HINODE 660GHX125-125A Ultra-Fast Fuse Link

HINODE (Hinode Electric Manufacturing Co., 주식회사, 일본) Semiconductor Protection Ultra-Fast Fuse. 660GHX series, 125에이, AC/DC 660V, bolt-mount type, widely used for short-circuit protection of power circuits in inverters, 정류기, 변환기, DC power supplies and energy storage systems. 모델 설명 660: Rated voltage AC/DC 660V GH: Series of cylindrical bolt-mounted high breaking capacity ultra-fast fuses X: ...

  • 제품 세부정보

HINODE (Hinode Electric Manufacturing Co., 주식회사, 일본) Semiconductor Protection Ultra-Fast Fuse. 660GHX series, 125에이, AC/DC 660V, bolt-mount type, widely used for short-circuit protection of power circuits in inverters, 정류기, 변환기, DC power supplies and energy storage systems.

모델 설명

660: Rated voltage AC/DC 660V

GH: Series of cylindrical bolt-mounted high breaking capacity ultra-fast fuses

엑스: Product suffix for basic version, without microswitch for blown fuse alarm. The alarm version is suffixed with S, 예를 들어. 660GH125S

125: Rated current 125A

Common shorthand in market: 660GHX125, full marking 660GHX125-125A

핵심 전기 사양

목매개변수
정격전압AC660V / DC660V (L/R=10ms)
정격전류125에이
차단 용량AC660V: 100그만큼; DC660V: 100그만큼
CCC Certified Version (suffix TC)AC660V: 50그만큼; DC450V: 50그만큼
Minimum Breaking CurrentAC/DC 660V: 5×에서 (625에이)
Maximum Arc Voltage1400다섯
작동 특성Ultra-fast type for semiconductor protection, short-circuit interruption in microseconds
건설Ceramic body, bolted mounting lugs at both ends, quartz sand filler
규정 준수RoHS 규제, UL/CCC certification optional (suffix UL / TC)

개요 & 설치

구조: Flange with mounting holes at both ends, bolt-tight mounting, clip mounting is not allowed

Basic cylinder dimension: φ17mm, overall length increases with current rating

설치: Matched fuse holder series HT6017

일반적인 응용 분야

Power circuit protection for variable frequency drives and servo drives

Short-circuit protection for rectifier bridges, IGBTs and thyristor power semiconductors

DC bus, battery test equipment, low-voltage energy storage converters

야금, 철도 운송, high-power UPS power supplies

선택 & 교체 지침

  1. 구별: 660GHX125 (알람 없음) vs 660GH125S (with blown fuse signal microswitch). Identical outline dimensions and interchangeable holders.
  2. 국내 대체: Select semiconductor ultra-fast fuses of same rating 660V 125A. 차단 용량, mounting hole pitch and time-current characteristic must be verified. General gG/gL fuses cannot be substituted.
  3. 대사: Power cut and voltage verification mandatory. After fuse blowout, check for breakdown of power semiconductors; never fit a new fuse and energize directly.

Reference Models in Same Series

660GHX063, 660GHX080, 660GHX100, 660GHX125, 660GHX160, 660GHX200

Domestic Replacement List for HINODE 660GHX125 (660V 125A aR Ultra-Fast Fuse Link) + Mounting Dimension Comparison

Original part: Hinode 660GHX125, cylindrical double-flange bolt-on aR semiconductor protection fuse, φ17mm body, overall length approx.98mm, flanged mounting lugs at both ends, no striker (select striker version for alarm type). AC/DC660V, 차단 용량 100kA, for IGBT/rectifier short-circuit protection.

Core precondition for replacement: Only aR class semiconductor ultra-fast fuses are acceptable. gG general fuses are strictly prohibited for direct substitution. Priority for fully compatible dimensions to fit original HT6017 holder directly; close dimensions require hole pitch verification.

Baseline Dimensions of Original 660GHX125

목Dimension mm
Cylinder Outer Diameterφ17
Overall Length of Fuse Link98
Flange Width28
장착 구멍 직경φ6.5
Center Distance Between Two Mounting Holes76
유형Cylindrical bolt-on, AR, no striker (striker version optional for replacing 660GH125S)

Domestic Replacement Model Comparison Table

Domestic Model상표평가유형Body φ
RGS4A-660V125A aRMRO (Mingrong)AC660V 125A DC660VaR Semiconductor Ultra-Fast Fuseφ17
RGS4-660/125 aRShanghai LongrongAC660V 125A DC660VARφ17
RGS4A 690V125A aRBomugeAC690V 125A DC660VARφ17
RS94G-660V125A aRSinofuseAC660V 125A DC660VARφ19
RS77Z-690V125A aRMRO (Mingrong)AC690V 125A DC500VARf20

선택 & 교체 노트

  1. Time-Current Characteristic (TCC Curve): RGS4A/RGS4 have the closest pre-arcing time and current limiting characteristics to 660GHX125. For high-power IGBT circuit replacement, request TCC curves from manufacturer for comparison.
  2. DC 응용: Original fuse supports DC660V (L/R=10ms). RGS4A and RS94G support DC660V. Some domestic models have derated DC rating; DC bus application must confirm DC specifications.
  3. Blown Fuse Alarm Function

Original 660GHX125: no microswitch → select RGS4A without striker

Original 660GH125S (with alarm) → select RGS4A with striker, paired with holder microswitch for blown fuse signal output

  1. Breaking Capacity Derating Risk: Original Hinode AC breaking capacity 100kA; domestic RGS4 series is 80kA. For most inverters and DC power supplies, site prospective short-circuit current <80kA and acceptable. Re-evaluation required if prospective short-circuit current >80그만큼.
  2. Installation Inspection: Even with fully matched dimensions, inspect HT6017 holder copper contact surface for oxidation before replacement; control tightening torque to avoid overheating and nuisance fuse blowout.

Not Recommended Replacements (Avoid Pitfalls)

RT18, RT28 series: gG general purpose protection, not aR semiconductor ultra-fast fuses. Slow short-circuit response will cause IGBT burnout, strictly prohibited for substitution.

RS0, RS3 standard square body fast fuses: 정사각형 하우징, fully different flange mounting structure, cannot fit into original holder.

Quick Selection Recommendation

Spare part direct replacement without holder modification: Priority MRO RGS4A-660V125A aR or Longrong RGS4-660/125 aR

DC bus / energy storage application requiring high safety certification: Sinofuse RS94G (verify cabinet mounting clearance)

Fuse Replacement Verification Procedure (Pre-Energization Check + Power-On Test, HINODE 660GHX125 → Domestic RGS4A/RGS4)

애플리케이션: Fuse replacement for variable frequency drives, rectifier units and DC power circuits. Core objective: Prevent secondary power semiconductor damage from direct energization.

  1. Power Isolation & Safety Pre-Work (필수적인)
  2. Disconnect upstream circuit breaker / contactor and implement Lockout/Tagout (마음). Fully discharge DC bus and capacitors; verify AC/DC voltage <5V with multimeter.
  3. Remove blown fuse link and visual inspection:

Ceramic body crack, arc flash or blackening;

Copper terminals of HT6017 fuse holder: 산화, burn mark or deformation;

Thread damage on holder bolts.

⚠️ Once fuse blows, do not merely replace fuse. Power semiconductors on downstream must be inspected.

  1. Downstream Power Semiconductor Fault Screening (Critical after Fuse Blowout)
  2. Rectifier bridge / IGBT module test (multimeter diode mode)

Measure forward and reverse voltage drop of each terminal to confirm short-circuit breakdown.

Check snubber capacitors and DC bus capacitors for bulging, leakage and short circuit.

  1. Inspect busbars and terminals for short circuit and cable insulation damage.

If IGBT / rectifier bridge breakdown is found: replace damaged power semiconductor first before installing new fuse. Short-circuited devices will blow new fuse instantly or cause explosion upon energization.

  1. Pre-Installation Verification of New Fuse Link
  2. Model check: aR semiconductor ultra-fast fuse, rated voltage ≥660V, rated current 125A. Confirm striker status (original 660GHX125 has no striker; avoid mistakenly fitting striker-equipped version).
  3. Dimension verification: body φ17, overall length 98mm, hole center distance 76mm, flange hole φ6.5; confirm smooth fitting into HT6017 holder.
  4. 육안검사: ceramic housing crack-free, metal terminals at both ends no dent or deformation.
  5. 조임 토크: Recommended bolt torque 8~10 N·m. Insufficient torque causes high contact resistance and overheating leading to nuisance blowing; excessive torque cracks ceramic body.
  6. Cold Insulation Test (De-Energized)
  7. Disconnect wiring on one side of fuse link, use megger:

Main circuit insulation test to earth (1000V 메가, pass if ≥100MΩ);

Verify no short circuit between phases or DC positive/negative bus.

  1. Recheck inter-phase / DC bus positive-negative for short circuit with multimeter.
  2. Stepwise Power-On Verification (No Full Load Closing at Once)
  3. No-load energization: Disconnect output side (모터 / 짐). Apply low trial voltage first (variable transformer preferred), ramp up gradually to rated 660V.

Monitor fuse and holder for abnormal noise, smoke or overheating;

Measure voltage across fuse link; voltage drop shall be extremely low under normal no-load condition.

  1. No-load operation for 10~30 minutes: Infrared temperature measurement on metal terminals at both ends of fuse link; temperature rise ≤70K is acceptable. Shut down immediately if temperature rises rapidly and inspect contact surface.
  2. Stepwise load ramp-up: Load at 25%→50%→75%→100% in sequence, hold each step for 15~30 minutes, continuously monitor terminal temperature.
  3. Record: Circuit current and fuse terminal temperature for future baseline maintenance reference.
  4. 비정상적인 상태 & Shutdown Criteria

Immediately cut off power if any of the following occurs:

  1. Fuse blows the moment of closing;
  2. Continuous rapid temperature rise at terminals;
  3. Arc, burning smell or ceramic body discoloration;
  4. Abnormally high circuit current.
  5. Long-Term Inspection after Commissioning
  6. Periodic infrared thermal inspection, focus on fuse flange terminals;
  7. Annual power-off inspection for oxidation of holder contact surface and re-torque;
  8. Retain TCC curves of original and replacement fuse for future failure analysis.

보충: Replacement Boundary Risk Statement

Domestic RGS4 series AC breaking capacity is 80kA vs original Hinode 100kA.

If site prospective short-circuit current >80그만큼, this domestic model is not applicable; re-evaluation or continue using imported fuse required.