Full Model: QUINT4-UPS/24DC/24DC/40/PN
Product Category: 35mm DIN rail mounted 24VDC uninterruptible power supply (DC-UPS, QUINT4 series, with IQ-Technology and PROFINET interface)
✅ Core Technical Specifications
Order No.: 2907079
Input: 24 V DC, operating range 18…30 VDC
Output: 24 V DC / 40 A, rated power 960 W
Communication: PROFINET (PN); built-in web server; remote reading of battery status, load conditions and fault diagnostics
Mounting: 35 mm DIN rail
Terminals: Screw-type terminals
Charging current: 5 A; compatible with VRLA lead-acid and lithium-ion battery modules
Deep-discharge protection threshold: 19.2 V DC
Key Features: IQ intelligent battery recognition; auto-detect battery capacity to calculate backup runtime; battery temperature monitoring; fault alarm & relay dry contact output
📌 Model Breakdown
QUINT4-UPS /24DC/24DC /40 /PN
- QUINT4-UPS: 4th-generation QUINT series DC-DC industrial UPS
- 24DC: 24 V DC input
- 24DC: 24 V DC output
- 40: Rated output current = 40 A
- PN: PROFINET industrial Ethernet interface (other variants: USB / EIP / EC)
🧩 Same Series 40A Model Comparison
| Full Model | Order No. | Communication Interface |
| QUINT4-UPS/24DC/24DC/40 | 2907077 | No communication (dry contact only) |
| QUINT4-UPS/24DC/24DC/40/USB | 2907078 | USB-Modbus RTU |
| QUINT4-UPS/24DC/24DC/40/PN | 2907079 (Your model) | PROFINET |
| QUINT4-UPS/24DC/24DC/40/EIP | 2907080 | EtherNet/IP |
| QUINT4-UPS/24DC/24DC/40/EC | 2907081 | EtherCAT |
🔋 Compatible Battery Modules (sold separately)
VRLA Lead-Acid (AGM)
UPS-BAT/VRLA/24DC/1.3AH
UPS-BAT/VRLA/24DC/3.4AH
UPS-BAT/VRLA/24DC/7.2AH
Li-ion Lithium Battery
UPS-BAT/LI-ION/24DC/128WH
UPS-BAT/LI-ION/24DC/284WH
Batteries can be paralleled for extended runtime; IQ-Technology automatically identifies battery type without manual capacity setting
📋 Typical Application Scenarios
24VDC power fail protection for PLCs, servo controllers and industrial PCs on automated production lines
Control cabinets in rail transit, warehousing & logistics, metallurgy and petrochemical industries requiring continuous power supply
PROFINET network projects with remote monitoring of UPS operation, battery life and backup runtime via host PLC
📎 Certifications & Environmental Data
Standards: IEC 61010, EN 61000 industrial EMC; marine certification available
Protection Class: IP20 (for cabinet installation only)
Shock & Vibration: Complies with IEC 60068-2-27 (30g shock resistance)
🔧 Troubleshooting Guide
- No output: Verify 24VDC input, battery wiring and deep-discharge lockout
- PROFINET communication failure: Confirm IP address, check RJ45 cabling and view PN status via built-in web page
- Shortened backup time: Battery aging; check battery SOH (State of Health) via IQ diagnostic page
- Charging failure: Mismatched battery type, abnormal temperature or loose wiring
Application Case: Phoenix QUINT4 DC-UPS (including 2907079 PROFINET version)
Core advantages: DIN rail 24VDC uninterruptible power, IQ smart battery management, industrial bus communication (PN/EIP/EC/USB), battery SOH diagnosis, cold start and controlled safe shutdown; ideal for EtherCAT / PROFINET systems
3) 20A High Power (5A charging current)
| Full Model | Order No. | Communication |
| QUINT4-UPS/24DC/24DC/20 | 2907071 | No communication |
| QUINT4-UPS/24DC/24DC/20/USB | 2907072 | USB-Modbus RTU |
| QUINT4-UPS/24DC/24DC/20/PN | 2907073 | PROFINET |
| QUINT4-UPS/24DC/24DC/20/EIP | 2907074 | EtherNet/IP |
| QUINT4-UPS/24DC/24DC/20/EC | 2907076 | EtherCAT |
4) 40A Ultra High Power (Your model, 5A charging current)
| Full Model | Order No. | Communication |
| QUINT4-UPS/24DC/24DC/40 | 2907077 | No communication (dry contact) |
| QUINT4-UPS/24DC/24DC/40/USB | 2907078 | USB-Modbus RTU |
| QUINT4-UPS/24DC/24DC/40/PN | 2907079 (Your model) | PROFINET |
| QUINT4-UPS/24DC/24DC/40/EIP | 2907080 | EtherNet/IP |
| QUINT4-UPS/24DC/24DC/40/EC | 2907081 | EtherCAT |
III Model Naming Rule
QUINT4-UPS / 24DC / 24DC / 40 / PN
- QUINT4-UPS: 4th-generation intelligent DC UPS with IQ battery management
- 24DC: 24 V DC input voltage
- 24DC: 24 V DC output voltage
- 40: Rated output current (5/10/20/40 A available)
- Suffix: No suffix = no communication; USB/PN/EIP/EC = corresponding industrial bus interface
IV Compatible Battery Modules (full series compatible, auto-recognition via IQ)
VRLA Lead-Acid (AGM)
UPS-BAT/VRLA/24DC/1.3AH (Order No. 2320296)
UPS-BAT/VRLA/24DC/3.4AH (Order No. 2320306)
UPS-BAT/VRLA/24DC/7.2AH (Order No. 2320307)
Li-ion Lithium Battery (long cycle life, wide temperature range)
UPS-BAT/LI-ION/24DC/128WH (Order No. 1396415)
UPS-BAT/LI-ION/24DC/284WH (Order No. 1460923)
V General Common Parameters (applies to entire QUINT4-UPS range)
Input voltage range: 18~30 VDC
Seamless switchover time: <10 ms
Cold start support (power on solely from battery without mains power)
IQ Functions: Auto-detect battery type & capacity; SOC/SOH health monitoring; temperature-compensated charging; deep-discharge protection
Output Boost: 125% static overload; 200% dynamic overload (5 seconds); SFB selective fuse breaking protection
VI Quick Selection Guide (40A range, for 2907079)
- Standard cabinet without bus communication: Choose 2907077
- Local PC commissioning & USB parameter reading: Choose 2907078
- PROFINET bus (S7‑1200 / S7‑1500 PLC): Choose 2907079
- EtherNet/IP (Rockwell PLC): Choose 2907080
- EtherCAT (Beckhoff / Inovance bus): Choose 2907081