Siemens 3TK2827-1BB41 Safety Relay

상태: 단종 (단종). It belongs to the legacy 3TK28 series of basic safety units. 24 V DC 공급, 나사 터미널, monitored start, adjustable off-delay 0.05~3 s. ✅ Model Code Definition 3TK: SIRIUS safety relay series 28: Safety relay module 27: 2 instantaneous NO safety outputs + 2 delayed NO safety outputs, plus 1 NC signal ...

  • 제품 세부정보

상태: 단종 (단종). It belongs to the legacy 3TK28 series of basic safety units. 24 V DC 공급, 나사 터미널, monitored start, adjustable off-delay 0.05~3 s.

✅ Model Code Definition

3TK: 천랑성 안전 릴레이 시리즈

28: Safety relay module

27: 2 instantaneous NO safety outputs + 2 delayed NO safety outputs, plus 1 NC signal feedback contact

1: Monitored start (external reset pushbutton mandatory)

BB: DC24V

4: 나사 터미널

1: Delay version 0.05~3 s (접미사 40 for same series = 0.5~30 s)

📋 Core Technical Specifications

사양
공급DC24V (0.85~1.1Un)
안전 출력2순간적 없음 + 2NO off-delay
Signal Contact1NC for fault/status feedback
지연 범위0.05 … 3 s adjustable via front potentiometer
시작 모드Monitored start (controlled reset); auto-start not supported
안전등급SIL3 / PL 전자 (EN ISO13849-1). EN954-1 Category4 for instantaneous circuit; Category3 for delayed circuit
설치DIN 레일, 45 mm 폭
보호Housing IP40, terminals IP20
배선나사 터미널, conductor 0.5~4 mm²
애플리케이션비상 정지, safety gate monitoring; Stop Category 0/1 (EN60204)
확장 가능Compatible with external 3TK2830 contact expansion module to increase safety output capacity

🛠️ Typical Application Scenarios

Dual-channel safety signal evaluation for emergency stop and safety guard doors, where delayed disconnection is required (inertial motor stop; delay before cutting off power circuit).

Dual-channel input with contact welding self-test and positively driven / force-guided contact structure, complying with machinery safety certification.

🔁 Replacement Selection (Discontinued Substitution)

The entire legacy 3TK28 series is superseded by the new generation 3SK1/3SK2 safety relays:

Recommended direct equivalent: 3SK1121-1CB42 (24VDC, monitored start, 2 instantaneous NO + 2 delayed NO, 0.05–3s delay)

⚠️ 경고: Terminal assignment and layout differ from 3TK2827-1BB41. Not a direct plug-and-play replacement. Rewiring and full safety loop reassessment are mandatory.

📌 Troubleshooting Checklist (중고 / Installed Units)

  1. No output after power-up: Check reset circuit (Y33/Y34 monitored start terminals, external reset button required)
  2. Cannot reset: Verify consistency of dual-channel safety inputs; check for single-channel wire breakage
  3. Delay failure: Aged front potentiometer or damaged internal timing circuit
  4. 접촉용접: Load exceeds AC15/DC13 rated capacity; front-end fuse protection required
  5. Second-hand inspection: Static continuity test on contacts; power-on test for dual-channel safety cut-off, timing function and reset logic

📎 Customs HS Code

85364900 (Electromagnetic safety relay, electrical switching apparatus)

⚠️ Important Notice

Only surplus stock or used spare parts are available. 3TK legacy series is not recommended for new projects; select 3SK1 directly. 교체 후, full validation of the machine safety circuit must be performed.

지멘스 3TK2827-1BB41 Safety Relay Overall Dimensions (DIN rail mounted unit)

Official datasheet dimensions: W × H × D = 44.8 mm × 138.5 mm × 120 mm

Engineering notation: 45mm(여) ×138.5mm(시간) ×120mm(디). 45 mm is standard DIN rail module width.

너비(여): 44.8 mm (명사 같은 45 mm on panel)

키(시간): 138.5 mm (including top and bottom terminals)

깊이(디): 120 mm (from DIN rail backplate to front face)

설치: DIN rail snap-on mounting, 또는 나사 고정; any mounting orientation permitted

순중량: 대략. 0.457 kg (same for all 3TK2827 variants)

📌 Cabinet layout note:

Reserve 45mm width occupancy on cabinet rail; depth ≥120 mm plus extra clearance for wiring.

The replacement model 3SK1121-1CB42 has a smaller footprint, so installation space must be rechecked for cabinet retrofits.

Working Principle of Siemens 3TK2827-1BB41 Safety Relay

Core definition: Dual-channel redundant, force-guided contacts, 오프 딜레이, monitored start (controlled reset) safety evaluation module. Used for E-stop / safety gates to achieve EN60204 Stop Category 1 (controlled shutdown: brake first with delay, then cut main power).

  1. Internal Hardware Composition
  2. DC24V power supply unit (A1/A2)
  3. Two independent redundant safety input channels (Y11-Y12 / Y21-Y22): Dual-channel detection, connected to NC contacts of E-stop or safety door switches
  4. Two sets of independent internal force-guided relays, mutually cross-checked. A single fault will not result in loss of protection.
  5. Electronic timing circuit (front potentiometer adjustable 0.05~3s, 오프 딜레이)
  6. Monitored start circuit Y33/Y34: Detects the falling edge of the reset pushbutton (triggered on button release), and detects short-circuit faults on reset wiring
  7. Output contacts

2NO instantaneous safety outputs (13-14, 23-24): Immediately open when safety signal trips; meets EN954-1 Category4

2NO delayed safety outputs (47-48, 57-58): Open after preset time once safety signal trips; Category3

1NC status feedback signal contact (31-32): 잘못 / stop status signal for PLC diagnostics

Force-guided contact principle: NO and NC contacts are mechanically interlocked via rigid linkage. Even if NO contacts weld and stick closed, the mechanical linkage ensures the NC contacts cannot close, enabling detection of contact welding faults. This is the key difference between safety relays and standard relays.

  1. Complete Operating Logic (4 스테이지)

Stage 1: Power-up Standby

DC24V applied to A1/A2, POWER LED illuminates. Both safety input channels Y11-Y12 and Y21-Y22 must be fully closed (E-stop released, safety gate closed).

The module continuously compares the status of both channels. Mismatched channel states → fault detected, outputs locked off. Cross-wire short-circuit detection is also active.

Stage 2: Monitored Start (Key Feature)

Auto-start is NOT available!

With safety inputs fully closed, the external reset pushbutton (Y33/Y34) must be pressed and released. The module detects the falling edge pulse upon button release to enable internal relay energization.

Protection logic: If Y33/Y34 wiring is permanently shorted, the module identifies a fault and refuses startup to prevent unexpected machine auto-restart.

✅ After successful startup:

Instantaneous NO contacts (13-14, 23-24) 닫다

Delayed NO contacts (47-48, 57-58) 닫다

31-32 NC remains closed (normal running signal)

Stage3: Safety Trip (E-stop pressed / safety gate opened)

If either of dual safety input channels opens → module triggers hazardous state:

  1. Instantaneous outputs (13/14, 23/24) open immediately, cutting brake / 제어 회로;
  2. Internal timer starts countdown (0.05~3초);
  3. When countdown completes, delayed outputs 47/48, 57/58 open to disconnect main contactors, allowing time for motor inertial stop and braking;
  4. 31-32 NC contact opens to output fault / stop signal externally.

Typical use case: High inertia motors; cut control circuit to initiate braking first, then main power after delay, complying with Stop Category1 controlled shutdown.

Stage4: Fault Latch, Manual Reset Mandatory

After E-stop reset / safety gate re-closed, outputs will NOT recover automatically.

Faults must be cleared, then reset pushbutton pressed again. The module runs self-test before reactivating outputs.

If internal faults including contact welding, channel mismatch or wiring short-circuit are detected, the module latches permanently. Power cycling cannot reset; hardware faults must be investigated.

  1. Safety Mechanism (안전 장치)
  2. Dual-channel cross-check: Real-time comparison of two input channels; mismatch triggers immediate shutdown and latch
  3. Force-guided contact self-test: Contact adhesion checked on every operation
  4. Wiring short-circuit detection: Detects cross-short faults on safety and reset wiring
  5. De-energize-to-safe state: All safety outputs open upon loss of supply voltage
  6. Fault latching: Hold shutdown state after fault, preventing automatic restart and secondary hazards
  7. Safety Rating Description

Instantaneous output circuit: 안에 954-1 범주 4, SIL3, PL 전자

Delayed output circuit: 안에 954-1 범주 3, SIL2, PL d

이유: Timing electronics are single-channel, hence lower safety rating for delayed outputs.

  1. 일반적인 오해
  2. Do NOT short to single-channel wiring; redundancy is lost and safety rating invalidated
  3. Monitored start ≠ auto-start; reset pushbutton must supply pulse signal. Permanent short of Y33/Y34 is forbidden
  4. Delay is OFF-Delay (de-energization delay), NOT power-on delay. Timer starts only after safety trip.
  5. Fault Determination Logic List (3TK2827-1BB41)

Once the module detects any of the following faults, safety outputs latch open. Most faults cannot be cleared by power cycling. Fault must be rectified before performing monitored reset.

  1. Safety Input Channel Faults (Y11-Y12 / Y21-Y22 dual channels)
  2. Single channel wire break: Mismatched channel states (one open, one closed) → immediate output cut-off and latch.
  3. Dual channels open simultaneously: Normal E-stop / safety gate trip, classified as normal shutdown, not hardware fault. After safety circuit recovery, reset required for restart.
  4. Cross short-circuit between dual channels (Y11 shorted to Y21, Y12 shorted to Y22): Module detects wiring short-circuit, rejects startup or trips and latches.

✅ Key rule: Safety loop must use two independent NC contacts; external parallel connection is not permitted.

  1. Reset Circuit Faults (Y33-Y34, monitored start terminals)
  2. Permanent short across Y33/Y34 (reset wiring shorted): Module identifies fault and blocks startup.

원칙: Monitored start relies on detecting falling edge of button release. Continuous short is treated as wiring fault to prevent power-on auto-start.

  1. Reset button stuck closed with no pulse: Even if safety loop is healthy, startup cannot be triggered after power-up.
  2. Reset circuit wire break: Reset pulse cannot be received; module fails to start.

III. Internal Relay Contact Faults (Force-guided contact self-check)

  1. Welded internal safety output contacts: Detected by self-test on each operation, outputs latched off.

징후: Safety input opens, but internal contacts remain welded. Module latches after fault detection; power cycle will not recover. Module replacement required.

  1. Mismatched status between the two internal redundant relays → fault latch.
  2. Supply Related Faults (A1/A2 DC24V)
  3. Supply voltage below 0.85Un (DC20.4V): Module unstable; safety outputs open (fail-safe characteristic).
  4. Voltage fluctuation or pulse interference: May trigger unintended shutdown; DC24V power buffer / fuse recommended.
  5. Delay Circuit Faults
  6. Damaged front potentiometer: Fixed delay value or zero delay. Usually will not trigger latch, but function lost, safety assessment invalid.
  7. Failed timing circuit: Delayed outputs fail to open upon safety trip; hazardous failure. Module must be replaced.
  8. Table to Distinguish Normal Shutdown vs Fault Trip
현상유형치료
E-stop pressed / gate opened → outputs open; restore safety loop then reset to restartNormal safety shutdownRemove hazard, reset and restart
전원 켜기, safety loop fully closed, reset button pressed with no response, cannot startFault latchCheck dual channels, reset wiring, cross shorts
Intermittent shutdown; reset allows short run before tripping againIntermittent fault느슨한 배선을 확인하십시오, aged contacts, supply voltage drop
Fault latched; power cycle still cannot resetSevere fault (contact welding / internal damage)Replace safety relay immediately; do not continue operation

⚠️ Safety Warning

In case of latched fault due to internal contact welding, bypassing the safety relay or shorting outputs to force startup is prohibited. This removes safety protection and violates EN ISO13849.