Advantech ADAM-5018 Analog Input Module - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

 Advantech ADAM-5018 Analog Input Module - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

PLC/

 Advantech ADAM-5018 Analog Input Module

The ADAM-5018 is a 7-channel differential thermocouple analog input module for the ADAM-5000 rack system. It adopts RS485 Modbus RTU and is designed for temperature data acquisition, supporting multiple thermocouple types, mV voltage and current signals. Model Code Definition ADAM: Series code for Advantech remote I/O modules 50: ADAM-5000 rack backplane series (plug-in design; must ...

  • Product Details

The ADAM-5018 is a 7-channel differential thermocouple analog input module for the ADAM-5000 rack system. It adopts RS485 Modbus RTU and is designed for temperature data acquisition, supporting multiple thermocouple types, mV voltage and current signals.

  1. Model Code Definition

ADAM: Series code for Advantech remote I/O modules

50: ADAM-5000 rack backplane series (plug-in design; must be installed on ADAM-5000 series chassis, different from standalone ADAM-4018)

18: 7-channel thermocouple & multi-function analog input

Suffix A2E/AE: Standard industrial version; ADAM-5018P = enhanced version with independent range per channel

Note: Standard ADAM-5018 shares one range across all channels; the 5018P allows separate configuration for each channel.

  1. Key Technical Specifications
  2. Channels: 7 differential input channels
  3. Resolution: 16-bit
  4. Total Sampling Rate: 10 S/s (all channels combined, low-speed temperature measurement)
  5. Accuracy: ±0.1%FS for voltage/thermocouple mode; ±0.2%FS for current mode
  6. Isolation: 3000 VDC optocoupler isolation to protect host and field circuits
  7. CMRR: ≥92 dB @ 50/60 Hz, strong anti-interference against power frequency noise
  8. Thermocouple Types: J, K, T, E, R, S, B

J: 0~760°C

K: 0~1370°C

T: -100~400°C

E: 0~1000°C

R/S: 500~1750°C

B: 500~1800°C

  1. Universal Analog Signals: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V; ±20 mA, 4~20 mA (built-in 120 Ω sampling resistor, no external resistor required)
  2. Protection: TVS/ESD, withstand ±35 V overvoltage, reverse polarity protection
  3. Operating Environment: -10 ~ +70°C, 5~95% RH non-condensing
  4. Communication: Backplane RS485, Modbus RTU protocol
  5. Power Supply: 10~30 VDC from rack, typical 24 VDC
  6. Hardware & Wiring Guidelines

Terminal: 16-pin pluggable screw terminal; differential wiring: thermocouple positive → CHx+, negative → CHx-

CJC Cold Junction Compensation: On-board cold-junction temperature sensor, automatic compensation, no external compensation required

Wiring Recommendation: Use matched thermocouple extension cables; route cables away from power cables to reduce EMI

Mounting: DIN rail mounting, plug directly into the ADAM-5000 rack slot.

  1. Typical Applications

Heat treatment furnaces, ovens, kilns, food sterilization, chemical reactors, multi-point temperature monitoring for HVAC, furnace group temperature collection; paired with PAC/PLC/SCADA host systems for temperature data logging.

  1. ADAM-5018 vs ADAM-5018P
ModelRange Configuration
ADAM-5018Single unified range for all channels
ADAM-5018PIndependent signal type & range per channel; mixed K/J thermocouples and 4-20mA signals on one module, higher project flexibilityAdvantech
  1. Alternative Options & Selection Guide
  2. In-series Upgrade: ADAM-5018P (preferred for mixed sensor types)
  3. Standalone Module (No Rack Required): ADAM-4018+ / ADAM-4019+
  4. Next-Generation Bus I/O: AMAX-5018 (EtherCAT, 6-channel thermocouple, high-speed acquisition)

Warning: AMAX-5018 belongs to EtherCAT slice I/O, not compatible with ADAM-5000 RS485 racks.

ADAM-5000 Series Full Model List

  1. Rack Backplanes (Mandatory Base Unit)

RS485 (Modbus RTU)

  1. ADAM-5000/485: 4-slot rack
  2. ADAM-5000E: 8-slot rack

Ethernet (Modbus TCP)

  1. ADAM-5000L/TCP: 4-slot Ethernet rack
  2. ADAM-5000/TCP: 8-slot Ethernet rack
  3. ADAM-5000/TCP-CE: 8-slot PAC rack with CE embedded system
  4. Analog Input Modules (AI)
  5. ADAM-5013: 3-channel RTD (PT100/Ni100), 16-bit, 3000 VDC isolation
  6. ADAM-5017: 8-channel universal AI (mV/V/4~20mA), single shared range; total sampling rate 10 S/s
  7. ADAM-5017P: 8-channel AI with independent range per channel (upgraded model)
  8. ADAM-5017H: 8-channel high-speed AI, max total sampling rate 8 kHz
  9. ADAM-5017UH: 8-channel ultra-high-speed AI, max total sampling rate 200 kHz
  10. ADAM-5018: 7-channel thermocouple input (J/K/T/E/R/S/B), unified range across all channels, built-in CJC cold junction compensation
  11. ADAM-5018P: 7-channel thermocouple input with independent channel configuration; mixed TC/mA signals supported (preferred enhanced model)
  12. Analog Output Modules (AO)
  13. ADAM-5024: 4-channel isolated analog output; signal types: 0~10 V, 0~20 mA, 4~20 mA; 12-bit, 3000 VDC isolation
  14. Digital Input Modules (DI)
  15. ADAM-5051: 16-channel non-isolated digital input

ADAM-5051S: Sink type

ADAM-5051D: Source type

  1. ADAM-5052: 8-channel isolated DI (3000 VDC isolation)
  2. ADAM-5053S: 32-channel high-density isolated DI
  3. Digital Output Modules (DO)
  4. ADAM-5050: 16-channel universal DIO, jumper-selectable DI/DO mode
  5. ADAM-5055S: 8DI+8DO mixed isolated module with LED indicators
  6. ADAM-5056: 16-channel digital output

ADAM-5056D: With LED status display

ADAM-5056S: Sink-type isolated output

ADAM-5056SO: Source-type isolated output

  1. ADAM-5057S: 32-channel high-density isolated DO
  2. Relay Output Modules (Contact Output)
  3. ADAM-5060: 6-channel relay output (2 Form A + 4 Form C contacts)
  4. ADAM-5068: 8-channel relay output
  5. ADAM-5069: 8-channel high-power relay output with LED indicators
  6. High-Speed Counter / Frequency Modules
  7. ADAM-5080: 4-channel bidirectional up/down counter, isolated, low-speed pulse input
  8. ADAM-5081: 4-channel high-speed counter & frequency measurement for high-frequency pulse acquisition
  9. Suffix Ordering Codes

AE / A2E: Standard industrial version (standard ordering)

BE: Wide-temperature ruggedized version

P: Enhanced model with independent channel ranges (key upgrade for 5017P & 5018P)

  1. Quick Selection Summary

Multi-channel thermocouple temperature acquisition: ADAM-5018 (unified range) / ADAM-5018P (independent range, recommended)

PT100 RTD temperature measurement: ADAM-5013

Voltage & current analog acquisition: 5017 / 5017P / 5017H high-speed version

Analog control output: ADAM-5024

Digital signal input: 5051 / 5052; Digital control output: 5056; Relay contact output: 5060 / 5069

Prev: