위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

Schneider IPRU40‑40KA Surge Protective Device - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

전기 같은/

Schneider IPRU40‑40KA Surge Protective Device

  IPRU40‑40KA is a Type 2 pluggable AC surge protective device (SPD) from Schneider Electric’s Acti9 series. Key specifications: maximum discharge current 40 kA, nominal discharge current 20 kA, maximum continuous operating voltage 350 V AC. It uses metal oxide varistor (MOV) technology and is suitable for lightning and surge protection in power distribution networks with TT/TN‑S earthing systems. 모델 ...

  • 제품 세부정보

 

IPRU40‑40KA is a Type 2 pluggable AC surge protective device (SPD) from Schneider Electric’s Acti9 series.

Key specifications: maximum discharge current 40 kA, nominal discharge current 20 kA, maximum continuous operating voltage 350 V AC.

It uses metal oxide varistor (MOV) technology and is suitable for lightning and surge protection in power distribution networks with TT/TN‑S earthing systems.

  1. Model Explanation
암호의미설명
IPRU시리즈Pluggable SPD of Schneider Acti9 series, supports hot‑swap module replacement for easy maintenance
40Maximum discharge current (아이맥스)40 kA (8/20 μs waveform)
40KANominal discharge current (~ 안에)20 kA (8/20 μs waveform) (메모: 40KA in model corresponds to In = 20 kA)
350다섯Maximum continuous operating voltage (Uc)350 V AC, suitable for 400 V three‑phase and 230 V single‑phase systems
Number of poles1P+N / 2피 / 3P+N / 4피
  1. Key Technical Specifications
메모
Protection classType 2Complies with IEC 61643‑11:2011 & EN 61643‑11:2012
Discharge currentIn = 20 kA, Imax = 40 kA (8/20 μs)Common mode (CM) & differential mode (DM)
Voltage protection level (Up)≤ 1.8 kV (DM), ≤ 1.4 kV (CM)Low residual voltage
Response time≤ 25 nsNanosecond‑level response
Operating voltageUe = 230/400 V AC, 50/60 HzStandard low‑voltage distribution
Max continuous voltage (Uc)350 V AC (DM), 260 V AC (CM)Stable under grid fluctuations
Ingress protectionIP40 front, IP20 terminalsIndustrial environment suitable
Operating temperature‑25 °C to +60 °CWide temperature range
Mounting35 mm standard DIN railCompatible with Acti9 circuit breakers
배선Max 35 mm², recommended 16 mm² solid / 25 mm² flexibleGood conductivity & heat dissipation
치수Width varies with poles (2피:45 mm, 3P+N:72 mm, 4피:90 mm), H85 mm, D65 mmCompact design
무게대략. 200–450 g (depends on poles)Lightweight
Earthing systemTT / TN‑SNot suitable for TN‑C
  1. Key Advantages & 응용
  2. Advantages

Pluggable design: Hot‑swap module without power interruption

Easy maintenance: Local status indicator (green = normal, red = fault)

High reliability: MOV technology, 긴 서비스 수명, strong anti‑aging

Safe design: Built‑in thermal disconnector to prevent fire risk

Strong compatibility: Fully compatible with Schneider Acti9 series

  1. 일반적인 응용 분야
FieldApplicationProtected Equipment
산업 자동화Workshop power, PLC cabinets, VFDsAutomation equipment, 센서
Commercial buildingsOffices, malls, hotelsLifts, 공조, security, 네트워크
InfrastructureData centers, telecom, transportServers, communication, monitoring
New energyPV inverters, wind convertersPower electronic devices
주거용Distribution boards, smart homesHousehold appliances
  1. 공통 모델 & Pole Configurations
Full ModelPolesOrder No.Application
IPRU40‑40KA 1P+N 350V1P+NA9L040200Single‑phase 2‑wire
IPRU40‑40KA 2P 350V2피A9L040300Single‑phase 3‑wire
IPRU40‑40KA 3P+N 350V3P+NA9L040600Three‑phase 4‑wire
IPRU40‑40KA 4P 350V4피A9L040400Three‑phase 4‑wire (full‑pole)
  1. Selection & 사용법 참고 사항
  2. Coordination: Used as Type 2 protection, cooperate with Type 1 (예를 들어. IPR 120KA)
  3. 극 선택: 3P+N/4P for three‑phase; 2P/1P+N for single‑phase
  4. 설치: Incoming side of main / sub‑distribution board, after circuit breaker
  5. Backup protection: Series 16–32A circuit breaker (breaking capacity ≥ 50 kA)
  6. 배선: Short and thick copper cable, length ≤ 50 cm
  7. Maintenance: Check indicator regularly; replace module when red (typical 5–8 years)
  8. Difference Between IPRU40 & IPRD40
FeatureIPRU40IPRD40설명
Module typeBasic pluggablePluggable with remote indicationIPRD40 supports remote signal
StatusLocal LEDLocal LED + remote contact1 C/O dry contact
Order No.A9L040xxxA9L40xxxDifferent prefix
PriceLowerHigherDue to remote function
  1. Full List of Schneider Surge Protective Devices (Acti9 Series)
  2. Pluggable Type (iPRU / iPRD, Type 2, mainstream)
시리즈모델아이맥스 / ~ 안에UcPolesOrder No.메모
iPRU (Basic)IPRU10‑10KA10 kA / 5 kA350 V1P+N/2P/3P+N/4PA9L010xxxLocal indication
IPRU20‑20KA20 kA / 10 kA350 V1P+N/2P/3P+N/4PA9L020xxxGeneral Type 2
IPRU40‑40KA40 kA / 20 kA350 V1P+N/2P/3P+N/4PA9L040xxxYour model
IPRU65‑65KA65 kA / 30 kA350 V1P+N/2P/3P+N/4PA9L065xxxHigh current
IPRU100‑100KA100 kA / 50 kA350 V3P+N/4PA9L100xxxHigh energy
iPRD (Remote)iPRD10/20/40/65Same as iPRU350 V1P+N/2P/3P+N/4PA9L40xxxWith remote dry contact
  1. Fixed Type (iST / iPR, Type 2)

iST series: iST20, iST40, iST65 (Imax 20/40/65 kA), order no. A9L916xxx

iPR series: iPR20, iPR40, iPR65 (older fixed type, gradually replaced by iPRU)

  1. Type 1 / Combined Type 1+2

iPRF1‑12.5r: Type 1, Imax = 12.5 kA (10/350 μs), 3P+N/4P, A9L012xxx

iPRD1‑15r/20r/25r: Type 1+2, Imax = 15/20/25 kA, 3P+N/4P

  1. Special Series

iPRU‑DC: For PV DC systems (500 V / 1000 V DC)

iPTU: For low‑voltage signal lines

EA9L: Easy9 economical fixed type

  1. Cross‑Brand Replacements for IPRU40‑40KA

(Type 2, Imax = 40 kA, In = 20 kA, Uc ≈ 350 V)

  1. Siemens 5SD7 Series

5SD7462‑6CN: 2피, 40 kA/20 kA, 350 V, pluggable

5SD7464‑6CN: 4피, 40 kA/20 kA, 350 V, pluggable

5SD7466‑6CN: 3P+N, 40 kA/20 kA, 350 V, pluggable

  1. ABB OVR T2 Series

OVR T2 2L 40‑320 P U: 2피, 40 kA/20 kA, 320 V

OVR T2 4L 40‑320 P U: 4피, 40 kA/20 kA, 320 V

OVR T2 3N 40‑320 P U: 3P+N, 40 kA/20 kA, 320 V

  1. Chinese Brands (Cost‑effective)

CHINT NU6‑II 40 kA/20 kA: 350 V, 1P+N/2P/3P+N/4P

DELIXI DZ47Y 40 kA/20 kA: 350 V, all poles

ZHONGLI ZL1‑40/2‑350: Type 2, 40 kA/20 kA, 350 V

III. Schneider Internal Replacements

Downsizing: IPRU20‑20KA (Imax = 20 kA), for low surge environments

Equal replacement: iPRD40‑40KA (with remote signal)

Upgrading: IPRU65‑65KA (Imax = 65 kA), higher surge protection

  1. Selection & Replacement Rules
  2. Match core parameters: 아이맥스, ~ 안에, Uc, Type 2, poles must be consistent
  3. Mounting compatible: 35 mm DIN rail, similar width
  4. Function difference: iPRD / 5SD7 / OVR have remote contacts; iPRU only local indication
  5. System suitable: All for TT/TN‑S, not for TN‑C