Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

CHINT NXMLE-630S/4300A-630A - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

disjuntor/

CHINT NXMLE-630S/4300A-630A

Model Explanation Model Part Description NXMLE CHINT Kunlun Series Residual Current Operated Circuit Breaker (MCCB with earth leakage protection) 630 Frame rating current 630A S Breaking capacity class S (25kA at AC400V/415V, ultimate breaking capacity 50kA) 4300A 4P (three-phase four-wire, 3P+N), thermal-magnetic trip unit, standard version without accessories 630A Rated operational current 630A Key Parameters ...

  • Detalhes do produto

Model Explanation

Model PartDescription
NXMLECHINT Kunlun Series Residual Current Operated Disjuntor (MCCB with earth leakage protection)
630Frame rating current 630A
SBreaking capacity class S (25kA at AC400V/415V, ultimate breaking capacity 50kA)
4300UM4P (three-phase four-wire, 3P+N), thermal-magnetic trip unit, standard version without accessories
630UMRated operational current 630A
  1. Parâmetros principais
Categoria de parâmetroValueNotas
Parâmetros Básicos
TypeMoulded Case Circuit Breaker with Earth Leakage Protection (Disjuntor de corrente residual)Provides overload, short-circuit and earth leakage protection
Poloneses4P (3P+N)Three phases + neutral
Tipo de viagemThermal-magnetic (Curve C)For power distribution protection
Rated insulation voltage Ui800V e
Rated operational voltage Ue400V/415V AC (4P)
Rated frequency50/60Hz
Current Parameters
Frame current Inm630UM
Rated current In630UM
Residual operating current Iホ馬100/200/300mA adjustableSelectable per requirements
Residual current tripping time0.3é (padrão)Fast personal safety protection
Quebrando Capacidade
Rated service breaking capacity Ics25o (AC400V)Classe S
Ultimate short-circuit breaking capacity Icu50o (AC400V)
Funções de proteçãoLong-time overload, short-time delay, instantaneous short-circuit, earth leakage protectionFull protection for circuits and equipment
  1. Mounting Dimensions
Mounting TypeDimensões (W×H×D, milímetros)Notas
Fixed (front/rear connection)280×280×100Standard 4P dimensions
Plug-in type280×280×120Including plug-in base
Mounting modeFixed / Plug-in
Connection typeFront / Rear connectionRear connection requires special kit
Terminal sizeM12 hex socket screwFor large cross-section cables
  1. Applications
  2. Low-voltage distribution systems: Main or branch protection for three-phase four-wire circuits up to 630A
  3. Industrial equipment protection: Protect motors, transformers and other electrical devices against overload, short-circuit and earth leakage
  4. Building electrical: Main and sub-distribution boards in commercial buildings and industrial plants
  5. Personal safety: Indirect contact protection against fatal electric shock
  6. Electrical fire prevention: Protection against earth fault current induced electrical fires
  7. Operating Notes
  8. Ambient conditions:

Temperatura ambiente: -25℃ ~ 70℃

Altitude: ≤ 2000m (derate if exceeded)

Umidade: ≤ 95% (sem condensação)

Avoid flammable, explosive or highly corrosive environments

  1. Wiring requirements:

Strictly separate N line and phase lines; N line must pass through the leakage detection transformer

Terminals must be securely tightened to avoid overheating

Cable cross-section suitable for 630A (≥ 185mm² copper recommended)

  1. Selection matching:

Residual current: 300mA for general distribution, 30mA for personal protection (special model)

Breaking capacity must match system short-circuit current; Class S suitable for general industry

  1. Maintenance:

Test monthly using the test button

Regularly check terminals for overheating

Keep clean to ensure heat dissipation

  1. Solução de problemas
SymptomPossíveis causasSoluções
Trips immediately after closing1. Short circuit1. Locate short circuit
2. Residual current too low2. Adjust to suitable Iホ馬
3. Trip unit fault3. Replace trip unit
Fails to trip on overload1. Thermal trip failure1. Replace thermal trip
2. Over-current setting too high2. Reset current setting
Fails to trip on earth leakage1. Leakage module fault1. Replace leakage module
2. N line not through CT2. Rewire correctly
3. Test button fault3. Replace test button
Excessive heating during operation1. Loose connections1. Tighten terminals
2. Sobrecarga2. Reduce load
3. Poor ventilation3. Improve cooling
  1. Brand Alternatives
MarcaModelo AlternativoCompatibilidade
SchneiderNSX630S TM630D 4P 3D (with Vigi module)Same breaking capacity and rated current, similar dimensions
ABBTmax T6H630 PR221DS-LSI R630 4P (with RC221)Matching protection, separate leakage module required
Siemens3VL630N630 4P (with 30mA leakage add-on)Same frame and rated current, compatible mounting
DeliciosoCDM3L-630S/4300A-630ADirect Chinese alternative, identical dimensions and parameters
Changshu SwitchCM3L-630S/4300A-630AMatching technical data, compatible mounting
  1. Resumo

CHINT NXMLE‑630S/4300A‑630A is a high-performance 4P earth leakage MCCB for 630A three‑phase four‑wire distribution systems. It provides overload, short‑circuit and earth leakage protection, with Class S breaking capacity suitable for general industrial applications. Its thermal‑magnetic trip (Curve C) is ideal for distribution, effectively protecting equipment and personnel. Correct selection of residual current and proper installation are essential; regular maintenance ensures long service life and reliable protection.

CHINT NXMLE-630S/4300A-630A Mounting Dimensions

  1. Overall Mounting Dimensions

Mounting dimensions vary slightly by installation type. Official standard values:

Mounting TypeDimensões Gerais (W×H×D, milímetros)Panel Cutout (milímetros)Notas
Fixed (front/rear)280×280×100245×245 (bolt centers)Standard 4P, front/rear fixed same
Plug-in280×280×120245×245 (base centers)Includes base depth
Rear connection (special)280×280×100245×245Requires rear connection kit
  1. Key Dimension Details
  2. Largura (C): 280mm – Standard 4P MCCB width, compatible with mainstream switchgear
  3. Altura (H): 280mm – Including operating handle, consistent with Kunlun 630A frame
  4. Profundidade (D):

Tipo fixo: 100milímetros

Plug-in type: 120milímetros (body + base)

  1. Mounting bolts: M12 hex socket for high-current 630A application
  2. Mounting plate thickness: ≥ 6mm recommended for strength and cooling
  3. Minimum clearances: ≥25mm left/right, ≥50mm top/bottom for operation and ventilation
  4. Mounting Methods
  5. Fixed mounting: Most common, bolted directly to panel; front or rear connection
  6. Plug-in mounting: Uses dedicated base for fast replacement, suitable for frequent maintenance
  7. Rear connection: Terminals on rear side, saves front panel space and improves layout
  8. Notas de instalação

Install vertically or horizontally, tilt angle ≤ 15°

Correctly separate N and phase lines; N must pass through leakage transformer

Check and tighten all terminals after installation

Allow sufficient ventilation to prevent overheating

Anterior:

Deixe uma resposta

Deixe um recado