MLFB Order Code Breakdown
3RW 44 43 6 B C 4 4
- 3RW: SIRIUS soft starter product series
- 44: High-performance built-in bypass 3-phase fully controlled 소프트 스타터 (independent thyristor regulation per phase, integrated bypass contactor as standard)
- 43: 사이즈 코드, 정격 전류 203 에 40 °C for standard loads
- 6: Control circuit terminal type = screw terminals; main circuit connected via copper busbars
- 비: Integrated bypass contactor (2/3-phase bypass for zero loss during steady-state operation)
- 기음: Independent 3-phase thyristor control (full 3-phase control to balance 3-phase currents)
- 4: Control supply voltage Us = AC 230 다섯
- 4: Main circuit operating voltage Ue = AC 200~460 V
- 핵심 전기 매개변수 (40 ℃, 수업 10 표준 부하)
| 목 | 매개변수 값 |
| Rated current for standard wiring (motor directly connected to soft starter) | 203 에이 |
| Matched motor power at 400 다섯 | 110 kW |
| Rated current for inside-delta connection (motor windings split into two branches) | 352 에이 |
| Matched motor power at 400 V for inside-delta wiring | 200 kW |
| 주회로 전압 범위 | AC 200~460 V (50/60 헤르츠) |
| Control supply | 교류 230 V ±10% |
| Phase control mode | Anti-parallel thyristors per phase with independent regulation |
| Standard functions | Integrated bypass contactor to bypass thyristors during running |
| Standard overload trip class | 수업 10; 수업 10/20/30 configurable manually |
| 보호 기능 | 위상 손실, 위상 불균형, 모터 과부하, 과열, thyristor short-circuit, start timeout, earth fault detection |
| Communication expansion | Profibus DP compatible (requires 3RW4900-0KC00 communication module) |
| 무게 | 대략. 11.2 kg |
| 원산지 | 독일 |
III. 부하 매칭 & Selection Limits
- 적용 하중
워터 펌프, 팬, 벨트 컨베이어, 공기 압축기, 냉각기, centrifugal equipment (고정 속도, only smooth start/stop required)
- Derating Reference for Heavy-Duty Operation (40 ℃)
수업 20 헤비 듀티 (빈번한 시작, high starting torque): permissible current 170 에이, matched motor 90 kW
수업 30 extra heavy duty (볼밀, 파쇄기): permissible current 145 에이, matched motor 75 kW
- Prohibited Operating Conditions
Continuous speed regulation, frequent forward/reverse switching, high-frequency jogging (≥30 times per hour)
- Hardware Structure & 배선 설명
- 주회로: Copper busbar terminals; L1/L2/L3 line side input, T1/T2/T3 motor side output; supports standard wiring and inside-delta wiring
- 제어 회로: Screw terminals for start/stop signals, fault outputs, 다시 놓기, external thermistor input
- 조작 패널: Built-in LCD display for setting start ramp, initial voltage, 소프트 스톱, current limit and protection thresholds
- 설치: 수직 벽 장착; minimum 150 mm top/bottom clearance for heat dissipation; ambient temperature 0~40 °C (derate for temperatures above 40 ℃)
- 제품 수명주기 & 교체 모델
- 상태: 3RW44 series discontinued (PLM: PM490 end-of-support phase); original manufacturer stops mass production, only stock spare parts available
- Direct OEM Replacement Model (Recommended for New Projects)
3RW5543-6HA14 (new-generation 3RW55 series, same 203 정격 전류, 230 V control supply, 200-460 V main voltage, 나사 터미널, 통합 바이패스)
- Differences Between Old & 새로운 모델
Smaller footprint, 낮은 전력 소비, native Modbus RTU and optimized protection logic for 3RW55
Different mounting cutout dimensions; copper busbars and mounting brackets need modification during cabinet retrofit
- Recommended Matching Protection Devices
- Main Circuit Short-Circuit Protection: Moulded case circuit breaker matched to 110 kW motor circuit
- Specialized Thyristor Protection: aM/gR ultra-fast fuse 500 다섯 315 에이 (mandatory upstream of soft starter, no thyristor short-circuit protection without it)
- Additional Motor Protection: External PTC thermistor connectable to control terminals for winding overtrip protection
Ⅶ. 일반적인 문제 해결 매트릭스
| 결함 증상 | 근본 원인 | 해결책 |
| Overheating alarm during startup | Blocked cooling air duct / ambient temp above 40 ℃ / long-duration heavy-load startup | Clean dust, 캐비닛 환기 개선, upgrade to higher-rated soft starter |
| Phase loss alarm | Single-phase power loss, loose busbar connection, broken motor winding | 배선을 조이세요, measure 3-phase input voltage and motor winding resistance |
| Unrestricted starting current, direct full voltage output | Broken-down thyristors, welded bypass contactor contacts | Disconnect power supply to test thyristors; replace bypass contact module |
| Startup timeout trip | Too low initial voltage, seized mechanical load, insufficient ramp time | Increase initial voltage, inspect mechanical load, extend start ramp time |
Ⅷ. 주요 장점
- Independent 3-phase voltage regulation; eliminates 3-phase current unbalance common in 2-phase soft starters, extending motor bearing service life
- Integrated bypass eliminates thyristor power loss during steady operation, delivering over 98% energy saving vs non-bypass models
- Supports soft stop and pump stop water hammer suppression, ideal for water supply, drainage and HVAC systems
- Comprehensive integrated motor protection, eliminating the need for separate thermal overload relays
Full Dimension Specifications of 지멘스 3RW4443-6BC44
- Overall Equipment Dimensions (폭 × 높이 × 깊이, 단위: mm)
210 (너비) × 230 (키) × 298 (깊이)
- 장착 컷아웃 & Fixing Dimensions
- Horizontal center distance between mounting holes: 167 mm
- Vertical center distance between mounting holes: 190 mm
- Fastener specification: M8 bolt, 조임 토크 15 N·m
- Cabinet panel cutout minimum reserved width ≥210 mm, height ≥230 mm
III. Mandatory Minimum Cabinet Clearance for Heat Dissipation (Vertical Wall Mount)
Top clearance: ≥100mm
Bottom clearance: ≥75 mm
Side clearance (multiple units side-by-side): ≥5 mm
Equipment rear surface to cabinet backplate: direct contact permitted
- Outer Carton Dimensions (창고 & Logistics Reference)
348 × 433 × 394 mm, net weight 11.22 kg
- 보충 노트
- 보호 등급: IP00; for cabinet installation only
- All 3RW4443 variants (-6BC34/-6BC44/-2BC45) share identical overall dimensions; differences only in control terminals and supply voltage
- Replacement model 3RW5543-6HA14 has a smaller footprint; recalculate cabinet cutout size for retrofits
전체 목록 & Function Definition of Control Terminals – Siemens 3RW4443-6BC44
This model is equipped with screw-type control terminals, categorized into five groups: 제어 전원 공급 장치, 디지털 입력, motor PTC temperature sensing, 프로그래밍 가능한 릴레이 출력, general fault relay.
- Control Power Supply Terminals (Unit Main Supply)
- A1, A2
기능: Main control power supply for soft starter
Model rating: 교류 230 V ±10%, 50/60 헤르츠
Wiring rule: A1 live line L, A2 neutral line N
- 체육
Control circuit protective earth terminal; connect to cabinet earth busbar
- L+, 엘-
Built-in internal DC24 V auxiliary supply for passive digital input switches; 외부 24 V power supply not required
L+ = DC24 V positive pole; L= DC24 V negative pole (공통점)
- 4 Programmable Digital Input Terminals IN1 / IN2 / IN3 / IN4
논리: Connect one end of switch to L+, the other end to corresponding INx to trigger assigned function; all functions configurable via panel parameters
Factory Default Allocation
IN1: Motor start (Parameter Group 1 forward rotation)
IN2: Unassigned
IN3: Unassigned
IN4: Fault trip reset
All Customizable Functions
Local manual mode, emergency start, low-speed creep, fast emergency stop, fault reset, 3 groups of forward/reverse motor parameter switching
III. Motor Winding Temperature Sensing Terminals T1, T2
For external motor PTC thermistor connection (motor overheat protection)
Soft starter trips automatically when winding temperature exceeds threshold
Short-circuit T1 and T2 if no PTC fitted to disable thermal protection
- 3 Independent Programmable Relay Outputs (Passive dry contacts, AC250 V / 5 에이)
Each pair consists of normally-open contacts with fully assignable functions via parameter menu
- 13, 14 산출 1
기본: Motor running signal (closes after startup completion and bypass contactor pull-in)
- 23, 24 산출 2
기본: Unassigned; configurable for bypass status, startup-in-progress, 사전 알람, DC braking, 등.
- 33, 34 산출 3
기본: Unassigned; customizable for all types of equipment status signals
- General Fault Relay Terminals 95, 96, 98 (Global Fault Alarm)
3-pole changeover contact for unified fault signaling, widely used in safety circuits
95: Common terminal COM
95-96: 평상시 닫힘 (NC): conductive when unit healthy; opens upon fault trip
95-98: 평상시 열림 (아니요): closes when fault occurs, for fault indicator light / alarm horn wiring
Terminal Summary Table
| Terminal Group | 터미널 번호 | Core Purpose |
| 제어 전원 공급 장치 | A1, A2 | AC230 V control voltage input |
| Protective Earth | 체육 | Control circuit grounding |
| 내장 24 V Supply | L+, 엘- | DC24 V power for digital inputs (positive / ground) |
| 디지털 입력 | IN1, IN2, IN3, IN4 | Start/stop, 다시 놓기, parameter switchover, manual mode etc. |
| PTC Temperature Sensing | T1, T2 | Motor winding overheat thermistor interface |
| 릴레이 출력 1 | 13, 14 | Motor running status (평상시 열려 있음) |
| 릴레이 출력 2 | 23, 24 | Customizable equipment status (평상시 열려 있음) |
| 릴레이 출력 3 | 33, 34 | Customizable equipment status (평상시 열려 있음) |
| Fault Changeover Contact | 95, 96, 98 | Global fault alarm (COM + NC + 아니요) |
Supplementary Wiring Guidelines
- Tightening torque for control wires: 1.2~1.5 N·m; wire cross-section 0.75~1.5 mm² copper conductors
- Digital inputs are passive contact type; power solely from internal L+/Lwithout external PLC 24 V 공급
- Series the normally closed 95/96 contacts in safety circuit to cut upstream contactor power on fault
- Profibus communication requires separate 3RW4900-0KC00 module with dedicated port (not part of front control terminals)