Model Breakdown Code Description A9F18325 Official order number for Schneider Electric Acti9 iC65N Miniature Circuit Breaker IC65N Product series: Acti9 iC65 series, N-type breaking capacity (6o), thermal-magnetic trip unit 3P Number of poles: 3 postes (3-phase 3-wire), can switch off three phases simultaneously C25A C-curve tripping, rated current 25A (at 30°C) Key Technical Parameters Item ...

  • Detalhes do produto
  1. Análise do modelo
CodeDescrição
A9F18325Official order number for Schneider Electric Acti9 iC65N Disjuntor Miniatura
IC65NSérie de produtos: Acti9 iC65 series, N-type breaking capacity (6o), thermal-magnetic trip unit
3PNumber of poles: 3 postes (3-phase 3-wire), can switch off three phases simultaneously
C25AC-curve tripping, rated current 25A (at 30°C)
  1. Principais parâmetros técnicos
ItemEspecificação
MarcaSchneider Electric
Série de produtosActi9 iC65N
TipoDisjuntor Miniatura (MCB), viagem termomagnética
Corrente nominal25UM (at 30°C)
Poloneses3P (3 protective poles)
Curva de tropeçoC-curve (instantaneous trip at 5–10In, for distribution and lighting circuits)
Quebrando Capacidade6o (compliant with IEC/EN 60898-1)
Tensão nominal400V e (3-fase), 230V e (monofásico)
Rated Frequency50/60Hz
Montagem35mm standard DIN rail mounting
Ambient ConditionsTemp: -25°C ~ +40°C, altitude ≤2000m, umidade ≤95% (sem condensação)
ProteçãoProteção contra sobrecarga (thermal trip) e proteção contra curto-circuito (magnetic trip)
  1. Product Features
  2. Alta confiabilidade: Thermal-magnetic tripping provides accurate overload and short-circuit protection
  3. Projeto Modular: Tamanho compacto, saves panel space, easy installation and maintenance
  4. Wide Application: For all low-voltage distribution systems: residencial, commercial and industrial
  5. Certifications: Em conformidade com IEC/EN 60898-1, GB10963.1 and other international & national standards
  6. Long Service Life: Mechanical life ≥20,000 operations, electrical life ≥5,000 operations
  7. Applications

3‑phase distribution systems: Overload and short-circuit protection for 3‑phase circuits

Lighting circuits: 3‑phase lighting protection in large commercial buildings and industrial plants

Power equipment: Control and protection of small 3‑phase motors, bombas, fãs, etc..

Distribution boards / cabinets: Main or branch switch for low-voltage distribution systems

  1. Replacement Models & Cross-Brand Comparison

5.1 Schneider Same-Series Replacements

ModeloDifferenceApplication Change
A9F1832020UM, C-curve, 3PFor lower load current
A9F1833232UM, C-curve, 3PFor higher load current
A9F1932525UM, D-curve, 3PFor inductive loads such as motors
A9F1822525UM, C-curve, 2PSingle-phase circuit protection
  1. Instalação & Usage Notes
  2. Antes da instalação, confirm model matches system parameters: check rated current, poles and tripping curve
  3. Must be mounted on standard 35mm DIN rail for secure installation
  4. Ensure terminals are tightly connected to avoid overheating
  5. Inspect breaker status regularly to ensure proper tripping mechanism
  6. After a fault trip, eliminate the cause before manually resetting
  7. Recomendações de seleção
  8. C-curve is suitable for distribution and lighting circuits; not recommended for frequent-start motors (use D-curve)
  9. 3P breakers are for 3-phase 3-wire systems; use 4P if neutral protection is required
  10. 6kA breaking capacity is for general industrial & edifícios comerciais; use higher-rated types (e.g. H-type 10kA) for high short-circuit current

Recommended Replacements for A9F18325-IC65N-3P-C25A

  1. Direct Replacements (Schneider Electric)
Replacement ModelOrder No.Parâmetros principaisDifferenceApplication
IC65N 3P C25AA9F183253P, C25A, 6oIdentical, originalSame distribution protection
IC65N 3P C20AA9F183203P, C20A, 6o20UM (lower)3-phase lighting / distribution with lower load
IC65N 3P C32AA9F183323P, C32A, 6o32UM (higher)3-phase lighting / distribution with higher load
IC65N 3P D25AA9F193253P, D25A, 6oD-curve (10–14In trip)3-phase motors, compressors and inductive loads
IC65H 3P C25AA9F283253P, C25A, 10o10o (higher breaking capacity)Industrial environments with high short-circuit current
IC65L 3P C25AA9F383253P, C25A, 15o15o (highest level)Critical power systems with very high fault current
IC65N 4P C25AA9F184254P, C25A, 6o4 postes (includes neutral protection)3-phase 4-wire systems
  1. Upgraded Replacements (New Schneider Series)
SérieModeloOrder No.Upgrade AdvantageApplication
Acti9 IC60NIC60N 3P C25AA9F58325More compact, higher short-circuit withstandNew projects with limited panel space
Acti9 IC40NIC40N 3P C25AA9P58325Ultra-slim (18mm/pole), space-savingSmall distribution boards, residencial / comercial
  1. Cross-Brand Equivalent Replacements
MarcaModeloParâmetros principaisMatchCusto
ABBS203-C253P, C25A, 6o★★★★★Médio, reliable quality
Siemens5SY6325-7CC3P, C25A, 6o★★★★★Médio, German quality
CHINTNXB-63-3P C253P, C25A, 6o★★★★☆Lower, high-quality domestic
DeliciosoCDM30s-63C25/33003P, C25A, 6o★★★★☆Lower, cost-effective
Interruptor ChangshuCH1-63C25/3P3P, C25A, 6o★★★★☆Lower, well-known domestic brand
LiangxinNDM1-63C25/3P3P, C25A, 6o★★★★☆Lower, suitable for industry

Key Selection Advice for Replacements

  1. Direct equivalent: Prefer IC65N 3P C25A (A9F18325) to match original protection characteristics
  2. Tripping curve:

C-curve (5–10 pol.): distribution & iluminação

D-curve (10–14In): motores, transformers to avoid nuisance tripping

  1. Capacidade de ruptura:

6o (N-type): general commercial & residencial

10o (H-type): industrial & large commercial

15o (L-type): critical systems with high fault current

  1. Poloneses:

3P: 3-phase 3-wire (no neutral protection)

4P: 3-phase 4-wire (fase + proteção neutra)

  1. Brand choice:

Internacional (ABB, Siemens): stable, for critical equipment & export projects

Doméstico (CHINT, Delicioso): cost-effective, for general industrial & civil projects

Anterior: