Order No.: 046938
Part of Moeller PKZM0 series; 3-pole rotary-knob motor circuit breaker integrating overload & short-circuit protection, Class 10 trip characteristic, with built-in phase-failure protection.
✅ Core Technical Parameters
Poles: 3P
Adjustable current setting range: 10~16 A
Rated operational voltage Ue: Max. AC 690 V
Matched motor power (AC-3, 50 Hz):
230 V: 4 kW
400 V: 7.5 kW
440 V: 9 kW
Instantaneous short-circuit trip current: Fixed at 248 A
Trip class: Class 10
Termination: Screw terminals
Protection class: IP20 (front touch-safe)
Overall dimensions: W45 mm × H93 mm × D76 mm
Electrical endurance: 100,000 operations
Standards: IEC/EN 60947-4-1, VDE, UL508, CE, CSA certified
✅ Key Features
- Sensitive phase-failure protection; trips rapidly on single phasing to prevent motor burnout.
- Rotary knob with padlock provision for lockout/tagout (LOTO) safety isolation.
- Built-in TEST pushbutton for manual mechanical trip testing.
- Wide range of add-on accessories: auxiliary contacts, fault trip contacts, undervoltage release, shunt trip, side busbars.
- DIN rail mounting; modular design, directly combinable with DILM contactors to form MSC motor starter units.
✅ Variants with Suffixes (Same Current Rating)
PKZM0-16: Standard screw terminals (Order No. 046938)
PKZM0-16-EA: EA export version
PKZM0-16-SPI32: Screw terminals on line side, push-in spring terminals on load side
PKZM0-16-GVP2: Bulk packaging version
✅ Selection & Equivalent Cross Reference
Domestic equivalents: Delixi CDP6-16, Chint NS2-25 (10–16 A)
Next higher rating in series: PKZM0-20 (16~20 A)
Note: PKZM0 is an integrated breaker; it cannot be used solely as an overload relay. Use ZB series if only thermal overload protection is required.
✅ Troubleshooting Guide
- Trips immediately with no load: Check if current setting is too low, phase loss, or mechanical trip mechanism jamming.
- Instant trip on motor startup: Short-circuit protection triggered; inspect motor winding short-circuit or cable fault.
- Slow trip under sustained overload: Normal Class 10 inverse-time behaviour; if tripping frequently under heavy load, increase the current setting or upgrade to a higher-rated model.
Full Accessory List for PKZM0 Series (Applicable to PKZM0-16)
Installation rule: NHI-E = front-mounted; NHI = side-mounted; AGM = fault trip contact; U-PKZ0 = undervoltage release; A-PKZ0 = shunt trip. Suffix -PI = push-in spring terminals; no suffix = screw terminals.
- Standard Auxiliary Contacts (Main contact status feedback: closed/open signal)
- NHI-E-10-PKZ0|1NO, front-mounted
- NHI-E-01-PKZ0|1NC, front-mounted
- NHI-E-11-PKZ0|1NO+1NC (most common), front-mounted
- NHI11-PKZ0|1NO+1NC, side-mounted
- NHI21-PKZ0|2NO+1NC, side-mounted
- NHI12-PKZ0|1NO+2NC, side-mounted
PI version available: NHI-E-11-PKZ0-PI (spring terminals)
Rating: AC-15 230 V 0.5 A, DC-13 24 V; used for PLC feedback and status indication lamps.
- Fault Trip Contacts (Only actuated on protective trip – critical distinction!) AGM Series
Only changes state when tripped by overload / short-circuit / phase loss; remains inactive during manual ON/OFF operations, used exclusively for fault alarm signals.
- AGM2-01-PKZ0|2NC (standard for engineering projects)
PKZM0 Full Model List
1) Standard Screw Terminal Models (Base Version, No Suffix)
| Model | Adjustment Range Ir | Matched Motor (400 V) | Eaton Order No. |
| PKZM0-0,16 | 0.10~0.16 A | 0.04 kW | 72730 |
| PKZM0-0,25 | 0.16~0.25 A | 0.06 kW | 72731 |
| PKZM0-0,4 | 0.25~0.40 A | 0.09 kW | 72732 |
| PKZM0-0,63 | 0.40~0.63 A | 0.18 kW | 72733 |
| PKZM0-1 | 0.63~1.00 A | 0.25 kW | 72734 |
| PKZM0-1,6 | 1.00~1.60 A | 0.37 kW | 72735 |
| PKZM0-2,5 | 1.60~2.50 A | 0.55 kW | 72736 |
| PKZM0-4 | 2.50~4.00 A | 1.1 kW | 72737 |
| PKZM0-6,3 | 4.00~6.30 A | 2.2 kW | 72738 |
| PKZM0-10 | 6.30~10.0 A | 4.0 kW | 46937 |
| PKZM0-12 | 8.00~12.0 A | 5.5 kW | 278486 |
| PKZM0-16 | 10.0~16.0 A | 7.5 kW | 46938 |
| PKZM0-20 | 16.0~20.0 A | 9.0 kW | 46988 |
| PKZM0-25 | 20.0~25.0 A | 11 kW | 46989 |
| PKZM0-32 | 25.0~32.0 A | 15 kW | 278489 |
Suffix Definition (Same current rating, only terminal/function differs)
- -PI: Push-in spring terminals (tool-free wiring); example: PKZM0-16-PI
- -C: Older spring clamp version (same function as PI)
- -EA: Export overseas standard model (identical construction to domestic standard version)
- -T: Transformer protection variant (NO phase-failure protection, only thermal + short-circuit trip); example: PKZM0-0,63-T
- /AK: Thumb-lock rotary handle, field padlockable
- -SPI32: Mixed terminals: line-side screw, load-side push-in
2) PKZM01 Compact Series (Toggle handle, NO phase-failure protection; only overload + short-circuit trip)
Note: PKZM01 has no phase-loss protection; only for small motors without single-phasing risk.
| Model | Adjustment Current Range |
| PKZM01-0.4 | 0.25~0.4 A |
| PKZM01-0.63 | 0.4~0.63 A |
| PKZM01-1 | 0.63~1 A |
| PKZM01-1.6 | 1~1.6 A |
| PKZM01-2.5 | 1.6~2.5 A |
| PKZM01-4 | 2.5~4 A |
| PKZM01-6.3 | 4~6.3 A |
| PKZM01-10 | 6.3~10 A |
| PKZM01-12 | 8~12 A |
| PKZM01-16 | 10~16 A |
| PKZM01-20 | 16~20 A |
| PKZM01-25 | 20~25 A |
3) Higher-Current PKZM4 Series (16~63 A, fully interchangeable accessories with PKZM0)
PKZM4-16 / PKZM4-20 / PKZM4-25 / PKZM4-32 / PKZM4-40 / PKZM4-50 / PKZM4-63
4) Model Naming Rule (Quick Selection)
PKZM0 16 PI
- PKZM0 = Motor-protective circuit breaker (with phase-failure protection, rotary handle)
- Numeric value = Maximum adjustable current (16 = 10~16 A)
- Suffix = Terminal type / special function
5) Standard Accessory List (Fits all PKZM0 variants)
1) Auxiliary Contacts (Position feedback)
NHI-E-11-PKZ0 (Front-mounted: 1NO+1NC)
NHI11-PKZ0 (Side-mounted: 1NO+1NC)
2) Fault Trip Contacts (Only triggered by overload/phase loss/short-circuit)
AGM2-01-PKZ0 (2NC, standard for site engineering)
3) Voltage Releases (Only one can be fitted at a time, not both together)
U-PKZ0 Undervoltage release (24VDC / 110V / 230V / 400V)
A-PKZ0 Shunt trip release (24VDC / 110V / 230V / 400V)
4) Mechanical Accessories
PKZ0-XRH: Extended rotary handle for cabinet door mounting (padlockable)
CL-PKZ0: Phase barrier
B-PKZ0: Parallel busbar for multiple units
6) Selection Guidelines
- Require phase-failure protection → Choose PKZM0; No phase-loss risk & cost-sensitive → Choose PKZM01.
- Remote tripping → Select A-PKZ0 shunt trip; Anti-restart on power failure → Select U-PKZ0 undervoltage release (cannot mount both).
- Frequent on-site wiring → Prefer -PI push-in terminal version; General installation → Standard screw terminal model.