NV = Earth Leakage Circuit Breaker (ELCB); 250 = 250AF frame size; SV = Standard breaking capacity (S급); 3P = 3-pole; In=250A; AC-type electronic residual current circuit breaker
✅ 핵심 기술 매개변수
프레임 크기: 250의, rated current 250A
폴란드: 3피 (3-폴, 3-위상 3선)
정격 사용 전압 Ue: AC100~440V (compatible with AC380/400/415V)
절연전압 Ui: 440다섯; impulse withstand voltage Uimp: 6kV
차단 용량 (AC400V): Icu=Ics=36kA
Earth leakage sensitivity: 3 adjustable levels: 100/200/500엄마 (select Instantaneous / Time-delayed type when ordering)
트립 단위: 열 자기 여행 (초과 적재 + 단락 보호) + electronic residual current protection
표준: IEC60947-2, GB/T14048.2, CE 인증
치수: W105mm × H165mm × D92mm; standard front wiring
빈도: 50/60헤르츠
📌 Model Code Breakdown
NV: Earth Leakage Circuit Breaker (ELCB); NF = non-leakage standard MCCB
250: 250프레임 크기
SV: S-class Standard breaking capacity; 다른 변형: 이력서 (economic low breaking), HV (높은 차단 용량, 50그만큼)
3피: 3-폴; 4P version available
접미사: J = Instantaneous trip; D = Time-delayed trip (for selective protection against upstream tripping)
🧩 Optional Accessories (Interchangeable within the series)
Auxiliary switch (도끼), Alarm switch (알), 션트 트립 (SHT), 부족전압 트립 (UVT), Extended rotary handle, Rear terminal blocks, Terminal safety covers
📋 모델 선택 & 교체 옵션
- Upgraded model within the same series: NV250-SEV (new WS-V generation, electronic adjustable overload trip, CCC 인증, mainstream stock model for domestic projects)
- High breaking capacity same-frame variant: NV250-HV (Icu=50kA @ AC400V)
- 메모: NV250-SV is an older imported model; NV250-SEV is the domestic mainstream stock model. Direct replacement requires verification of leakage current range, mounting dimensions and accessory interfaces.
- 국내 대체 참고자료: Chint NM1LE-250S, Delixi CDM1LE-250 (similar breaking capacity and leakage logic, but cabinet cutout and accessories are not interchangeable)
⚠️ Application & 문제 해결 팁
애플리케이션 시나리오: Main incoming feeders in 3-phase power cabinets, 팬, water pumps and production lines, with integrated overload, short-circuit and earth fault protection.
3P version only detects 3-phase leakage; single-phase 220V loads with neutral wire are not allowed. Select 4P if single-phase loads exist.
Common fault: 폐쇄 후 즉시 트립. First distinguish between earth leakage trip (leakage indicator pops out) and overload/short-circuit trip. Adjust leakage setting to 500mA to avoid tripping caused by normal equipment residual current.
Maintenance test: Press the built-in leakage test button regularly to verify the residual current function.
📎 Complete Ordering Example
NV250-SV 3P 250A 100/200/500mA J (Instantaneous type)
비교표: NV250-SV / NV250-SEV / NV250-HV (250AF frame, 3P 250A, AC-type ELCB)
All belong to WS-V series; 장착 치수, cabinet cutouts and accessory interfaces are fully interchangeable for direct in-situ replacement.
Core differences: 트립 유닛, breaking capacity and market positioning.
| 목 | NV250‑SV | NV250‑SEV | NV250‑HV |
| 포지셔닝 | Older standard breaking model, 열 자기 여행 | New domestic mainstream model, standard breaking, electronic adjustable overload trip | High breaking model, 열 자기 여행 |
| Icu/Ics @ AC400V | 36그만큼 / 36그만큼 | 36그만큼 / 36그만큼 | 50그만큼 / 50그만큼 |
Full Model List of 미쓰비시 WS-V Series MCCB
- NF (Standard MCCB without earth leakage) & NV (ELCB with earth leakage) — Small & 중형 프레임 (32~250AF)
(1) 32AF 프레임
NF (MCCB): NF32-SV (only S-class available)
NV (ELCB): NV32-SV
(2) 63AF 프레임
NF: NF63-CV (간결한), NF63-SV (기준), NF63-HV (높은 파괴)
NV: NV63-CV, NV63-SV, NV63-HV
(3) 125AF 프레임 (가장 널리 사용됨)
- Thermal-magnetic fixed trip: NF125-CV, NF125-SV, NF125-HV
- Electronic adjustable trip: NF125-SEV, NF125-HEV
- Current-limiting type: NF125-UV, NF125-RV
NV Earth Leakage Breakers: NV125-CV, NV125-SV, NV125-HV, NV125-SEV, NV125-HEV
(4) 250AF 프레임 (Your current model frame)
NF Standard MCCB (No leakage protection)
열자기: NF250-CV, NF250-SV, NF250-HV
Electronic adjustable: NF250-SEV, NF250-HEV
전류 제한: NF250-RV, NF250-UV
NV Earth Leakage Circuit Breakers (ELCB, including NV250-SV)
NV250-CV (경제 버전)
NV250-SV (standard general model, your selected type)
NV250-HV (높은 차단 용량, 50그만큼)
NV250-SEV (electronic adjustable overload)
NV250-HEV (전자 여행 + 높은 차단 용량)
Leakage current settings: 100/200/500mA 3-level adjustable; J=Instantaneous, D=Time-delayed.
- 대용량 전류 프레임 (400~4000AF, Traditional WS Series)
- 400의: NF400-CW / SW / HW; NV400-CW / SW / HW
- 630의: NF630-CW / SW / HW; NV630-CW / SW / HW
- 800~4000AF: NF800~NF4000, NV800~NV4000 (only thermal-magnetic trip; suffix = CW/SW/HW, no SV suffix)
III. Universal Accessory Cross Reference (32/63/125/250의)
| 프레임 크기 | Auxiliary Switch AX | Alarm Switch AL | Shunt Trip SHT | Undervoltage Trip UVT | Locking Cover |
| 32의 | 도끼-05SV | 알-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 63의 | 도끼-05SV | 알-05SV | SHT-05SV | UVT-05SV | LC-05SV |
| 125의 | AX-1SV | AL-1SV | SHT-1SV | UVT-1SV | LC-1SV |
| 250의 | 도끼-05SV | 알-05SV | SHT-05SV | UVT-05SV | LC-2SV |
결론: All accessories for NV250-SV are fully compatible with NF250-CV/SV/HV/SEV/HEV and can be retrofitted on site without factory modification.
- UL Export Models (접미사 U)
NF125-SVU / HVU; NF250-CVU / SVU / HVU
NV125-SVU / HVU; NV250-CVU / SVU / HVU
- Full Ordering Format
- 표준형: NV250-SV 3P 250A J 100/200/500mA (순간여행)
- Selective protection type: NV250-SV 3P 250A D (Time-delayed leakage trip)
- Full set with accessories: NV250-SV 3P 250A + AX+AL+SHT(AC220V)+UVT(AC380V)
- Old-to-New Model Replacement (WS → WS-V Series)
Old model NF250-SGW → New model NF250-SV
Old model NV250-SW → New model NV250-SV
치수, cutouts and accessories are 1:1 interchangeable with no cabinet modification required
접촉기,회로 차단기,감지기,인코더,PLC,변환기