(BMXCP53500 is an incorrect model number)
- 모델 코드 분석
| Part | 의미 |
| BMX | Product identifier for Schneider Modicon X80 series |
| CPS | Type code for power supply module |
| 3500 | Specific model: 3 = 36W power rating, 5 = AC input, 00 = standard version |
- 제품개요
The Schneider BMXCPS3500 is a high-power AC power supply module for the Modicon X80 platform, specifically designed for Modicon M340 and M580 Programmable Automation Controller (PAC) racks. It provides stable DC output to power the backplane, I/O modules, CPU, and field sensors.
- 주요 기술 사양
| 매개변수 | 값 |
| 입력 전압 | 100-240V AC (operating range: 85–264V AC) |
| Input Frequency | 50/60 헤르츠 (range: 47–63 Hz) |
| Total Output Power | 36여 |
| 출력 전압 & Power Allocation | • 3.3V DC: 15여 (logic power for I/O modules) |
| • 24V DC (sensor power): 21.6여 | |
| • 24V DC (I/O module power): 31.2여 | |
| Output Current | • 3.3V DC: 4.5에이 |
| • 24V DC (sensor): 0.9에이 | |
| • 24V DC (입출력): 1.3에이 | |
| 능률 | Typical 85% |
| Isolation | Input‑output: 3000뷔와 |
| Output‑output: 500뷔와 | |
| Protection Features | Internal fuse, 과부하 보호, 과전압 보호, short‑circuit protection |
| 설치 | Rack‑mount (compatible with BMXXBP series backplanes) |
| 유입 방지 | IP20 |
| 작동 온도 | 0°C ~ +60°C |
| 보관 온도 | -40°C to +85°C |
| 치수 | Standard X80 module size, 폭 대략. 17.5 mm |
- 운영 환경 & 응용
- 산업 자동화 시스템: PLC control systems in manufacturing, process industries, infrastructure, 등.
- Harsh Industrial Environments: Resistant to wide temperature ranges, 전압 변동, and electromagnetic interference.
- Medium-to-Large PLC Systems: Supplies stable power for multi-module configurations, supporting expanded I/O and complex control tasks.
- Global Deployment: Wide input voltage design compatible with power grid standards worldwide.
- 교체 모델 & Series Comparison
Complete Model List of X80 Series Power Supply Modules
| 모델 | Input Type | 입력 전압 | Total Power | 특징 |
| BMXCPS2000 | DC | 24DC에서 | 16.8여 | Basic DC power supply |
| BMXCPS2010 | DC | 24DC에서 | 16.8여 | Enhanced DC power supply |
| BMXCPS3020 | DC | 24–48V DC | 31.2여 | Wide‑range DC power supply |
| BMXCPS3500 | 교류 | 100-240V AC | 36여 | Standard AC power supply (this product) |
| BMXCPS4002H | 교류 | 100-240V AC | 40여 | High‑power AC supply for harsh environments |
대사 & Compatibility Information
직접 교체: BMXCPS3500 can replace legacy M340 series power supply modules.
Compatible Racks: BMXXBP0600, BMXXBP0800, BMXXBP1200, and other X80 series backplanes.
Incompatible: BMEXBP series backplanes (dedicated for EcoStruxure Control Expert platform).
- Official Ordering Code & 선적 서류 비치
Official Ordering Code: BMXCPS3500 (standard version with no suffix)
Official Manual: Schneider Electric SQD-BMXCPS3500.PDF
인증: CE, RCM, Merchant Navy, CSA, EAC, UL; compliant with EN 61131-2, 안에 61000-6-4, 등.
- Engineering Implementation Recommendations
- 설치 참고 사항
Install the power supply module on the far left of the rack (recommended position).
Allow sufficient space for heat dissipation; avoid adjacent placement with high-power modules.
Use shielded cable for input power to reduce electromagnetic interference.
- 배선 표준
Correctly connect live (엘), neutral (N), and protective earth (체육) 전선.
Separate sensor power and I/O power terminals to avoid cross-connection.
High-current loads should be powered directly from external sources to reduce module load.
- 선택 지침
Select the appropriate power supply based on total system power requirements, with 20–30% power margin.
Consider on-site power quality; install surge protectors and filters if necessary.
The Schneider BMXCPS3500 is a highly reliable, high-efficiency industrial power supply module that provides a complete power solution for the Modicon X80 platform. Its wide input voltage, multi-channel output, and comprehensive protection make it an ideal choice for medium-to-large PLC systems. If you need to verify BMXCP53500, please confirm the correct model number or contact Schneider Electric technical support for more information.
BMXCPS3500 is an isolated AC/DC switching power supply
that provides stable multi-channel 3.3V and 24V DC power for M340/M580 PLC racks. Its core operation consists of 5 stages:
- Input Processing (AC → High-Voltage DC)
입력: 100-240V AC (50/60 헤르츠)
EMI filtering: suppresses grid surges and high-frequency interference
Rectifier bridge: converts AC to pulsating high-voltage DC (대략. 310DC에서)
Capacitive filtering: smoothes into stable high-voltage DC
- High-Frequency DC/DC Conversion (Core Stage)
PWM controller drives MOSFET high-frequency switching (tens of kHz)
High-frequency transformer:
Provides input-output electrical isolation (3000뷔와)
Converts high-voltage DC into multi-channel low-voltage high-frequency pulses
- Output Rectification & Filtering
Secondary high-frequency pulses → Schottky diodes / synchronous rectification → DC
LC filtering: smoothes ripple to produce clean, stable voltage
- Multi-Channel Regulated Output (Unique to BMXCPS3500)
3.3DC에서 / 4.5에이: powers CPU, backplane bus, and I/O logic
24DC에서 / 1.3에이: main power for rack I/O modules
24DC에서 / 0.9에이: dedicated sensor power (isolated, independent current limiting)
- Closed-Loop Regulation + Protection Mechanism
- Voltage Regulation
Output voltage sampled via voltage division → compared with internal reference
PWM duty cycle dynamically adjusted to maintain constant output voltage
- Integrated Comprehensive Protection
과전압 / undervoltage protection (input and output)
초과 적재 / 단락 보호 (per-channel current limiting, hiccup recovery)
과열 보호 (power reduction or shutdown at excess temperature)
Internal fuse
- Status & Alarm
Front-panel READY LED: ON in normal operation, flashing in fault condition
Passive alarm relay:
Normal: contacts closed
Power loss / fault / overtemperature: contacts open (can connect to PLC or audible-visual alarm)
RESET button: manually restarts the rack and resets faults
- Overall Operating Principle (요약)
Mains AC → Rectification & Filtering → High-Frequency Isolated Switching → Multi-Channel Rectification & Filtering → Closed-Loop Regulation → Distribution to CPU / 입출력 / Sensors via Backplane, with full protection and status monitoring.
- Typical Application Sequence
- Power-on → Input filtering and rectification
- Control circuit startup → PWM begins operation
- Outputs gradually establish → Regulation locks in
- READY LED illuminates → Alarm relay energizes → CPU startup enabled
- 잘못 (overcurrent / overtemperature / power loss) → Outputs shut off immediately → Alarm relay de-energizes → Fault indication