Siemens 6ES7132-6HD01-0BB1 Relay Output Module

SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay Output Module Distributed IO ET200SP, 4-channel normally-open digital relay output module, contact isolated type ✅ Model Code Interpretation 6ES7: SIMATIC S7 Automation System 132: ET200SP Digital Output Module 6HD01: 4-채널 릴레이 출력, 120VDC~230VAC, 5A normally open 0BB1: Single pack (1 상자당 단위); `2BB1` = 10-piece bulk pack ...

  • 제품 세부정보

SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay 출력 모듈

Distributed IO ET200SP, 4-channel normally-open digital 계전기 output module, contact isolated type

✅ Model Code Interpretation

6ES7: SIMATIC S7 오토메이션 체계

132: ET200SP Digital Output Module

6HD01: 4-채널 릴레이 출력, 120VDC~230VAC, 5A normally open

0BB1: Single pack (1 상자당 단위); `2BB1` = 10-piece bulk pack

📋 Key Technical Specifications

매개변수
Channel Count4 normally-open relay outputs (아니요), channel-to-channel isolation
접촉 등급120V DC ~ 230V AC, 최대. 5채널당 A
Base Unit TypeCompatible with BU B0 / BU B1 base units; color code CC40
Backplane Bus Supply55엄마, typical power consumption 1.5W
진단 기능Module supply diagnostics, substitute value output
작동 온도0 ~ +60 ℃ (standard module)
의사소통프로피넷 / 프로피버스 DP (with ET200SP interface module)
HS코드85389091

🧩 Features

  1. Relay dry contact isolation: Galvanic isolation between PLC low-voltage side and load high-voltage side. Suitable for solenoid valves, 접촉기, indicator lamps and other AC loads.
  2. Substitute value: When communication fails or CPU stops, output state can be preset in TIA Portal: hold / reset to 0 / set to 1.
  3. Channel status LEDs + module diagnostic LED for fault alarm.
  4. Separate base & electronic module design: Hot-swappable electronics while wiring remains on base for easy maintenance.

⚙️ Typical Application Scenarios

Control of 220VAC solenoid valves, small contactors, alarm lamps, fan start/stop in control cabinets

Not suitable for high-frequency switching applications (limited relay mechanical service life; cannot handle high-speed pulses)

Distributed remote IO station deployed with IM155-6 interface module

⚠️ Selection & 배선 참고 사항

  1. Base unit must be BU B0 / BU B1 type, A-type bases are incompatible; recommended BU20-P16+A0+2B.
  2. Relay contacts are passive dry contacts. Load power is not supplied by module backplane, external power supply required.
  3. 유도 부하 (접촉기 코일) are recommended to connect varistor / freewheeling diode in parallel to extend relay service life.
  4. 5A per channel is rated current; pay attention to heat dissipation when all 4 channels run at full load simultaneously.

📌 Alternative & 파생 모델

6AG1132-6HD01-7BB1: SIPLUS wide-temperature conformal coated version, -40~+70℃, for harsh environments (화학 산업, 집 밖의)

국내 대안: ET200SP compatible 4-channel normally-open 5A relay modules. Verify base compatibility and diagnostic telegram.

Application Scenarios for 6ES7132-6HD01-0BB1 (ET200SP 4-Channel Relay Output Module)

핵심 기능: Passive dry contacts, 채널 격리; 최대. 5저항 부하용 A, 최대. 2유도성 부하용 A; supports 24V~230V AC/DC loads; PROFINET distributed remote IO. Ideal for low-frequency switching control requiring galvanic isolation between strong and weak circuits.

  1. 산업별 애플리케이션
  2. 기계 제조 (가장 일반적인)

220VAC pneumatic & hydraulic solenoid valve control (cylinder, hydraulic valve on/off)

Drive coils of small AC contactors to indirectly control fans, 슬리퍼, 컨베이어

Equipment alarm lights, 들리는 & visual alarms, panel indicator lamps

Door interlock, guard door signal output, equipment enable signal

해당되는: 포장 기계, 공작기계, 생산 라인, 사출 성형 기계, textile machinery remote IO stations

  1. 프로세스 자동화 / 수처리

Remote field cabinet: 220V solenoid valves, dosing pumps, drain valves, agitator start/stop control

Field instrument power switching, warning lights, on-site audible & visual alarms

Water tank level interlock output; remote stations deployed at different plant locations

이점: Relay isolation prevents field high-voltage interference from coupling into PROFINET bus

  1. 공조 & 빌딩 자동화

AC220V air damper actuators, electric butterfly valve on/off control

Contactor coil control for fans, 배기 팬, 물 펌프

Fire linkage signal output, on-site alarm indication

  1. 에너지, PV & Power Auxiliary Control

Switchgear auxiliary circuit, relay loop switching, alarm contact output

Small heater, dehumidifier on/off control

Signal isolation transfer: Convert PLC low-voltage signals to dry contacts for 3rd-party systems (DCS, relay protection)

  1. Supported Load Types
  2. AC220V solenoid valves, indicator lamps, buzzers
  3. AC220V contactor / intermediate relay coils
  4. 저항 부하: heating tapes, 백열등 (5A 이하)
  5. DC24V~DC120V DC loads (dry contacts work for both AC and DC)
  6. Passive contact output for hard-wired interlock with other control systems

III. 부적합한 용도

  1. ❌ High-frequency switching: Mechanical relay has limited service life, not for multiple operations per second. Use transistor DQ modules for high frequency.
  2. ❌ Direct drive of high-power motors (only drives contactor coils, not main motor circuit)
  3. ❌ Inductive load current exceeding 2A (solenoid & contactor are inductive loads; varistor / freewheeling diode required to absorb back EMF)
  4. ❌ Safety circuits (this module is non-failsafe. F-RQ failsafe modules are required for emergency stop and safety gate circuits)
  5. ❌ High inrush current loads (contact erosion risk; each channel needs external 6A max. fast fuse protection)
  6. Architecture Characteristics

ET200SP distributed IO: This module is mounted in remote field enclosures away from the main PLC and connected via IM155-6 PROFINET interface module.

Load wiring for 220VAC is routed locally, reducing long-distance high-voltage cables

Relay isolation protects PLC low-voltage system and improves EMC immunity

Substitute value configurable in TIA Portal: Output state can be defined for bus interruption or CPU stop to ensure safe equipment status

ET200SP Digital Output Module Selection Comparison Sheet

Compare 6ES7132-6HD01-0BB1 (RQ 4-channel relay output) vs common transistor DQ modules

  1. 핵심 매개변수 비교표
6ES7132-6HD01-0BB16ES7132-6BH01-0BA06ES7132-6BD20-0BA0
Relay Output RQTransistor DQ 16×24VDCTransistor DQ 4×24VDC/2A
출력 유형패시브 건식 접촉, normally-open relay NOPNP transistor, active 24VDCPNP transistor, active 24VDC
Channel Count4 채널16 채널4 채널
Load Voltage Range120VDC ~ 230VAC, 교류 & DC compatibleDC24V 전용DC24V 전용
Rated Current per Channel5A resistive; 2A inductive0.5채널당 A2채널당 A
갈바닉 절연✅ Channel isolation, strong/weak voltage isolation❌ No channel isolation, common 24V ground❌ No channel isolation
응답 속도느린: millisecond level (mechanical contact)빠른: microsecond level빠른: microsecond level
서비스 수명Mechanical life ~10⁷ operations (low frequency)Nearly unlimited electronic life, high frequency capableNearly unlimited electronic life
일반적인 부하AC220V solenoid valves, 접촉기 코일, audible/visual alarms, dry-contact interlockDC24V solenoid valves, indicator lamps, sensor power supplyHigh-current DC24V loads, DC solenoid valves
Base Color CodeCC40CC01CC01
  1. When to select 【6ES7132-6HD01-0BB1 Relay Module】

✅ Recommended

  1. Load voltage is AC220V, no extra intermediate relay required on site
  2. Galvanic isolation required, heavy field interference, prevent high voltage from damaging PLC IO bus
  3. Need passive dry contact output for hard-wired interlock to 3rd-party DCS / protection relays
  4. Low switching frequency (triggered every few minutes/hours, not frequent on/off)
  5. Mixed loads: both AC220V and DC loads up to 120V

❌ Not Recommended

  1. 빈번한 전환: multiple start-stop per second (rapid contact wear and shortened lifetime)
  2. Pure DC24V loads with large point count requirement (transistor modules cheaper, higher channel density)
  3. High-speed pulse & motion control output (relay cannot generate pulses)
  4. SIL safety circuits (Failsafe F-series modules required)

III. When to select 【Transistor DQ Module】

✅ Recommended

  1. All loads are DC24V, 빈번한 전환 (continuous actuation of cylinder solenoids)
  2. Requirement for high-speed switching signals or pulse outputs
  3. Large I/O point count, high channel density to save cabinet space
  4. Field loads are low-current DC components without isolation requirement

❌ Not Recommended

  1. AC220V loads: must add external intermediate relays
  2. Severe field high-voltage interference without isolation; risk of IO module burnout
  3. Quick Selection Rule

짐: AC220V, low frequency, isolation required → 6ES7132-6HD01-0BB1

짐: DC24V, frequent operation → Transistor DQ (6BH01 for many points / 6BD20 for high per-channel current)

  1. Additional Selection Notes
  2. 유도 부하 (솔레노이드 밸브, 접촉기) need absorption components: varistor in parallel for AC loads, freewheeling diode for DC loads to suppress back EMF and extend contact life.
  3. Relay module base color code CC40, not interchangeable with transistor DQ base CC01.
  4. Cost reference: Relay modules usually cost more for same channel quantity. 하지만, overall system cost may be lower when eliminating external intermediate relays.
  5. Failure characteristics: Relay contacts risk sticking; transistor modules mostly fail by breakdown with no mechanical sticking risk.
  6. Special Alternatives

Failsafe output: 6ES7136-6DB00-0CA0 (F-DQ for safety circuits)

Solid-state relay output (no moving contacts, suitable for high-frequency AC switching): ET200SP RQ solid-state relay models