- 제품개요
모델: BMXCPS3500
시리즈: Modicon X80 Rack-mounted 전원공급장치 (Compatible with M340 / M580 PLCs)
포지셔닝: 36W standard AC input backplane power supply for medium & large X80 racks, with isolated 24V sensor output built-in
Derivative Model: BMXCPS3500H (넓은 온도 버전, -25℃ ~ +70℃)
모델 코드 분석
BMX-CPS-3500
BMX: Modicon X80 platform series
CPS: Control Power Supply rack power module
3500: 36W wide AC voltage high-power variant
- 핵심 전기 사양
2.1 Input Ratings (교류)
Nominal Voltage: 100~240V AC
Full Wide Voltage Range: 85~264V AC (Universal for global power grids)
빈도: 47~63Hz (50/60헤르츠 호환)
입력 전류: 1.04A @115V / 0.52A @240V
돌입 전류: 30A @120V / 60A @240V (Built-in soft start)
Apparent Power: 120버지니아
Input Fuse: Non-replaceable internal fuse
2.2 Three Isolated DC Outputs (Total Rated Power: 36여)
| Output Channel | 전압 | 정격전류 | 힘 | 애플리케이션 |
| Logic Power | 3.3DC에서 | 4.5에이 | 15여 | CPU, backplane bus, I/O logic chips |
| Main Rack 24V | 24DC에서 | 1.3에이 | 31.2여 | CPU modules, digital/analog I/O, 통신 모듈 |
| Isolated Sensor 24V | 24DC에서 | 0.9에이 | 21.6여 | 4-20mA transmitters, field sensors, 밸브 |
> Key Limitation: All three channels cannot run at full load simultaneously; maximum total output power of the unit is 36W.
2.3 기계 & 환경 사양
전체 치수: 242.4 × 35 × 110 mm (Single-slot X80 rack module)
순중량: 0.36kg
보호 등급: IP20 (캐비닛 설치 전용)
Standard Operating Temperature: 0℃ ~ +60℃
Wide-temperature Model 3500H: -25℃ ~ +70℃ (Automatic power derating at high temperatures)
보관 온도: -40℃ ~ +85℃
습기: 5%~95% 상대습도, 비응축
MTBF: 4.3 million hours (Continuous operation at 25℃)
2.4 안전 & EMC Certifications
CE, UL508, CSA, RCM, EAC, ATEX explosion-proof certification
준수 표준: 안에 61131-2, 안에 61000-6-2/6-4, 안에 61010-2-201
- Front Panel Interfaces & 기능
- 5-pin Main Terminal Block
L/N: AC mains input
체육: Protective Earth
24V+/0V: Isolated sensor power output (0.9에이)
- 2-pin Alarm Relay Terminal Block
Passive dry contact; contacts open upon power failure; connect to upper-level alarms or audible/visual annunciators
- Dual LED Status Indicators
좋아요 (녹색): Main rack power normal; Off = Backplane power fault
24V SENSOR (녹색): Sensor 24V output normal; Off = Short circuit / overload on sensor circuit
- RESET Button: Cold restart of the rack, quick reset for CPU and backplane bus
- Built-in Protection Mechanisms
입력측: Overcurrent fusing, 서지 억제
출력측: 과전압 (OVP), 과전류 (OCP), short-circuit latch-off, 온도 이상 (OTP)
Independent isolated short-circuit protection for sensor circuit, no impact on PLC rack power supply
Fault Latch: After clearing short circuit, power cycle or press RESET to restore operation
- X80 Power Supply Selection Comparison within the Same Series
| 모델 | 입력 유형 | Total Power | Sensor 24V Current | Applicable Rack Scale |
| BMXCPS2000 | 85~264V AC | 20여 | 0.45에이 | Small racks ≤12 slots |
| BMXCPS3500 | 85~264V AC | 36여 | 0.9에이 | 중간 & large multi-rack systems |
| BMXCPS3500H | 85~264V AC | 36여 | 0.9에이 | Severe high/low temperature sites |
| BMXCPS4002 | 24DC에서 | 40여 | 1.6에이 | DC-powered control cabinets, on-board equipment |
Selection Conclusion for Replacement
- Downward Replacement: BMXCPS2000 can be used if total load <20여, but sensor power capacity is halved; not directly interchangeable for high-load systems.
- Upward Replacement: No higher-power AC-input X80 power supply available. Multiple BMXCPS3500 units shall be configured for separate racks in multi-rack systems.
- Low-temperature Applications: BMXCPS3500H is mandatory for field temperatures below 0℃; 기준 3500 will derate or trigger faults at low temperatures.
- 일반적인 애플리케이션 시나리오
- 중간 & large Modicon M340/M580 PLC control systems
- Main control cabinets for water treatment, 야금, 화학적인, packaging machinery and building automation
- Projects requiring independent isolated 24V power for transmitters, flow meters and pressure sensors
- Centralized power supply for multi-expansion racks (BMXXBP series backplanes)
- 문제 해결 매트릭스
| 결함 현상 | 근본 원인 | Handling Procedures |
| Both LEDs fully off | No AC input, 느슨한 배선, 끊어진 내부 퓨즈 | 1. Measure L/N voltage; 2. 터미널을 조이세요; 3. Replace module if fuse blown |
| OK LED off, Sensor LED on | Total rack load exceeds 36W, backplane short circuit | 1. Calculate total power consumption of all modules; 2. Remove redundant I/O modules; 3. Inspect backplane for short circuit |
| Only 24V Sensor LED off | 단락 / overload on sensor circuit | 1. Disconnect external sensor cables; 2. Locate short circuit in field wiring; 3. Restart power supply after recovery |
| Indicators flicker after running for a period | Ambient temperature over 60℃, poor heat dissipation | Install cabinet cooling fan, replace with 3500H wide-temperature model, reduce rack load |
| Alarm relay remains open | Protection triggered on any output channel | Power off for 5 minutes to cool down, inspect short circuit and overloaded loads |
- 설치 & 배선 금지 (Hard Rules)
- Do not share the same circuit with high-power inverters and contactors; separate isolated power supply is required.
- Sensor 24V cables shall not be routed in the same trunking as power cables to avoid interference.
- The module must be reliably connected to PE protective earth; otherwise EMC interference may cause false alarms.
- Total load of a single 3500 unit is strictly limited to 36W max; separate power supplies must be used for multiple racks.
- Do not plug/unplug the module during operation (no hot-swap design); replace only after power cut-off.
- Compatible Backplanes
Fully compatible with all BMXXBP X80 backplanes: BMXXBP0400 / 0600 / 0800 / 1200, 등.
Incompatible: Old-generation Quantum BMEXBP series backplanes; mixed use is forbidden.
Complete Installation Specification for Schneider BMXCPS3500
- Core Installation Structure (Two Layers)
1.1 Base Layer: 35mm 표준 DIN 레일 장착 (Cabinet Rear Panel)
The unit is equipped with a built-in DIN35 standard snap-on base, compatible with national standard 35mm electrical mounting rails (AM1 ED rail).
모듈 폭: 35mm, single-slot occupation; 치수: 242.4 (시간) × 35 (여) × 110 (디) mm
Snap structure: Dual upper & lower elastic snaps for rail fastening without screws; top/bottom latches prevent detachment
Rail mounting steps:
- Secure 35mm DIN rail to cabinet rear panel, ensure rail is level and undeformed
- Hook the module’s bottom snap onto the lower edge of the rail first, then push the upper part of the module upward until a “딸깍 하는 소리” sound confirms full engagement
- Fully lock both upper and lower snaps; no vertical looseness under pulling force. 제거하려면, pry open upper/lower snaps with a flat screwdriver.
1.2 Upper Layer: X80 Dedicated Backplane Slot Installation (Core Rack Power Connection)
BMXCPS3500 must be inserted into BMXXBP series X80 rack backplanes to supply power to CPU and I/O backplanes; standalone operation without backplane is not allowed.
Compatible Backplane Models
Only compatible: BMXXBP0400 / 0600 / 0800 / 1200 (including H wide-temperature variants)
Mixed Use Forbidden: Old BMEXBP…02 Quantum backplanes with mismatched physical connectors.
Standard Backplane Mounting Procedure (Power Off Mandatory, Hot Swap Prohibited)
- Cut off power to the whole unit and disconnect AC input
- Align the metal guide slots on the rear of the power module with upper/lower rails of the rack backplane, slide horizontally smoothly to the bottom of the slot
- After full insertion, backplane bus gold fingers are fully mated; front face of the module aligns flush with other I/O modules
- Built-in left & right locking latches on the module, snap inward to lock onto the rack and prevent loosening under vibration
- Power supply shall be installed in the 1st leftmost slot of the rack as priority (Official recommended layout); one CPS3500 for each independent backplane in multi-rack systems.
- Mounting Attitude & Tilt Restrictions
- Standard Attitude: Vertical upright installation (cabinet rear panel vertical, module vertical top-to-bottom) for vertical convection cooling airflow, optimal heat dissipation
- Allowable Tilt: Full-load operation permitted within ±30° panel tilt; derating required if tilt exceeds 30°, cabinet internal temperature ≤40℃
- 엄격히 금지됨: Horizontal flat or upside-down mounting – airflow blocked, frequent overtemperature tripping, drastically shortened service life.
- Mandatory Heat Dissipation Clearance Requirements (Hard Installation Gaps)
The module relies on natural air cooling via top & bottom ventilation holes; clearances must be reserved:
위에 & below the module: ≥20mm free space, unobstructed by cable ducts or other components
Left & right sides of the module: ≥10mm, no tight contact with adjacent modules
Horizontal distance between heat-generating components (인버터, 접촉기) and power supply inside cabinet ≥50mm
Cooling fan recommended for sealed small cabinets; replace with BMXCPS3500H wide-temperature model if ambient temperature >55℃.
- Terminal Accessory Installation (Wiring Matching Parts)
Standard factory supply: Screw-type terminal block BMXXTSCPS10; Spring push-in terminal block BMXXTSCPS20 available as separate order.
- 5-pin main power terminal (L/N/PE/24V circuit/Sensor 24V): Insert horizontally into lower front interface of module, lock via built-in snap
- 2-pin alarm dry contact terminal: Adjacent to the right of 5-pin terminal, used for fault alarm output
- Terminal Removal: Pinch both side snaps of terminal and pull straight outward; diagonal pulling is prohibited to avoid broken pins.
- 설치환경 & Protection Specifications
- Protection Class IP20, cabinet installation only; no direct exposure to outdoor environment, dust or moisture.
- Flat, burr-free mounting surface; firmly fixed DIN rail; rail end stops required for high-vibration operating conditions.
- PE protective earth wire must be reliably connected to cabinet earth bar to reduce EMC interference.
- No power derating required for altitude ≤2000m; 10% load derating mandatory above 2000m.
- 설치 금지 (Absolute Forbidden Operations)
- Plug/unplug module or wiring terminals while powered – risk of burning backplane bus and power supply.
- Unlocked fixing latches cause poor backplane contact and system shutdown under long-term vibration.
- Insufficient top/bottom heat dissipation space or close contact with cable ducts triggers overtemperature protection under high temperature.
- Upside-down / flat mounting blocks cooling airflow.
- Mixed use of old BMEXBP backplanes with mismatched physical connectors; forced insertion damages gold fingers.
- Single power supply driving multiple independent backplanes leads to overload protection triggered when total power exceeds 36W.
- Supplementary Redundant Power Supply Installation (Multi-Power Scenarios)
예비 전원 공급용, install one BMXCPS3500 in two separate slots of the same rack, each fed by an independent AC circuit. The backplane performs automatic redundant switching. Reserve ≥15mm heat dissipation gap between the two power supplies.
접촉기,회로 차단기,태양광 인버터,전기 계량기,감지기,인코더,PLC
























NH42-63-318x560.png)