-C 변류기 (EOCR 전용)

  1. 모델 코드 해석
코드 세그먼트의미설명
3CT제품 시리즈Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1사양 코드Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100정격 1차 전류100에이 (numerator of transformation ratio)
기음Mounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. 핵심 기술 매개변수
매개변수 카테고리사양주목
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
정확도 등급수업 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10버지니아Max permissible secondary loop impedance 200mΩ
주파수 범위50/60헤르츠General industrial frequency
정격 절연 전압AC 600VMaximum continuous operating voltage
내전압2kV (50헤르츠, 1분)Insulation test standard between windings and earth
절연저항≥100MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
전반적인 차원W150×H71×D55mm컴팩트한 구조, space-saving installation
장착 유형패널 장착표준 35mm DIN 레일과 호환 가능
재료Flame-retardant engineering plasticCompliant with UL94 V0 standard
무게대략. 0.58kgSingle unit weight
인증CE, ULConforms to international safety standards
주문 번호3CT-H1-100-CExclusive official Schneider order code
  1. 전체 모델 목록 (EOCR 3CT Series)
모델비율Aperture ShapeBore Size정격전류장착 유형
3CT-HS-75-C/Z75/5에이Circularφ22mm75에이C=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5에이Circularφ25mm100에이C=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5에이Square30×30mm150에이C=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5에이Square35×35mm200에이C=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5에이Square45×45mm300에이C=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5에이Square55×55mm400에이C=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
상표모델비율정확성BurdenAperture호환성
슈나이더

(SAMWHA)

3CT-H1-100-C100/5에이수업 110버지니아φ25mmPerfect match for EOCR
지멘스5SD7410-7100/5에이수업 110버지니아φ25mm유니버셜 타입, adaptation test required
씨줄CT-AR/100100/5에이수업 115버지니아φ25mmHigher burden capacity, EOCR compatible
친트BH-0.66/100100/5에이수업 110버지니아φ25mmCost-effective domestic alternative
맛있는LMZ1-0.66/100100/5에이수업 110버지니아φ25mm국내 대체, minor dimension difference

교체 노트

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. 문제 해결 & 유지
결함 현상가능한 원인Inspection Steps솔루션
No secondary output잘못된 배선, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
절연 불량Dampness, insulation aging, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

안전 규칙

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. 애플리케이션 & Cases

적용 가능한 시나리오

EOCR motor protection system: 과전류, undercurrent and phase loss protection

저전압 배전: Current monitoring and protection for circuits below AC 600V

Motor control center: Compact layout saves cabinet space

Industrial production lines: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400헤르츠) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

일반적인 경우

사례 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

사례 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, 절약 50% 설치 공간, simplifying wiring and improving operational reliability.

  1. 선택 & Installation Guidelines

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

설치시 주의사항

Keep correct S1(나+) and S2(나-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

유지보수 일정

주기기준
육안검사월간 간행물No crack, looseness or overheating mark
Terminal tightening계간지Torque range 2-3N·m
절연 테스트매년Resistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 정확성, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.