Schneider GV2ME08C Motor Circuit Breaker - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

 Schneider GV2ME08C Motor Circuit Breaker - 접촉기,회로 차단기,감지기,인코더,PLC,변환기

회로 차단기/

Schneider GV2ME08C Motor Circuit Breaker

TeSys Deca GV2ME Motor Circuit Breaker (MPCB), push-button operated, screw clamp terminals ✅ Core Technical Specifications Poles: 3P Thermal overload setting range: 2.5~4 A Matched motor power (400V 삼상): 1.5 kW Rated operational voltage Ue: 690뷔와, 50/60 Hz Insulation voltage Ui: 690다섯; 임펄스 내전압 Uimp: 6kV Magnetic short-circuit trip: 대략. 13×In ≈ 51A ...

  • 제품 세부정보

TeSys Deca GV2ME 모터 회로 차단기 (MPCB), push-button operated, 나사 클램프 단자

✅ 핵심 기술 사양

폴란드: 3피

Thermal overload setting range: 2.5~4 A

일치하는 모터 출력 (400V 삼상): 1.5 kW

정격 사용 전압 Ue: 690뷔와, 50/60 헤르츠

절연전압 Ui: 690다섯; 임펄스 내전압 Uimp: 6kV

Magnetic short-circuit trip: 대략. 13×In ≈ 51A (순간 단락 보호)

Rated short-circuit breaking capacity Icu: 100kA @ 400V

활용 카테고리: AC-3 (for direct-on-line motor starting); built-in isolation function + 위상 손실 보호

제어: Red STOP pushbutton, black START pushbutton, with TEST position

설치: DIN 레일 표준; IP20 (finger-safe on front face)

✅ Model Code Definition

GV2: TeSys GV2 motor circuit breaker series

나: Push-button version (rotary knob version: GV2P)

08: Current rating code, corresponding to 2.5–4A

기음: China version with CCC certification

✅ Protection Functions

  1. 열 과부하 보호: Time-delayed tripping for continuous motor overload & 잠긴 로터; adjustable within 2.5~4A via the setting dial
  2. Magnetic short-circuit protection: Instant trip for phase-to-phase short circuit
  3. Phase-loss protection: Accelerated tripping when one phase is lost, preventing motor burnout
  4. Built-in start/stop operation: Can be used alone for small-motor direct start, or paired with contactors for star-delta / auto-transformer starting circuits

✅ Compatible Accessories (Field-mountable)

GVAN: 보조 접점 (1아니요+1NC, for ON/OFF & trip status feedback)

GVAX: 알람 접점 (differentiates overload trip from short-circuit trip)

GVAD: 션트 트립 / undervoltage trip coil

GV2AF3: 부스바, adapter & interlock module

✅ 선택 & 교체 참조

Same-series knob variant: GV2P08C (identical thermal-magnetic curve & tripping parameters, 2.5-4A)

국내 대안: Delixi CDM6e-M, 친트 NS2-25 08 (2.5~4A motor protector)

Higher frame upgrade: GV3ME series with same current rating

✅ Wiring Guidelines

Line side L1/L2/L3: 3상 전원 공급 장치 연결; Load side T1/T2/T3: 모터를 연결하세요

보조 접점 (장착된 경우): 을 위한 PLC fault feedback & pilot lamp circuits

Setting rule: Align the dial with the motor rated current on nameplate; avoid long-term setting near the upper limit of the range

✅ 일반적인 문제 해결

  1. Trips immediately on startup: Mostly short circuit. Check motor winding & cable insulation; may also be caused by magnetic trip threshold mismatch
  2. Trips after running for a period: 초과 적재. Verify actual motor current, load condition and thermal setting; check poor heat dissipation
  3. Phase-loss tripping: Check three-phase incoming voltage and loose terminal connections

✅ GV2-ME08C (푸시 버튼 유형)

작업: Push-button start/stop (black START, red STOP)

현재 범위: 2.5~4A; same tripping characteristics as GV2P08C

특징: Small panel cutout; designed for local cabinet operation; no obvious mid-position trip indication

애플리케이션: Standard domestic panel build, 일반 팬 & 물 펌프 (most widely used model)

✅ GV2P08C (Rotary Knob Type)

작업: 회전식 핸들 (knob control)

현재 범위: 2.5~4A (same as GV2ME08C)

주요 기능: Clear trip mid-position; you can distinguish manual opening from fault tripping at a glance; supports external door-mounted extension handle GV2APN

장점: Compliant with UL508 Type E; higher SCCR short-circuit rating; ideal for export equipment, door-mounted operation and strict safety specifications

📋 Comparison Table

목GV2ME08CGV2P08C
작업Push-button start/stopRotary knob handle
여행 표시No dedicated mid-positionLocked mid-position after trip
Door extension handle지원되지 않음Compatible with GV2APN
터미널 유형나사 클램프 (접미사 C)나사 클램프 (접미사 C)
여행 곡선Identical thermal-magnetic curveSame tripping parameters
일반적인 사용법Domestic cabinet local operationExport machines & door-mounted control

Step-by-Step MPCB Selection Guide

Applicable to GV2ME / GV2P thermal-magnetic motor circuit breakers, only for three-phase asynchronous DOL motors; NOT for resistive loads, soft starters or inverter output circuits.

단계 1: Collect 3 key data from motor nameplate

  1. 정격 전류 입력 (most critical)
  2. 정격전압 (typically 380/400V AC three-phase)
  3. 정격 출력 (only for reference; never select purely by power)

Common mistake: Two 1.5kW motors with different pole counts have different rated currents; power-only selection frequently leads to mis-setting.

단계 2: Select the thermal setting range (core rule)

The MPCB adjustment range must fully contain the motor rated current, preferably in the middle third of the range

공식:

Lower limit of breaker range < Motor rated current < Upper limit of breaker range

추천: Place In within 30%~70% of the total range; avoid setting near the upper end

✅ Example: Motor rated current = 3.2A

Select GV2ME08C (2.5~4A); set dial to 3.2A.

❌ If In=3.9A, it still fits but sits close to the upper limit; frequent nuisance tripping will occur under continuous heavy load.

Thermal setting principles

Continuous loads (팬, 물 펌프): Set thermal current = motor nameplate rated current

Long starting inertia (대형 팬, 파쇄기): Increase to 1.05~1.1×In; never exceed 1.1×In

Frequent jogging & shock loads: Do not simply raise the setting; use a separate thermal relay + contactor combination instead

온천 여행: 초과 적재, 잠긴 로터 & 위상 손실 보호 (time-delayed);

자기 여행: Fixed non-adjustable short-circuit protection (13× upper range value, 동시에 일어나는).

단계 3: Choose operation type (푸시 버튼 / 손잡이)

GV2MExxC (push-button, 예를 들어. GV2-ME08C): 저렴한 비용, local cabinet operation, no clear trip mid-position

GV2Pxx (회전식 손잡이): Visible trip mid-position; add external door handle; suitable for export machines & fault identification

단계 4: Choose terminal type

Suffix C: 나사 클램프 단자 (standard for domestic projects)

접미사 3: Spring-cage terminals (no-tool fast wiring; preferred for automated panel mass production)

단계 5: 전압 확인, 차단 용량 & utilization category

  1. 정격전압: Max 690V AC (400V standard)
  2. Short-circuit breaking capacity Icu: Must exceed the prospective short-circuit current at the installation point

Ordinary end circuits in small control cabinets: 100kA@400V of GV2 is sufficient

Circuits close to transformers with high short-circuit current: Add upstream fuses if Icu is insufficient

  1. Utilization category AC-3: Only valid for direct-on-line motor starting

❗ Not applicable: Star-delta starters, 소프트 스타터, inverter output terminals, DC 모터, resistive heating loads, heavy-duty reversing mechanisms.

단계 6: Configure accessories based on control scheme

  1. Local direct start (no PLC): Use MPCB alone with built-in pushbuttons
  2. Remote PLC control: MPCB only for isolation & 보호, paired with contactors; add GVAN auxiliary contacts (1아니요+1NC) for running/fault feedback; add GVAX alarm contacts to separate overload trip from short-circuit trip

Optional extras: Shunt trip GVAD10, undervoltage trip GVAD01, interconnection busbar GV2AF3

단계 7: Exclude unsuitable applications

❌ Inverter output side

❌ DC motors

❌ Resistive loads (히터, 조명)

❌ Frequent forward/reverse operations (prone to false tripping; use separate thermal relays)

❌ Outdoor / 신랄한 / dusty environments (must install inside an IP-rated enclosure)

빠른 선택 요약

  1. Read motor rated current from nameplate (primary data; power is only reference)
  2. Pick a GV2 model whose current range covers In, keep In away from the upper limit
  3. Select operation: Push-button GV2ME / Rotary knob GV2P
  4. Select terminals: Screw C / 봄 3
  5. Check short-circuit current to confirm breaking capacity is adequate
  6. Add auxiliary contacts / trip contacts according to control requirements

Practical Example

모터: 3-위상 400V, 1.5kW, rated current = 3.0A

Current range match: 2.5~4A → GV2ME08C

Set dial to 3.0A

Cabinet local operation without door handle → Push-button type

→ Final model: GV2-ME08C

이전:

답장을 남겨주세요

메시지를 남겨주세요