LUB12 = Non-reversing power base (base only, cannot work independently!)
It must be plugged together with an LUC series control unit to form a complete integrated 모터 스타터.
모델 코드 설명:
LUB: 파워 베이스
12: 정격 작동 전류 12 에이
접미사 없음: Non-reversing (unidirectional operation only)
Corresponding reversing model: LUB12R (forward & reverse power base)
- 핵심 전기 사양
| 목 | 매개변수 |
| 극 수 | 3P main circuit |
| 기존열전류 Ith | 12 에이 |
| Rated operational current Ie | ≤500V: 12 에이; 690다섯: 9 에이 |
| 정격 사용 전압 Ue | 맥스. 교류 690 다섯 |
| 적합한 모터 (AC-3, 400 다섯) | 5.5 kW |
| 정격 최대 단락 차단 용량 Icu | 50 kA @ 400 다섯 |
| 내장형 보조 접점 | 1아니요 + 1NC (mirror contacts) |
| 터미널 유형 | 나사 터미널 |
| 장착 방법 | DIN 레일 장착 / 나사 고정 |
| 전체 치수 | W45 mm × H154 mm × D126 mm |
| 보호 등급 | IP20 (after wiring) |
| 작동 온도 | -25 ~ +70 ℃ (when matched with LUCA/B/C/D) |
- 매칭 선택 (비판적인)
3.1 제어 장치 (Plugged on top of LUB12)
루카: 기본형 (초과 적재 & 단락 보호)
LUCB: 강화된 보호 (위상 손실, 위상 불균형, 지락 보호)
LUCC / LUCD: Advanced type with measurement & alarm functions
LUCM: Economy basic model
⚠️ Important: The control coil voltage is defined by the LUC model, not the base! Confirm voltage before ordering.
3.2 Optional Extension Modules (Plugged on the side)
LULCxxx: 모드버스 / Profibus communication module
LU9AP0: Auxiliary contact extension
LU9M: Manual operating accessory
- Distinction of Similar Base Models (Avoid Ordering Mistakes)
- LUB12: 나사식 터미널, non-reversing, standard model for general projects
- LUB120: Power base without built-in control terminals
- LUB12R: 12 A reversing power base, for forward/reverse motor operation
- LUB32: Larger frame size in the same series, 32 A power base
- 제품특징
- Modular plug-in architecture: Quick replacement of control unit during maintenance without removing power cables;
- Integrated isolator function: Front rotary handle supports padlocking for safe isolation during maintenance;
- 45 mm narrow width, greatly reduces cabinet space compared with traditional solution (회로 차단기 + 접촉기 + 열 과부하 릴레이);
- Inherent short-circuit breaking capacity; no additional upstream circuit breaker required for most applications;
- Comprehensive motor protection available: 초과 적재, 단락, 위상 손실, 위상 불균형 (subject to selected LUC unit).
- 일반적인 응용 분야
Unidirectional 3-phase asynchronous motors such as fans, 물 펌프, conveyor belts and small air compressors;
Widely used in HVAC, 수처리, packaging machinery and production lines.
- Common Misunderstandings
❌ LUB12 alone cannot be energized! LUC control unit is mandatory
❌ LUB12 cannot realize forward/reverse rotation; select LUB12R for reversing applications
❌ Control circuit voltage is not determined by the base, it depends on the LUC part number
Complete Installation Instructions for 슈나이더 LUB12 (TeSys U Power Base)
- Two Primary Fixing Methods
방법 1: Standard TH35 DIN Rail Clip Mounting (Most Common in Cabinets)
LUB12 is equipped with spring latches on the rear, 호환 가능 35 mm standard electrical TH35-7.5 DIN rail
- Hook the upper latch onto the top edge of DIN rail;
- Press the bottom of the device downwards until an audible click confirms bottom latch engagement;
- Pull the device manually to verify secure installation.
제거: Use a flat screwdriver to pry down the bottom release tab, then lift upwards to detach.
방법 2: Screw Plate Mounting (Cabinets without DIN rail)
Mounting holes are reserved on the housing for direct screw fixing on metal backplates;
Suitable for non-standard enclosures and renovation projects without DIN rails.
- Mandatory Installation Orientation Rules
✅ Recommended: Vertical upright mounting (front facing operator, terminals top & 맨 아래)
Upper terminals: L1/L2/L3 3-phase power supply incoming
Lower terminals: T1/T2/T3 motor outgoing
Natural downward airflow for heat dissipation, complying with original design.
⚠️ Allowable tilt angle: ≤±30° forward/side tilt;
❌ Horizontal mounting & upside-down installation are forbidden, which impairs heat dissipation and causes inaccurate thermal protection.
- Plug-in Procedure for LUC Control Unit (Top Module)
LUB12 is merely a base; LUC series control unit is required for operation
- Complete LUB12 base fixing; install control unit before wiring;
- Align LUC unit with the upper guide slot of the base and push vertically downward;
- Confirm audible latch engagement and no loose movement;
- If communication modules (LULC) or auxiliary contact modules are required, plug them into the right-side expansion slot of the base.
Removal of LUC unit: Press the front release buckle and pull upward directly, no need to disconnect power cables (major modular maintenance advantage).
- 배선사양 & Torque Requirements
| Circuit | Terminal Location | 조임 토크 | 적합한 케이블 |
| Main power circuit L1/L2/L3, T1/T2/T3 | 높은 & lower power terminals | 1.9~2.5 N·m | 1~10 mm² solid cable / 1~6 mm² flexible cable (ferrule terminal recommended) |
| 제어 / auxiliary circuit terminals | Side terminals | 0.8~1.2 N·m | 0.75~1.5 mm² cable |
⚠️ Strict prohibition of reversed wiring: Power at top, motor cable at bottom; do not swap inlet and outlet.
- Cabinet Heat Dissipation & Layout Clearance
- Side-by-side installation of multiple LUB12: Zero clearance between adjacent units is permitted;
- Vertical stacked installation: Maintain ≥50 mm ventilation gap between upper and lower devices;
- Avoid mounting directly adjacent to heat-generating components such as contactors and inverters;
- Maximum ambient temperature: -25 ~ +70 ℃ with LUCA/LUCB/LUCC/LUCD; 최대 +60 ℃ with LUCM.
- Common Installation Pitfalls & Taboos
- ❌ Do not install LUB12 base without LUC control unit — device cannot close contacts;
- ❌ Do not insert LUC unit obliquely or forcibly, to avoid bending internal pin connectors;
- ❌ Do not over-tighten terminals (risk of thread slipping & housing cracking); insufficient torque causes overheating and terminal burnout;
- ❌ Extension modules can only be fitted on the right side; no expansion interface on the left;
- ❌ Avoid direct installation under heavy vibration; vibration damping measures are required if necessary;
- ✅ Reserve sufficient front operating space for the padlockable isolating rotary handle to prevent cabinet door interference.
Installation Precautions for Schneider LUB12 (TeSys U Power Base)
- Mechanical Installation Requirements
- Installation Attitude Restriction (Hard Rule)
표준 장착: Vertical upright, main terminals arranged top to bottom, power cable on top, motor cable on bottom.
Permitted inclination: forward/side tilt ≤±30°;
❌ Horizontal and upside-down mounting prohibited, resulting in poor heat dissipation, false thermal tripping and shortened service life.
- Fixing Requirements
DIN 레일 장착: Securely clip onto standard TH35 rail, 흔들림 없음; release with flat screwdriver when removing.
나사 장착: Use reserved mounting holes; do not drill extra holes to damage housing.
- Cabinet Spacing & 열 방출
Horizontal side-by-side mounting: No gap required between units;
Vertical stacked layout: Reserve ≥50 mm vertical ventilation space;
Keep away from high heat components such as inverters and power resistors; ensure ambient temperature within rated range.
- Operating Space Reservation
The front isolator rotary handle supports padlocking; reserve enough front clearance to avoid cabinet door blocking rotation and lockout operation.
- 진동 환경
Vibration damping measures are recommended for equipment mounted on vibrating machinery, preventing loose terminals and module disengagement.
- Module Assembly Guidelines
LUB12 works only when matched with LUC control unit
- Slide LUC control unit vertically along guide track and push until audible lock; avoid angled or forced pressing to prevent pin damage.
- Communication modules (LULC) and auxiliary contact expansion modules can only be installed on the right expansion slot; no interface on left side.
- Disconnect upstream power supply before plugging/unplugging LUC unit for maintenance; press front latch and lift upward; no need to remove power cables.
- Never plug/unplug LUC unit under live condition, which will damage internal circuits.
- Wiring and Torque Rules (High Failure Risk Area)
| Circuit | 조임 토크 | 케이블 사양 |
| Main terminals L1/L2/L3, T1/T2/T3 | 1.9~2.5 N·m | 1~10 mm² solid wire; 1~6 mm² flexible wire (ferrule terminal strongly recommended for flexible cable) |
| Side auxiliary / control terminals | 0.8~1.2 N·m | 0.75~1.5 mm² conductor |
⚠️ Critical Wiring Restrictions
- Main circuit rule: Power enters top terminals, motor connects bottom terminals; power and motor cables must not be reversed!
- Bare flexible wires without cable ferrules easily cause strand scattering and short circuit;
- Insufficient torque → overheating and terminal burnout; excessive torque → thread slipping and plastic housing cracking;
- No exposed copper strands after wiring to prevent phase-to-phase short circuit; maintain IP20 protection degree.
- 환경 & 전기적 요구 사항
- Operating environment: No explosive atmosphere, 부식성 가스, and continuous condensation;
LUCA/LUCB/LUCC/LUCD: -25 ℃ ~ +70 ℃
LUCM economy type: -25 ℃ ~ +60 ℃
- Derating is required when operating altitude exceeds 2000 중.
- Verify coordination between upstream protective devices and short-circuit breaking capacity of LUB12.
- Ensure reliable earthing of control cabinet and motor complying with grounding regulations.
- 안전 & Commissioning Taboos
- ❌ LUB12 base cannot operate without fitted LUC control unit; motor cannot start.
- ❌ LUB12 is non-reversing base, not applicable for forward/reverse motor control; select LUB12R for reversing duty.
- ❌ Do not open housing or touch live internal parts under energized state.
- Check before closing: Set overload protection current of control unit according to motor rated current on nameplate.
- The front rotary handle provides isolation function; turn to OFF position for maintenance and apply lockout/tagout.
- 저장 & 운송
Keep dry during storage before installation; avoid long-term sunlight and humidity. Do not lift the device by gripping LUC control unit to prevent module detachment and damage.
Compatible Motors for Schneider LUB12 (TeSys U Power Base)
핵심 결론
LUB12 has no restrictions on motor brands! Compatibility depends only on electrical parameters and motor type, regardless of manufacturer.
It is merely a switching base for three-phase AC circuits. Any brand of three-phase AC asynchronous motor can be applied if all conditions below are satisfied.
- 적용 모터 (Brand Independent)
✅ Compatible Motor Brands (All Supported)
국내의: Wannan Motor, Baude Motor, Jiamusi Motor, Lijiu Motor, Wolong Motor, Dazhong Motor;
수입됨: 지멘스, 씨줄, 꿰매다, 파편, Toshiba, 미쓰비시, Hitachi three-phase asynchronous motors;
Schneider original motors are also fully compatible. There is no binding requirement to use Schneider motors only.
✅ Mandatory Electrical Conditions (All Must Be Met)
- 모터 유형: Three-phase squirrel-cage asynchronous motor (direct-on-line mains start)
- 전원공급장치: 교류 50/60 헤르츠, operating voltage ≤690 V
- 모터 정격 전류: ≤12 A (최대. compatible motor 5.5 kW @400 V)
메모: Rated allowable current derates to 9 A under 690 V 시스템.
- Operating condition: Unidirectional non-reversing operation (LUB12 non-reversing base; select LUB12R for forward/reverse control).
- 제어 모드: 직접 온라인 (DOL) mains starting.
- Inapplicable / Restricted Motor Types
❌ Forbidden for Direct Driving
- Permanent magnet synchronous motor: Normally driven by inverter; overload protection characteristics of LUC unit do not match permanent magnet motors, and cannot start directly from mains.
- Wound rotor asynchronous motor (rotor resistance speed regulation type): Protection logic mismatch.
- Single-phase motor, DC 모터.
- 서보 모터, inverter-duty motor: Controlled by inverter output; LUB12 cannot be connected on inverter output side.
⚠️ Important Reminder: Inverter-duty motor can only use LUB12 on the power input side as an isolator. LUB12 is strictly prohibited on inverter output terminals! High-frequency PWM voltage will damage contacts and control unit.
- Key Configuration Points for Cross-Brand Motor Application
- LUC control unit must be matched; LUB12 base cannot work independently.
- Accurately set overload protection current of LUC unit according to rated current printed on motor nameplate.
- For motors with high starting inrush current (공기 압축기, high-pressure pumps), prefer LUCB/LUCC advanced control units with phase loss and phase unbalance protection.
- When replacing motors of different brands, only readjust the LUC current setting; no replacement of the base required.
- Common Misconception Clarification
- ❌ Myth: Schneider motor starters can only be matched with Schneider motors
✅ Correction: TeSys U is a universal IEC standard motor starter. It is widely used with domestic and other foreign-brand motors in industry; no brand lock-in.
- ❌ Myth: Motors with power close to 5.5 kW are always suitable
✅ Correction: Priority reference: 정격 전류. Some multi-pole and special motors have higher current at the same power rating and cannot be used if exceeding 12 에이.
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지























NH42-63-318x560.png)