Siemens 3UG4501-2AW30 레벨 모니터링 릴레이

Technical Specification of Siemens 3UG4501-2AW30 Level Monitoring Relay 3UG4501-2AW30 is a mainstream resistance-type level monitoring relay of the Siemens SIRIUS series. It features dual-level control for upper and lower limits, adopts industry-standard DIN rail mounting and spring-cage terminals, and supports wide-range power supply of 24~240V AC/DC. Widely applied to industrial water tanks, sewage pools, 화학적인 ...

  • 제품 세부정보

Technical Specification of 지멘스 3UG4501-2AW30 Level Monitoring Relay

3UG4501-2AW30 is a mainstream resistance-type level monitoring relay of the Siemens SIRIUS series. It features dual-level control for upper and lower limits, adopts industry-standard DIN rail mounting and spring-cage terminals, and supports wide-range power supply of 24~240V AC/DC. Widely applied to industrial water tanks, sewage pools, chemical storage tanks and other facilities, it realizes high/low level alarm, automatic water filling and draining, as well as overflow and dry-run protection. It is also a highly searched and widely used control component for level monitoring in industrial control sites.

  1. Model Code Decoding (Core Basis for Model Selection)

Each character of the model represents hardware, function and structural attributes, which is the key to distinguish products in the same series. The detailed breakdown is as follows:

코드 세그먼트CharacterDetailed Definition & Technical Notes for Selection
3UG3UGStandard monitoring relay series of Siemens SIRIUS, specially designed for analog, level and resistance signal monitoring
44제품 유형: Analog monitoring unit focusing on resistance/level signal acquisition, differentiated from current and voltage monitoring models
55Housing width: Compact 22.5mm design, compatible with standard control cabinet rails to save installation space
11하드웨어 버전: Standard universal version without customized functions, featuring large market circulation and high compatibility
22Control points: 2-point control (upper limit + lower limit) for simultaneous high and low level monitoring; 손가락 1 stands for single-point control
에이에이기능 유형: Dedicated for level/resistance monitoring, no additional delay or communication expansion modules
터미널 유형: Spring-cage terminal, enabling fast wiring and excellent vibration resistance, ideal for sites with frequent maintenance and severe vibration; Letter A refers to traditional screw terminal
3030Basic specification code: Standard circuit structure without customized voltage or contacts

기술 노트: Prioritize distinguishing “2/1” (control points) 그리고 “W/A” (터미널 유형) during selection. Spring-cage terminals (여) are recommended for pump rooms with heavy vibration and outdoor control cabinets.

  1. 핵심 기능 & 작동 원리

2.1 핵심 기능

This level monitoring relay collects the equivalent resistance of conductive liquid via electrodes to implement two major control functions:

Dual-threshold monitoring: Independent settings for upper level limit and lower level limit. The contacts will act once the level exceeds the set limits to trigger alarms or interlock water pumps and valves.

Anti-chatter delay: Built-in adjustable operating delay ranging from 0.5s to 10s, which filters liquid level fluctuation and transient electrode interference to avoid frequent false tripping.

전기 절연: Complete isolation between the input monitoring circuit and output contact circuit, delivering strong anti-interference performance for sites with inverters, motors and other high-interference equipment.

2.2 작동 원리

The liquid level of conductive fluid changes the contact area between electrodes, thus generating different equivalent resistance (measuring range: 2kΩ ~ 200kΩ). The internal circuit of the relay collects resistance signals in real time and compares them with preset thresholds. A resistance value below the lower threshold is judged as low liquid level, while a value above the upper threshold is judged as high liquid level. 마지막으로, the changeover contacts are driven to complete on-off control.

  1. Full-range Technical Parameters (Including Operating Boundary Notes)
매개변수 카테고리명세서Technical Explanation & Boundary Reminders
Measuring ParametersMonitoring resistance range: 2 kΩ ~ 200 kΩSuitable for clean water, sewage and weakly acidic/alkaline conductive liquids. Not recommended for liquids with high concentration of acid and alkali beyond the measuring range
Power Supply Parameters정격전압: 24~240V AC/DC, 50/60헤르츠Wide voltage design for global application. No need to distinguish AC and DC, ensuring high fault tolerance for on-site wiring
전력 소비≤2 VA @ DC24V; ≤4 VA @ AC240V낮은 전력 소비, no heat generation during long-term standby, suitable for 24-hour continuous operation
작동 특성Continuously adjustable delay: 0.5~10sA delay of 3~5s is recommended for sites with strong interference or drastic liquid level fluctuation to prevent false triggering
Output Contacts1 전환 연락처 (1콜로라도); AC-15: 3A/250V; DC-13: 1A/24VPassive dry contacts only for secondary circuit control. Do not drive high-power loads directly
정확도 지수측정 정확도: ±20%; 온도 드리프트: 1%/℃Measurement error increases gradually when ambient temperature exceeds 40℃. Reserve threshold margin for areas around high-temperature storage tanks
전체 치수22.5×92×91mm (폭×높이×깊이)Standard DIN rail mounting with universal cabinet layout. No cabinet modification required for replacement of old models
주변 조건작동 온도: -25℃ ~ +60℃; 보호 등급: IP20For indoor cabinet installation only, not exposed to rain. Abnormal circuit operation may occur below -25℃
Anti-interference PerformanceSurge withstand: 4kV; Electrical isolation between input and outputCompliant with industrial EMC standards, can be installed in the same cabinet with inverters and contactors
배선사양Spring-cage terminals, compatible with solid wires of 0.5~4mm²Crimp terminals are required for stranded wires to prevent poor contact
  1. 설치 & 배선사양 (Wiring Method for Level Relay)

4.1 설치 요구 사항

Adopt standard snap-on DIN rail mounting. Keep the installation spacing ≥5mm for ventilation and heat dissipation. Reserve operating space on the front of the device for potentiometer adjustment.

4.2 Wiring Division (Two Independent Circuits, Strict Separation Required)

  1. Power Supply Circuit: Connect to 24~240V AC/DC power supply. No polarity limitation due to wide voltage compatibility.
  2. Electrode Monitoring Circuit: Connect external level electrodes for resistance signal measurement. Shielded cables are recommended and routed away from power cables.
  3. Output Contact Circuit: 연결하다 1 set of changeover contacts to alarm lamps, relay coils and water pump control circuits for secondary low-voltage control.

주의: Never route monitoring cables and power cables in the same conduit. Electromagnetic interference will occur and directly cause frequent false tripping of the relay.

  1. 모델 비교 & 교체 솔루션 (List of Main Alternative Models)

Comparison of different versions in the same series and similar models, commonly referenced for procurement replacement and equipment renovation:

모델Control Points터미널 유형핵심 차이점Replacement Feasibility
3UG4501-2AW30 (이 모델)2 전철기 (Upper & lower limits)Spring-cage terminalDual-level control with anti-vibration wiringReference standard model
3UG4501-2AA302 전철기 (Upper & lower limits)나사식 터미널Identical functions, only different wiring modeDirectly interchangeable, only wiring adjustment needed
3UG4501-1AW301 point (Single threshold)Spring-cage terminalOnly single level monitoring without upper/lower limit functionIncomplete functions, cannot replace this model directly
3UG4501-1AA301 point (Single threshold)나사식 터미널Single-point monitoring + 나사식 터미널Mismatched functions, replacement prohibited

Cross-brand replacement reference: Equivalent resistance-type level monitoring relays from Weidmüller and Phoenix Contact are compatible if power supply and contact parameters are consistent. Verify the measuring resistance range before replacement.

  1. On-site Commissioning & 매개변수 설정
  2. Threshold Adjustment: Rotate the front panel potentiometer to set the lower limit resistance (low liquid level) and upper limit resistance (high liquid level) 각기, and fine-tune according to the conductivity of on-site liquid.
  3. Delay Setting: Turn clockwise to increase the delay (3~5s recommended) for severe liquid level fluctuation and strong interference; set 0.5~1s for static clean water conditions.
  4. 전원 켜기 테스트: Simulate high and low liquid level conditions, check contact switching and actuation of alarm devices. Put into formal operation after confirming correct logic.
  5. Fault Analysis & 문제 해결 (Core Troubleshooting Content)

Analyze root causes based on electrical principles and provide step-by-step solutions for common on-site faults:

결함 현상Root Technical CausesStep-by-step Solutions
No relay operation, contacts fail to switch1. Power supply voltage out of 24~240V range; 2. Scaled or corroded electrodes leading to over-limit resistance; 3. 느슨한 배선1. Measure power supply with multimeter and rectify power circuit; 2. Remove and clean scaled/corroded electrodes, replace damaged ones; 3. Retighten spring terminals and check for broken wires
Normal liquid level but frequent false tripping1. Leakage between electrodes or liquid level fluctuation; 2. Electromagnetic interference from power cables; 3. Excessively short operating delay1. Extend operating delay to over 3s; 2. Replace monitoring cables with shielded wires and single-end grounding; 3. Clean electrodes to eliminate surface leakage
Contacts act but rear-end loads do not workAged or burned contacts; load current exceeds rated contact current1. Cut off power and test contact continuity, replace the relay if contacts are damaged; 2. Add intermediate relays for current expansion. Never drive high-power loads directly via the contacts
  1. 자주 묻는 질문 (자주 묻는 질문)

1분기: How to choose between relays with spring-cage terminals and screw terminals?

에이: Spring-cage terminals are preferred for vibration-prone sites such as pump rooms and vehicle-mounted equipment due to fast wiring and good vibration resistance. Screw terminals are suitable for permanently installed cabinets with rare maintenance for more stable connection.

2분기: Can this level monitoring relay directly replace the old model 3UG3501?

에이: 예, it is electrically fully compatible with consistent installation dimensions and wiring logic. As an upgraded model with identical functions, no circuit modification is required for replacement.

3분기: Why does the level relay frequently trip near inverters?

에이: Inverters generate high-frequency electromagnetic interference which couples into electrode signal cables. 솔루션: Route monitoring cables separately, use shielded cables and appropriately extend the operating delay.

Q4: What happens if the measured resistance exceeds 200kΩ?

에이: The device cannot identify level signals beyond the measuring range, continuously judges the state as high liquid level, keeps contacts actuated and loses monitoring function.