7MF1567: SITRANS P220 시리즈, 전체 스테인레스 스틸 용접 구조, 고압 및 냉매 전용, 압저항 게이지 압력 트랜스미터
3CB00:
측정 범위: 0 … 16 술집 (계량기)
Overpressure limit: 40 술집
Burst pressure: 대략. 80 술집
3AA1:
산출: 4–20 mA 2-wire system
Process connection: 1/2″-14 NPT internal thread (widely used in North America, different from G1/2″ external thread of 1AA1)
전기 연결: M16 connector (DIN EN 175301-803-A)
Explosion protection: 비방폭형 (표준형)
- 핵심 기술 매개변수 (2026 공식 매뉴얼)
- 측정 & 성능
Measured variable: Gauge pressure
측정 범위: 0–16 bar
정확성: ±0.25% FS (전형적인), 최대. ±0.5%FS
Non-linearity: ≤0.25% FS
반복성: ≤0.1% FS
응답 시간: <5 ms (T99)
Long-term stability: 0.25% FS per year
- 전기 사양
출력 신호: 4–20 mA 2-wire
전원공급장치: DC 7–33 V (24 VDC 권장)
부하 용량: R ≤ (U-10 V) / 0.02 에이
맥스. load resistance at 24 다섯: 대략. 700 오
- 온도 범위
중간온도: -30 … +120 ℃
주변 온도: -25 … +85 ℃
보관온도: -40 … +100 ℃
- 기계구조 & 재료
Wetted & non-wetted parts: Full stainless steel (1.4435/316엘), gasket-free fully welded design, ideal for high pressure and refrigerant media
Process connection: 1/2″-14 NPT internal thread
전기 연결: M16 connector, IP65 protection grade
무게: 대략. 0.2 kg
기원: 스위스 (CH)
III. 배선 지침 (M16 Connector, 4–20 mA 2-wire)
Pin definition (Standard EN 175301-803-A):
핀 1 (+): 24 VDC positive
핀 2 (-): 4–20 mA signal return (connect to PLC AI positive terminal)
핀 3: 여분의
체육: Earth connection (housing grounding)
배선 참고 사항:
2-wire design: Power positive shares line with signal negative
Shielded cable single-ended grounding (control cabinet side only)
권장 케이블: 0.5–1.5 mm² shielded twisted pair cable
- 설치 & 운영 지침
- 설치 위치: Vertical or horizontal mounting available; keep away from severe vibration
- Sealing treatment: Use PTFE tape or matched sealant for NPT thread connection
- Zero point calibration:
Output shall be 4.00 mA under zero pressure condition
Adjust zero trim screw at connector side if necessary
- Applicable media:
✅ Gas, 액체, 증기, 냉매 (R134a, R410A etc.)
✅ Slightly corrosive media (compatible with stainless steel)
❌ Strong corrosive fluid (concentrated acid, strong alkali), high abrasion slurry
- Common Alternative & 유사한 모델 (범위 & Connection Comparison)
| 모델 번호. | 범위 (술집) | Process Connection |
| 7MF1567-3CA00-3AA1 | 0-10 | 1/2″ NPT Internal |
| 7MF1567-3CB00-3AA1 | 0-16 | 1/2″ NPT Internal |
| 7MF1567-3CD00-3AA1 | 0-25 | 1/2″ NPT Internal |
| 7MF1567-3CE00-3AA1 | 0-40 | 1/2″ NPT Internal |
| 7MF1567-3CB00-1AA1 | 0-16 | G1/2″ 외부 (BSP) |
- 일반적인 문제 해결
- 결정된 4 mA output
비정상적인 전원 공급 (아래에 7 다섯)
Open circuit in signal loop
- 결정된 20 mA output
Over-range pressure (초과하다 16 술집)
Diaphragm damage
- Signal drift & unstable reading
접지 불량 또는 전자기 간섭
Sharp temperature fluctuation
Excessive installation stress
Ⅶ. 주문정보 & 리드타임 (2026 참조)
생산현황: Active in production
표준 배송 시간: 1 working day (European warehouse)
참고 가격: About CNY 700–900 (세금 포함, 1-5 PC)
일반적인 결함, Causes and Quick Solutions for Siemens 7MF1567-3CB00-3AA1 (P220) 압력 트랜스미터
- 출력 없음, zero current (0엄마)
- Insufficient supply voltage
원인: Voltage lower than 7VDC, large line voltage drop
해결책: 단자 전압 측정, keep stable at 20~26VDC
- Reverse positive and negative wiring
2-wire system rarely burns out device but causes no signal
해결책: Swap wiring of pin 1 그리고 핀 2
- Broken cable or loose terminal connection
해결책: Conduct continuity test and fasten M16 connector
- Internal circuit damage of transmitter
현상: No response after power-on, invalid after power replacement
- Constant 4mA minimum output without change
- Actual pressure is zero under normal static status
- Blocked pressure tapping pipeline
Medium crystallization, oil dirt and impurities block pressure inlet
해결책: Purge and dredge pressure guiding pipe
- Diaphragm stuck by foreign objects
- Wrong measuring range or mismatched PLC configuration range
- Severe zero drift
해결책: Trim zero point on site under zero pressure
- Constant 20mA full-scale output
- Actual pressure far exceeds 16 bar full range
해결책: Reduce pressure and verify field actual pressure
- Pressure trapped inside pipeline unable to release
- Pressure diaphragm breakdown and failure
Most frequent hardware fault, 교체가 필요합니다
- Short circuit of signal wire
Positive and negative wire short circuit leads to full current output directly
- Fluctuating and unstable signal reading
- Excessive on-site vibration (installed near pumps and fans)
해결책: Install shock-absorbing bracket and keep away from vibration sources
- 심각한 전자기 간섭
Power cables laid together with signal cables without shielding
해결책: Single-end grounding for shielded twisted pair, separate wiring layout
- Pulsating medium pressure itself
해결책: Install damper and pressure stabilizing buffer tank
- Temperature drift caused by drastic ambient temperature change
- 느슨한 배선, water ingress and oxidation inside connector
- Large measurement deviation, inaccurate reading, high or low indication
- Uncalibrated zero point (drift after long-term operation)
해결책: Calibrate zero under zero pressure to recover accuracy
- Static pressure error caused by improper installation position
- Exceed 120℃ medium temperature damages measurement precision
- 위에 40 bar overload pressure causes permanent offset
- Inconsistent range setting between PLC program and actual transmitter range
- Fault caused by water ingress and dampness
- Poor sealing of M16 connector leads to water penetration
현상: Random reading fluctuation, intermittent normal operation
해결책: Dry internal parts, replace waterproof connector and reapply sealing glue
- Rainwater and condensed water penetrate into internal structure for outdoor installation
- Overload resistance fault
현상: Normal supply voltage but current output insufficient
원인: Excessive internal resistance of rear PLC module exceeding 700Ω load limit
해결책: Shorten signal cable length and reduce loop resistance
- Typical Vulnerable Defects Exclusive to P220 Series
- Excessive force during NPT thread installation squeezes internal diaphragm and causes permanent scrappage
- Zero drift easily occurs after long-term operation with refrigerant and low-temperature media
- Failure rate doubles under high-frequency vibration environment
- Fully welded structure disables disassembly and maintenance, direct replacement needed once damaged
- Three-step Quick Self-check Method
- Cut off power supply, stand by for 3 minutes then re-energize
- Release all pressure to check if output returns to 4mA
- Apply standard pressure to verify linear output up to 20mA
핵심 결론
7MF1567-3CB00-3AA1 (P220) adopts factory integrated fully welded sealing structure. The diaphragm cannot be replaced separately on site. The whole transmitter must be replaced once diaphragm is damaged.
Reasons for Non-separable Diaphragm Replacement (Core Structure of P220)
Model feature: 7MF1567 is fully welded SITRANS P220 transmitter without sealing gasket or detachable pressure cover
Diaphragm structure: 316L/1.4435 diaphragm is directly welded on pressure cavity; pressure cavity and electronic chamber are integrated via laser welding or argon arc welding with no detachable bolts or clamps
Official specification: The transmitter is maintenance-free. Repair work is only available by Siemens authorized personnel and on-site disassembly is prohibited.
Typical Phenomena of Damaged Diaphragm
Fixed 20mA output (over-range or diaphragm breakdown)
Extreme zero drift unable to be calibrated
Medium leakage at thread root or housing joint
Random data fluctuation and internal corrosion caused by water ingress via M16 connector
On-site Replacement Solutions
해결책 1: Direct overall replacement (추천)
Spare part model: 7MF1567-3CB00-3AA1 (same range & 연결)
Replacement steps:
- Cut off power, release pressure and close pressure valve
- Remove M16 connector
- Unscrew 1/2″ NPT thread gently with spanner (avoid squeezing new diaphragm)
- Wrap PTFE tape on new thread, tighten manually then turn 1/4 circle with spanner
- Complete wiring, power on and perform zero calibration
해결책 2: Factory return maintenance (High cost & long cycle)
Maintenance content: Replace full welded pressure module and recalibrate
유지관리 비용: 에 대한 60-80% of new product price, 납품주기 2-4 주
Not cost-effective compared with direct replacement
Risks of Forced Disassembly
- Welded cavity cannot be opened without damage, resulting in housing deformation and diaphragm scrap
- Ultra-thin diaphragm (0.1-0.2mm) is easy to crack under prying, knocking and extrusion
- Siemens does not sell separate P220 diaphragm or pressure module, only complete transmitters available
- Disassembly will invalidate IP65 protection and explosion-proof certification, bringing potential safety hazards
Preventive Measures for Diaphragm Damage
- Strictly control installation torque for NPT thread, forbid excessive tightening
- Keep working pressure within 16 bar rated range, avoid instantaneous high pressure impact
- Install shock absorber when mounting near pumps and compressors to prevent fatigue crack of diaphragm
- Limit medium temperature below 120℃ to avoid metal creep and zero drift
- Apply sealing glue on M16 connector for reliable waterproof performance
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지














NH42-63-318x560.png)