Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive - Contactor,circuit breaker,solar inverter,electric meter,solar batteries

electrical/

Danfoss FC-051P2K2T4E20H3BXCXXXSXXX Variable Frequency Drive

Official Order No.:132F0022 ⚠️ Important Notice: Danfoss FC51 series is approaching end-of-life. Final order cutoff date: 30 Jun 2026; final delivery cutoff date: 30 Sep 2026. For new projects, evaluation of iC2-Micro as alternative is recommended. Model Code Decoding Code Description FC-051 Product Series: VLT Micro Drive FC51 compact general-purpose variable frequency drive P2K2 Rated ...

  • Product Details

Official Order No.:132F0022

⚠️ Important Notice: Danfoss FC51 series is approaching end-of-life. Final order cutoff date: 30 Jun 2026; final delivery cutoff date: 30 Sep 2026. For new projects, evaluation of iC2-Micro as alternative is recommended.

  1. Model Code Decoding
CodeDescription
FC-051Product Series: VLT Micro Drive FC51 compact general-purpose variable frequency drive
P2K2Rated power: 2.2 kW (3 HP)
T43-phase input, 380–480 V AC (50/60 Hz)
E20Ingress protection rating: IP20 (chassis mounting, for cabinet internal installation)
H3Built-in Class A1/B RFI filter (Category C1 environment)
BIntegrated brake chopper (external brake resistor connectable)
XWithout local control panel LCP (LCP11/LCP12 must be ordered separately if required)
CPCB with conformal coating, suitable for humid and dusty harsh environments
XXXNo auxiliary power modules equipped
SXXXStandard factory firmware version
  1. Core Electrical Parameters

Matched motor: 3-phase asynchronous motor, 2.2 kW

Rated output current: 5.3 A

Overload capability: 150% of rated current for 60 seconds

Control modes: VVC+ vector control / U/f control

Output frequency range: 0–200 Hz (VVC+); 0–400 Hz (U/f)

Communication: Onboard RS485 (Modbus RTU)

Frame size: M2

Net weight: 1.75 kg; Gross weight: 1.95 kg

III. Standard Hardware Configuration

✅ Built-in EMC filter

✅ Integrated brake chopper

✅ Conformal coated printed circuit board

❌ No control panel supplied (commissioning requires external panel or MCT10 software)

❌ Brake resistor not included (to be ordered separately)

  1. Typical Applications

Fans, water pumps, conveyors, packaging machinery, small machine tools, mixing equipment, textile machinery and other general constant-torque / variable-torque loads.

  1. Procurement & Replacement Tips
  2. Stock availability is tight as FC51 enters end-of-life phase;
  3. Next-generation direct alternative model: iC2-Micro 2.2 kW, 3-phase 400 V;
  4. Optional panels for this unit:

LCP11: Digital panel (without potentiometer)

LCP12: Digital panel with built-in potentiometer;

  1. Wiring reminder: Maximum shielded motor cable length applies when the built-in H3 filter is activated.

FC-051P2K2T4E20H3BXCXXXSXXX (Order No.132F0022|Frame M2, 2.2 kW, 380 V) Full List of Compatible Accessories

The drive is delivered without control panel, brake resistor and door-mount kit. Below are original manufacturer compatible models sorted by application:

  1. Local Control Panels (Essential for Commissioning)
Order No.ModelDescription
132B0100LCP11Digital control panel, without potentiometer, IP54 rated panel, for basic parameter setting and parameter copying
132B0101LCP12Digital control panel with integrated potentiometer, supports local speed adjustment, preferred for on-site commissioning

⚠️ Code X in model designation = panel excluded; panel must be purchased separately.

  1. Remote Door-Mount Kits for Control Panels
Order No.SpecificationPurpose
132B01121.5 m cable door mounting kitMount LCP11/LCP12 on control cabinet door
132B01023 m cable door mounting kitLong-distance cabinet door installation, including sealing assembly

III. Protection & Mounting Upgrade Kits (For M2 Frame Only)

Order No.NameFunction
132B0109IP21 Protection Kit for M2Original unit IP20; protection class upgraded to IP21 (NEMA Type1) after installation
132B0106De-coupling partition kit M1/M2Improve heat dissipation and reduce electromagnetic interference for multi-drive side-by-side installation

DIN rail mounting kit is only available for M1 frame. M2 frame does NOT support DIN rail mounting.

  1. Braking System (Code B = Built-in Brake Chopper)

Recommended Brake Resistor Specifications (Danfoss Official Specification)

Minimum resistance value: 90 Ω

Recommended power rating: ≥200 W (normal start-stop); select 400 W for frequent braking

Danfoss does not provide standard brake resistors with dedicated order numbers. Source externally according to 90 Ω / ≥200 W specification. Increase power rating for heavy-duty cycles.

  1. Commissioning & Communication Accessories
  2. PC commissioning cable

FC51 has onboard RS485 terminals. Use USB-to-RS485 adapter together with free MCT10 commissioning software (available for download on official website; Order No.130B1000 refers to software CD media).

  1. Fieldbus Expansion Note

FC51 has no slots for optional communication cards. Only native Modbus RTU over RS485 is supported; Profibus, EtherNet/IP and other fieldbuses cannot be added.

  1. Optional Filter & Reactors

This unit is equipped with built-in H3 = Class A1/B RFI filter (Category C1)

No extra input EMC filter required for standard cabinet installation;

For long motor cables or high-interference sites: install external 3-phase input AC line reactor (6 A reactor matched for 2.2 kW, 400 V system)

Use shielded motor cables; recommended maximum cable length ≤15 m when built-in filter is enabled.

VII. Spare Parts (M2 Frame)

132B0127|FC51 M2 Frame spare parts pack (terminal cover, RS485 connector, earthing screws)

VIII. Matching Drive Motor (Standard Selection)

3-phase asynchronous motor 2.2 kW, 380 V; rated current ≈4.8~5.2 A, compatible with drive rated output current 5.3 A

  1. Next-Generation Alternative Inverter (FC51 End-of-Life Backup)

iC2-Micro 2.2 kW 3-phase 400 V. Highly compatible terminal definitions and installation dimensions, applicable as replacement for new projects.

Quick Selection Guidelines

  1. Single unit on-site commissioning: LCP12 (132B0101) recommended;
  2. Cabinet door operation required: select 132B0112 (1.5 m) / 132B0102 (3 m);
  3. Frequent start-stop and rapid braking: externally source 90 Ω ≥200 W brake resistor;
  4. Multiple drives installed side-by-side: equip M2 de-coupling partition kit 132B0106.

Prev:

Leave a Reply

Leave a message